Anybus-E300-MBTCP Startup Guide

E300 Communication Module for Modbus TCP

Important User Information

Disclaimer

The information in this document is for informational purposes only. Please inform HMS Networks of any inaccuracies or omissions found in this document. HMS Networks disclaims any responsibility or liability for any errors that may appear in this document. HMS Networks reserves the right to modify its products in line with its policy of continuous product development. The information in this document shall therefore not be construed as a commitment on the part of HMS Networks and is subject to change without notice. HMS Networks makes no commitment to update or keep current the information in this document. The data, examples and illustrations found in this document are included for illustrative purposes and are only intended to help improve understanding of the functionality and handling of the product. In view of the wide range of possible applications of the product, and because of the many variables and requirements associated with any particular implementation, HMS Networks cannot assume responsibility or liability for actual use based on the data, examples or illustrations included in this document nor for any damages incurred during installation of the product. Those responsible for the use of the product must acquire sufficient knowledge in order to ensure that the product is used correctly in their specific application and that the application meets all performance and safety requirements including any applicable laws, regulations, codes and standards. Further, HMS Networks will under no circumstances assume liability or responsibility for any problems that may arise as a result from the use of undocumented features or functional side effects found outside the documented scope of the product. The effects caused by any direct or indirect use of such aspects of the product are undefined and may include e.g. compatibility issues and stability issues.

Document Conventions

Numbered lists indicate tasks that should be carried out in sequence:

  1. First do this
  2. Then do this

Bulleted lists are used for:

▶️ An action

[result] and a result

User interaction elements (buttons etc.) are indicated with bold text.

Program code and script examples

Cross-reference within this document: Document Conventions, p. 1

External link (URL): www.hms-networks.com

WARNING: Instruction that must be followed to avoid a risk of death or serious injury.

Caution: Instruction that must be followed to avoid a risk of personal injury.

Instruction that must be followed to avoid a risk of reduced functionality and/or damage to the equipment, or to avoid a network security risk.

[i] Additional information which may facilitate installation and/or operation.

Trademarks

Anybus® is a registered trademark of HMS Networks AB. All other trademarks are the property of their respective holders.

Safety

Intended Use

The intended use of this equipment is as a communication interface. The communication module allows an E300 Relay to be integrated into an automation system. The communication module has two RJ45 connectors that function as a switch. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

General Safety

WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from contaminants.

WARNING: Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice.

WARNING: In case of malfunction or damage, no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product.

Preparation

Support and Resources

For additional documentation and technical support, please visit www.anybus.com/support and www.rockwellautomation.com/support.

Recommended Ethernet Cables

E300 Communication Module Network Information

Label with Network Information: MAC Id, Serial Number and Firmware Revision.

Installation

Attach the E300 Communication Module

  1. Pull out the locking tab located on the upper left side of the E300 Relay Control Module.
  2. Attach the E300 Communication Module to the E300 Relay Control Module.
  3. To lock the modules, push in the locking tab located on the upper left side of the E300 Relay Control Module.

Connecting to Modbus TCP Network

The E300 Communication Module has two RJ45 ports that act as an Ethernet switch. The E300 Communication Module listens for incoming Modbus TCP connections on TCP port 502. Up to four simultaneous Modbus TCP connections are supported.

Connecting to Ground

Motor protection function: Ground Fault – zero sequence method (50 N)

▶️ Connect the Green Wire to Functional Earth (Ground).

IP Address Setting Via Rotary Switches

Node AddressFunction
001 - 254Set IP Address to 192.168.1.xxx
255 - 887Configure the module to “Use configured settings”, values from non volatile storage.
889 - 999Reset to factory defaults
000Configure the module to “Use configured settings”, values from non volatile storage. Enter Administration mode

[power cycle] A power cycle is required for the changes to take effect.

LED Guide

E300 Communication Module LED Indicators

PositionLED Indicator
ALink 1 Status and RJ45 Port G status
BLink 2 Status and RJ45 Port H status
CNetwork Status
DPower

E300 Communication Module LED Indicators (continued)

PositionLED Indicator
ETRIP/WARN
FModule Status

Test/Reset

Test: Ensure that the E300 Relay is untripped. To open the trip relay contact: Press the Test/Reset button for 2 seconds.

Reset: Ensure that the E300 Relay is tripped. To close the trip relay contact: Press and immediately release the Test/Reset button.

Models: E300-MBTCP, E300 Communication Module for Modbus TCP

File Info : application/pdf, 2 Pages, 1.20MB

PDF preview unavailable. Download the PDF instead.

hms-sp2873 1-0

References

PTC Arbortext Publishing Engine PDFlib PDI 9.0.7p3 (C /Win64)

Related Documents

Preview Anybus CompactCom 40 EtherCAT Network Guide
Comprehensive network guide for the Anybus CompactCom 40 EtherCAT communication module by HMS Networks, detailing features, operation, and implementation for industrial automation applications.
Preview Anybus CompactCom 40 DeviceNet Network Guide
Comprehensive guide detailing the features, operation, and technical specifications of the Anybus CompactCom 40 DeviceNet communication module for industrial automation networks. Includes information on CIP objects, DeviceNet implementation, and host application integration.
Preview Anybus CompactCom 40 EtherNet/IP Transparent Ethernet Network Guide
This network guide provides comprehensive information on the Anybus CompactCom 40 EtherNet/IP module, focusing on its Transparent Ethernet functionality. It details features, basic operation, implementation specifics, and technical specifications for industrial network integration.
Preview AnyBus-X J1939 to Modbus Interface User Manual
User manual for the AnyBus-X J1939 to Modbus Interface, detailing installation, configuration, operation, and specifications for connecting J1939 heavy-duty vehicle networks with Modbus RTU master devices.
Preview Anybus Communicator - EtherCAT: Serial to EtherCAT Gateway | HMS Networks
Detailed datasheet for the Anybus Communicator - EtherCAT (ABC3061) by HMS Networks, a robust serial to EtherCAT gateway with extensive features for industrial automation, including protocol conversion and high data transfer capabilities.
Preview HMS IPconfig User Manual - Anybus Networks
User manual for HMS IPconfig, a Windows-based tool by Anybus (HMS Networks) for configuring TCP/IP settings on HMS devices. Includes installation, device scanning, IP/DNS configuration, and password management.
Preview ProfiHub A5 User Manual - Industrial PROFIBUS DP Repeater by Anybus (HMS Networks)
This user manual provides detailed information on the Anybus ProfiHub A5, a 5-channel PROFIBUS DP spur and repeater component. It covers product features, application areas, installation instructions, technical specifications, and troubleshooting for industrial automation networks.
Preview Anybus Wireless Bolt RJ45 PoE Startup Guide - HMS Networks
Get started with the Anybus Wireless Bolt RJ45 PoE from HMS Networks. This startup guide covers installation, configuration, and technical specifications for seamless wireless industrial networking.