LUTRON HJS-0-FM VIVE Networking Wireless HUB
TYPICAL HUB – AS REQUIRED FLUSH MOUNT AND SURFACE MOUNT OPTIONS AVAILABLE BACNET INTEGRATION AVAILABLE ON CERTAIN MODELS MINIMUM OF 10′ BETWEEN HUBS ON THE SAME FLOOR
|
TYPICAL SENSORS & REMOTE CONTROLS CAN BE A MAX OF 30′ TO LOAD DEVICES – MAX OF 71′ FROM VIVE HUB AND LOCATED ON THE SAME FLOOR |
TYPICAL LOAD DEVICES CAN BE A MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME FLOOR |
TYPICAL WALLBOX LOAD CONTROLS CAN BE A MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME FLOOR |
FRONT OF HOUSE RETAIL AREA
AS REQUIRED FOR 0-10V DIMMING ZONE CONTROL
![]() RMJS-8TN-DV-B |
AS REQUIRED FOR ELV ZONE CONTROL ***DEVICE TO BE MOUNTED IN CEILING***
![]() MRF2S-6ELV120-GR |
AS REQUIRED FOR LED/INC ZONE CONTROL ***DEVICE TO BE MOUNTED IN CEILING***
![]() MRF2S-6CL-GR |
AS REQUIRED FOR TRIAC/MLV ZONE CONTROL ***DEVICE TO BE MOUNTED IN CEILING***
![]() MRF2S-6ND-120-GR |
AS REQUIRED FOR DIMMING SCENE CONTROL UP TO 10 PER MODULE
![]() PJ2-4B-GWH-XXX |
AS REQUIRED FOR SECOND FLOOR DAYLIGHT SENSING WHERE APPLICABLE MAX OF 1 PER MODULE
![]() LRF2-DCRB-WH |
BREAK ROOM
AS REQUIRED FOR VACANCY SENSING UP TO 10 PER MODULE
![]() LRF2-VCR2B-P-WH |
FOR USE WHEN DAYLIGHT SENSING IS REQUIRED
AS REQUIRED FOR DIMMING ZONE CONTROL TYPICAL OF 1 PER DIMMING ZONE
![]() PJ2-3BRL-GWH-XXX |
AS REQUIRED FOR 0-10V DIMMING ZONE CONTROL
![]() RMJS-8TN-DV-B |
AS REQUIRED FOR DAYLIGHT SENSING WHERE APPLICABLE MAX OF 1 PER MODULE
![]() LRF2-DCRB-WH |
OR
AS REQUIRED FOR NON-DIM ZONE CONTROL TYPICAL OF 1 PER NON-DIM ZONE
![]() PJ2-2B-GWH-XXX |
FOR USE WHEN DAYLIGHT SENSING IS NOT REQUIRED
![]() RMJS-16R-DV-B |
STORAGE ROOMS
AS REQUIRED FOR NON-DIMMING ZONE CONTROL
![]() MRF2S-8SSV-WH |
AS REQUIRED FOR 0-10V DIMMING ZONE CONTROL
![]() MRF2S-8SDV010-WH |
AS REQUIRED FOR ADDITIONAL VACANCY SENSING COVERAGE
![]() LRF2-VCR2B-P-WH |
TYPICAL EMERGENCY LIGHTING INTERFACES FOR USE WITH GENERATOR SYSTEMS
AS REQUIRED PER ZONE FOR CONTROL OF EMERGENCY 0-10V LOADS
![]() RMJS-8T-DV-B-EM |
AS REQUIRED PER ZONE FOR CONTROL OF EMERGENCY NON-DIM LOADS
![]() RMJS-16R-DV-B-EM |
TYPICAL EMERGENCY LIGHTING INTERFACES FOR USE WITH EITHER GENERATOR OR INVERTER SYSTEMS PROVIDED BY LVS CONTROLS – CONTACT YOUR LUTRON REPRESENTATIVE FOR MORE INFORMATION
AS REQUIRED FOR UL 924 COMPLIANCE
![]() LUT-SHUNT-D |
AS REQUIRED FOR UL 924 COMPLIANCE
![]() LUT-SHUNT LVS CONTROLS SHUNT RELAY FOR USE WITH LINE VOLTAGE SWITCHING AND DIMMING LOADS REFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS |
