Instruction Manual for YHDC models including: TST024L, TST024L Split Core Current Transmitter, Split Core Current Transmitter, Current Transmitter, Transmitter

TST024L英文版


File Info : application/pdf, 3 Pages, 848.96KB

PDF preview unavailable. Download the PDF instead.

TST024L e41f8fb3-60e2-4ea7-b67b-f171ea8bd79d ?v=1664354017
TST024L
Split core current transmitter
Split coresuspension indtallationoutput with cable.Detect AC current. High insulation between primary and secondary circuits.

Installation diagram

Product features
·Light weight ·Low power consumption ·Good linearity ·No insertion loss ·Fast response time ·Good anti-interference ability

1.Loosen the card buckle

2.Open up

Product application

·Railway

·Metallurgical

·Welding machine

·Robot

·Motor

·Inverter power supply ·Variable frequency governor

3.In the lead

4.Fasten card buckle

·Uninterrupted power supply and communication power supply

www.poweruc.pl 

E l e c t r i c a l p a r a m e t e r s : The following parameters are typical values and actual values
will be subject to product testing

Remarks

Rated input Input measurement range Rated output Accuracy Linearity Supply voltage(±5%) Current consumption Load impedance Zero offset voltage Response time weight Operating temperature Storage temperature Band width Delectric strength

100A

200A

300A

120A

240A

360A

0-20mA/4-20mA/0-5V/1-5V/0-10V

0.5%

Standard input
Default is 1.2 times the input rating Output one of five
0-10V output +24V power supply

0.5%

+12V / +24V

Supply voltage range ±5%

35mA

Current type output Voltage type output 250 Typification) 10K Current type output Voltage type output

±0.08mA

±15mV

200mS

196g

Reference will be subject to the measured
TA=25 Reference will be subject to the measured Reference will be subject to the measured

-10+70

-25+70

50~400Hz

2.5KV 50Hz 1min

Instruction for use
1.Connect the wires correctly according to the marked connection mode 2.With hole measurement, response time and following the speed for the best 3.Faulty wiring can lead to product damage and output uncertainty

Safe operation:
*Please read this specification carefully before use. *When you need to move the product, please be sure to disconnect the power and all the connected cables. *If found shell, devices attached to the fixed parts, wire, or have any damaged, please immediately deal with hidden dangers. *If there is any doubt about the safe operation of the equipment, the equipment and the corresponding accessories should be closed immediately, and the fastest time for troubleshooting.
Proclamations
As our products are constantly being improved and updated, we reserve the right to modify the content of this specification at any time without prior notice.

www.poweruc.pl 

Dimensions(in mm±0.5

24

Opening angle
180°

Cable

41.4

34.2

Cable specification

0.2mmThree core shielding wire

Three core colorRedaBlackaGreen

Cable length50cm

75

gain zero
potentiometer 53

Wiring diagram
gain zero

Cable definition
Red + V Black G N D Green o u t

+
out

GND

Acquisition module

power

The auxiliary power supply with ripple small (10mV) is selected
Switch on auxiliary power
Auxiliary power is connected to the transmitter
Transmitter detects the primary current

www.poweruc.pl 



References