AS REQUIRED FOR UL 924 COMPLIANCE
![]() LUT-ALCR-D |
AS REQUIRED FOR UL 924 COMPLIANCE
![]() LUT-ALCR |
AS REQUIRED FOR UL 1008 COMPLIANCE
![]() LUT-ATS-D |
WIRING LEGEND:
![]() |
INPUT POWER (NORMAL-EMERGENCY) |
![]() |
INPUT POWER (NORMAL) |
![]() |
2 #12AWG (4 mm2) |
![]() |
0-10V SIGNAL: 2 #18AWG (1.0 mm2) |
![]() |
1-WAY RF COMMUNICATION |
![]() |
2-WAY RF COMMUNICATION |
CONCEPT DRAWING NOTES: CONTROL SYSTEM DRAWING IS PROVIDED FOR CONCEPTUAL PURPOSES ONLY AND IS NOT INTENDED FOR CONSTRUCTION. EXACT EQUIPMENT REQUIREMENTS, INCLUDING LOCATIONS AND QUANTITIES, SHOULD BE VERIFIED IN ACCORDANCE WITH THE MOST UP-TO-DATE LIGHTING/ELECTRICAL REFLECTED CEILING PLANS, LIGHTING FIXTURE SCHEDULES, PANEL SCHEDULES, CONTROL INTENT AND SPECIFICATIONS. SHADE EQUIPMENT SHOULD BE VERIFIED IN ACCORDANCE WITH ARCHITECTURAL PLANS, SPECIFICATIONS AND WINDOW SCHEDULES/DETAILS. |
LED DIMMING REQUIRES AN EXACT MATCH BETWEEN THE LED ARRAY, DRIVER AND CONTROL. LUTRON CANNOT GUARANTEE COMPATIBILITY OR PERFORMANCE WITHOUT TESTING THIS COMBINATION
TO CONFIRM WHAT PRODUCTS LUTRON HAS AVAILABLE OR WHAT INTERFACES MAY BE REQUIRED, CALL 1-877-DIM-LED8 OR CHECK LUTRON’S PRODUCT COMPATIBILITY MATRIX ON-LINE AT WWW.LUTRON.COM/LED. TO REQUEST THE TESTING OF AN LED PRODUCT BY LUTRON MANUFACTURERS CAN FILL OUT AN LED EVALUATION REQUEST FORM ON-LINE AT WWW.LUTRON.COM/LED OR CONTACT LEDS@LUTRON.COM. LUTRON CAN GUARANTEE COMPATIBILITY AND PERFORMANCE OF LUTRON HI-LUME LED DRIVERS USED WITH APPROPRIATE LUTRON CONTROLS. PLEASE REFER TO THE SPECIFICATION SUBMITTAL SHEET FOR FURTHER INFORMATION. IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING 0-10V CONTROL, PERFORMANCE AND COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. PRODUCTS FOLLOWING THE IEC STANDARD 60929 ARE MORE LIKELY TO PROVIDE ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT ACCEPTABILITY IS UP TO THE USER’S DISCRETION. IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING PHASE CONTROL, PERFORMANCE AND COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. ELV PRODUCTS PROVIDING HIGH END AND LOW END TRIM ADJUSTMENTS OR LUTRON HI-LUME 1% 2-WIRE DRIVERS ARE MORE LIKELY TO PROVIDE ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT ACCEPTABILITY IS UP TO THE USER’S DISCRETION. |
LUTRON NOTES:
ALL DIMMING BALLASTS TO BE LUTRON ECOSYSTEM, ECOSYSTEM H-SERIES, OR HI-LUME 3D TYPE UNLESS OTHERWISE NOTED.
ALL DIMMING DRIVERS TO BE LUTRON ECOSYSTEM DRIVERS: HI-LUME 1%; HI-LUME 1% WITH SOFT-ON, FADE-TO-BLACK; 5-SERIES; OR HI-LUME PREMIER 0.1% UNLESS OTHERWISE NOTED.
E.E. TO CONFIRM ALL CIRCUITING REQUIREMENTS.
ARCHITECT TO VERIFY QUANTITY, LOCATION & FINISH OF ALL CONTROLS.
LUTRON FIELD SERVICE COMMISSIONING INCLUDED IN ALL SYSTEMS INITIATES AN 2 YEAR LIMITED WARRANTY. THE ELECTRICAL CONTRACTOR MUST CONTACT LUTRON (1-844-588-7661) TO SET UP VISIT WITH 10 DAYS NOTICE.
LUTRON SERVICES
ONSITE PROGRAMMING – 4 HOUR BLOCK (LSC-OS-PROG4–SP) | ONSITE SYSTEM PROGRAMMING VISIT – UP TO 4 CONTIGUOUS HOURS OF SYSTEM PROGRAMMING DELIVERED BY A LUTRON SERVICES REPRESENTATIVE . THE SYSTEM WILL BE PROGRAMMED PER AN APPROVED SEQUENCE OF OPERATION. QUANTITY DICTATES THE NUMBER OF 4-HOURVISITS PURCHASED. | |
REMOTE PROGRAMMING – 4 HOUR BLOCK (LSC–RMT-PROG4-SP) | REMOTE SYSTEM PROGRAMMING VISIT – UP TO 4 CONTIGUOUSHOURS OF SYSTEM PROGRAMMING DELIVERED BY A DEDICATED FACTORY CERTIFIED REMOTE TECHNICIAN EITHER VIA A REMOTE NETWORK CONNECTION OR WITH THE ASSISTANCE OF AN ELECTRICAL CONTRACTOR OVER THE PHONE. THE SYSTEM WILL BE PROGRAMMED PER AN APPROVED SEQUENCE OF OPERATION. QUANTITY DICTATES THE NUMBER OF 4-HOUR SESSIONS PURCHASED. | |
ONSITE SCENE & LEVEL TUNING (LSC-AF–VISIT) | AN ONSITE VISIT WITH THE SPECIFIER OR CUSTOMER REPRESENTATIVE TO REVIEW DESIGN INTENT, FINE-TUNE SCENE LEVEL PROGRAMMING, AND TIMECLOCK ADJUSTMENTS. | |
ONSITE PERFORMANCE VERIFICATION WALKTHROUGH (LSC–WALK) | ONSITE WALKTHROUGH WITH FACILITY REPRESENTATIVES OR PROJECT COMMISSIONING AGENTS TO DEMONSTRATE THAT THE SYSTEM FUNCTIONALITY MEETS THE DESIGN INTENT. THIS MAY INCLUDE ANY OF THE FOLLOWING ONSITE ACTIVITIES – CONSULTATION TRAINING DEMOS, FUNCTIONAL TESTING ASSISTANCE, & INVENTORY OF LUTRON EQUIPMENT. | |
POST-STARTUP SERVICES | ||
CUSTOMER–SITE SOLUTION TRAINING (LSC-TRAINING-SP) | A VISIT TO TEACH SYSTEM USERS HOW TO OPERATE AND MAINTAIN THE LIGHTING CONTROL SYSTEM. | |
SYSTEM OPTIMIZATION (LSC-SYSOPT-SP) | ONSITE CONSULTATIVE VISIT TO IDENTIFY & IMPLEMENT LIGHTING CONTROL ADJUSTMENTS TO SAVE ADDITIONAL ENERGY & CREATE A MORE PRODUCTIVE WORK ENVIRONMENT. | |
MAINTENANCE & SUPPORT SERVICES | ||
ONSITE PROGRAMMING – 4 HOUR BLOCK (LSC-OS-PROG4–SP) | ONSITE SYSTEM PROGRAMMING VISIT – UP TO 4 CONTIGUOUS HOURS OF SYSTEM PROGRAMMING DEUVERED BY A LUTRON SERVICES REPRESENTATIVE. THE SYSTEM WILL BE PROGRAMMED PER AN APPROVED SEQUENCE OF OPERATION. QUANTITY DICTATES THE NUMBER OF 4-HOUR VISITS PURCHASED. | |
REMOTE PROGRAMMING – 4 HOUR BLOCK (LSC–RMT-PROG4-SP) | REMOTE SYSTEM PROGRAMMING VISIT – UP TO 4 CONTIGUOUSHOURS OF SYSTEM PROGRAMMING DELIVERED BY A DEDICATED FACTORY CERTIFIED REMOTE TECHNICIAN EITHER VIA A REMOTE NETWORK CONNECTION OR WITH THE ASSISTANCE OF AN ELECTRICAL CONTRACTOR OVER THE PHONE. THE SYSTEM WILL BE PROGRAMMED PER AN APPROVED SEQUENCE OF OPERATION. QUANTITY DICTATES THE NUMBER OF 4-HOUR SESSIONS PURCHASED. | |
ONSITE SCENE & LEVEL TUNING (LSC–AF-VISIT) | AN ONSITE VISIT WITH THE SPECIFIER OR CUSTOMER REPRESENTATIVE TO REVIEW DESIGN INTENT, FINE-TUNE SCENE LEVEL PROGRAMMING, AND TIMECLOCK ADJUSTMENTS. | |
ONSITE PERFORMANCE VERIFICATION WALKTHROUGH (LSC–WALK) | ONSITE WALKTHROUGH WITH FACILITY REPRESENTATIVES OR PROJECT COMMISSIONING AGENTS TO DEMONSTRATE THAT THE SYSTEM FUNCTIONALITY MEETS THE DESIGN INTENT. THIS MAY INCLUDE ANY OF THE FOLLOWING ONSITE ACTIVITIES- CONSULTATION fTRAINING DEMOS, FUNCTIONAL TESTING ASSISTANCE, & INVENTORY OF LUTRON EQUIPMENT. | |
POST-STARTUP SERVICES | ||
CUSTOMER–SITE SOLUTION TRAINING (LSC-TRAINING-SP) | A VISIT TO TEACH SYSTEM USERS HOW TO OPERATE AND MAINTAIN THE LIGHTING CONTROL SYSTEM. | |
SYSTEM OPTIMIZATION (LSC-SYSOPT-SP) | ONSITE CONSULTATIVE VISIT TO IDENTIFY & IMPLEMENT LIGHTING CONTROL ADJUSTMENTS TO SAVE ADDITIONAL ENERGY & CREATE A MORE PRODUCTIVE WORK ENVIRONMENT. | |
MAINTENANCE & SUPPORT SERVICES | ||
ENHANCED SILVER (LSC–ESS) | YEARS 1 & 2: 100% REPLACEMENT PARTS & 100% LUTRON DIAGNOSTIC LABOR COVERAGE WITH A FIRST-AVAILABLE RESPONSE TIME (SILVER PLAN); YEARS 3-5: 50% PARTS ONLY COVERAGE; YEARS 6-8: 25% PARTS ONLY COVERAGE. | |
ENHANCED GOLD (LSC-ESG) |
YEARS 1-2: 100% REPLACEMENT PARTS & 100% LUTRON LABOR COVERAGE WITH A 72-HOUR RESPONSE TIME AND AN ANNUAL (1-DAY) SCHEDULED PREVENTATIVE MAINTENANCE VISIT (GOLD PLAN); YEARS 3-5: 50% PARTS ONLY COVERAGE; YEARS 6-8: 25% PARTS ONLY COVERAGE. | |
ENHANCED PLATINUM (LSC–ESP) |
YEARS 1-2: 100% REPLACEMENT PARTS & 100% LUTRON LABOR COVERAGE WITH A 24-HOUR RESPONSE TIME AND AN ANNUAL (1-DAY) SCHEDULED PREVENTATIVE MAINTENANCE VISIT (GOLD PLAN); YEARS 3-5: 50% PARTS ONLY COVERA E; YEARS 6-8: 25% PARTS ONLY COVERAGE. | |
SILVER TECHNOLOGY SUPPORT PLAN (LSC-SILV-IW) | AN ANNUAL SERVICE PLAN THAT COVERS 100% REPLACEMENT PARTS AND 100% LUTRON DIAGNOSTIC LABOR WITH A FIRST-AVAILABLE ONSITE OR REMOTE RESPONSE TIME. | |
GOLD TECHNOLOGY SUPPORT PLAN (LSC-GOLD–IW) | AN ANNUAL SERVICE PLAN THAT COVERS 100% REPLACEMENT PARTS AND 100% LUTRON LABOR WITH A 72-HOUR ONSITE OR REMOTE RESPONSE TIME. ALSO INCLUDES AN ANNUAL (1-DAY) SCHEDULED PREVENTATIVE MAINTENANCE VISIT EACH YEAR. | |
PLATINUM TECHNOLOGY SUPPORT PLAN (LSC–PLAT–IW) | AN ANNUAL SERVICE PLAN THAT COVERS 100% REPLACEMENT PARTS AND 100% LUTRON DIAGNOSTIC LABOR WITH A 24-HOUR ONSITE OR REMOTE RESPONSE TIME. ALSO INCLUDES AN ANNUAL (1-DAY) SCHEDULED PREVENTATIVE MAINTENANCE VISIT EACH YEAR. | |
PREVENTIVE MAINTENANCE VISIT(S)
(LSC–SCH– AINT) |
YEARLY SCHEDULED MAINTENANCE VISIT TO PERFORM PREVENTIVE MAINTENANCE, MINOR PROGRAMMING, AND CONDUCT SYSTEM TRAININGS. QUANTITY IS IN ADDITION TO ANY YEARLY VISITS SPECIFIED WITH AN ENHANCED WARRANTY OR TECHNOLOGY SUPPORT PLAN. | |
ON–SITE BATTERY REP LACEMENT SE RVICE (LSC–BATT-RPL –SP) | SCHEDULED MAINTENANCE FOR BATTERY OPERATED SENSORS & KEYPADS DURING WHICH ALL BATTERIES ARE REMOVED, RECYCLED & REPLACED. THIS IS A SINGLE USE SERVICE OCCURRING 7-8 YEARS AFTER SYSTEM STARTUP IS COMPLETE TO COINCIDE WITH APPROX. 20% -30% OF BATTERY LIFE REMAINING (ASSUMING AVERAGE USE). THIS SERVICE DOES NOT COVER INTERMITTENT BATTERY FAILURE PRIOR TO THE SCHEDULED REPLACEMENT. THIS SERVICE APPLIES TO ALL BATTERY-OPERATED SENSORS & KEYPADS PURCHASED IN THE SAME BILL OF MATERIAL AS THE SERVICE. | |
PLEASE GO TO WWW.LUTRON.COM/SERVICESFOR FURTHER INFORMATION. |
TYPICAL RETAIL |
|
CONCEPT DRAWING |
|
Project Number: | TBD |
Drawn By: | ER/TMS/CR |
Drawing Revision: | 2 |
Drawing Date: | 05.11.2022 |
Sheet: | 1 OF 1 |
Lutron Electronics Co., Inc.
7200 Suter Road | Coopersburg, PA 18036 | USA
610-282-3800 | fax: 610-282-1146
Documents / Resources
![]() |
LUTRON HJS-0-FM VIVE Networking Wireless HUB [pdf] User Guide HJS-0-FM VIVE Networking Wireless HUB, HJS-0-FM, HJS-0-FM HUB, VIVE Networking Wireless HUB, Networking Wireless HUB, Networking HUB, Wireless HUB, VIVE HUB, HUB |
![]() |
LUTRON HJS-0-FM VIVE Networking Wireless HUB [pdf] User Guide HJS-0-FM VIVE Networking Wireless HUB, HJS-0-FM, HJS-0-FM HUB, VIVE Networking Wireless HUB, Networking Wireless HUB, Networking HUB, Wireless HUB, VIVE HUB, HUB |
![]() |
LUTRON HJS-0-FM VIVE Networking Wireless HUB [pdf] User Guide HJS-0-FM VIVE Networking Wireless HUB, HJS-0-FM, HJS-0-FM HUB, VIVE Networking Wireless HUB, Networking Wireless HUB, Networking HUB, Wireless HUB, VIVE HUB, HUB |