LS ELECTRIC XBL-EIMT Programmable Logic Controller

LS-ELECTRIC-XBL-EIMT-Programmable-Logic-Controller-PRODUCT

Product Information

Specifications:

  • C/N: 10310001140
  • Product: Programmable Logic Controller XGB RAPIEnet XBL-EIMT/EIMH/EIMF
  • Dimensions: 100mm

Product Usage Instructions

Installation:

  1. Ensure the power source is disconnected before installation.
  2. Mount the PLC securely in a suitable location using appropriate hardware.
  3. Connect the necessary cables and peripherals according to the provided diagram.

Setup and Configuration:

  1. Power on the PLC and access the configuration settings.
  2. Set up input and output parameters based on your specific application requirements.
  3. Save the configuration settings before proceeding.

Operation:

  1. Start the PLC by following the manufacturer’s instructions.
  2. Monitor the system for proper functionality and check for any error indicators.
  3. Interact with the PLC using the provided interface for control and monitoring purposes.

FAQ

  • Q: What should I do if the PLC displays an error code?
    • A: Refer to the user manual for a list of error codes and their corresponding solutions. If the issue persists, contact customer support for further assistance.
  • Q: Can I expand the PLC’s input/output capacity?
    • A: Yes, you can typically expand the PLC’s I/O capacity by adding expansion modules or racks. Refer to the documentation for compatible expansion options.

This installation guide provides simple function information or PLC control. Please read carefully this data sheet and manuals before using products. Especially read precautions then handle the products properly.

Safety Precautions

Meaning of warning and caution label

WARNING

  • WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury

CAUTION

  • CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices

WARNING

  1. Do not contact the terminals while the power is applied.
  2. Be sure there are no foreign metallic matters.
  3. Do not manipulate the battery(charge, disassemble, hitting, short, soldering).

CAUTION

  1. Be sure to check the rated voltage and terminal arrangement before wiring
  2. When wiring, tighten the screw of the terminal block with the specified torque range
  3. Do not install flammable things on the surroundings
  4. Do not use the PLC in an environment of direct vibration
  5. Except expert service staff, Do not disassemble or fix or modify the product
  6. Use the PLC in an environment that meets the general specifications contained in this datasheet.
  7. Be sure that external load does not exceed the rating of output module.
  8. When disposing of PLC and battery, treat it as industrial waste.
  9. I/O signal or communication line shall be wired at least 100mm away from a high-voltage cable or power line.

Operating Environment

To install, observe the below conditions

No Item Specification Standard
1 Ambient temp. 0 ~ 55℃
2 Storage temp. -25 ~ 70℃
3 Ambient humidity 5 ~ 95%RH,  non-condensing
4 Storage humidity 5 ~ 95%RH,  non-condensing
 

 

 

 

5

 

 

 

Vibration Resistance

Occasional vibration
Frequency Acceleration Amplitude Number  

 

 

IEC 61131-2

5≤f<8.4㎐ 3.5mm 10 times in each direction

for

X, Y, Z

8.4≤f≤150㎐ 9.8㎨(1g)
Continuous vibration
Frequency Acceleration Amplitude
5≤f<8.4㎐ 1.75mm
8.4≤f≤150㎐ 4.9㎨(0.5g)

Applicable Support Software

For system configuration, the following version is necessary

  1. XBC Series : SU(V1.5 or above), H(V2.4 or above), U(V1.1 or above)
  2. XEC Series : SU(V1.4 or above), H(V1.8 or above), U(V1.1 or above)
  3. XBM Series : S(V3.5 or above), H(V1.0 or above)
  4. XG5000 Software : V4.00 or above

Accessories and Cable Specifications

Cable is recommended for CAT5E over S-FTP cable. Cable types vary Depending on your system configuration and environment. Please consult a professional supplier before installation.

Electrical Characteristic

Item Unit Value Condition
Conductor resistance Ω/km 93.5 Or less 25℃
Voltage endurance(DC) V/1min 500V In air
Insulation resistance(Min) MΩ-km 2,500 25℃
Characteristic impedance 100±15 10MHz
Attenuation Db/100m Or less 6.5 10MHz
8.2 16MHz
9.3 20MHz
Near-end crosstalk Attenuation Db/100m Or less 47 10MHz
44 16MHz
42 20MHz

Parts name and Dimension (mm)

This is front part of the product. Refer to each name when operating the system. For more information, refer to user’s manual.

LS-ELECTRIC-XBL-EIMT-Programmable-Logic-Controller-FIG (2)

LED details

Silk LED Status
On Blink Off
RUN Power on and CPU normal

operation

Power off and CPU abnormal

operation

HS When High Speed Link

service is enable

When High Speed Link

service is disable

P2P When P2P service is enable When P2P service is disable
PADT When XG5000 remote

connection is enable

When XG5000 remote

connection is disable

RING CH1, CH2 Ring network establish CH1, CH2 Change from ring to line

network

 

Line network establish

RELAY When frames are relayed
LINK When network link establish
ACT  

When communication is

normal

 

CHK There are modules whose

station no. is same.

FAULT There are modules whose station no. is same with no.

of self-station.

 

 

ERR When hardware has error

Installing / Removing Modules

Here describes the method to attach each module to the base or remove it.

Installing module

  1. Eliminate the Extension Cover at the product.
  2. Push the product and connect it in agreement with Hook For Fixation of four edges and Hook For Connection.
  3. After connection, push down the Hook For Fixation and fix it completely.

Removing module

  1. Push up the Hook For Disconnection, and then detach the product with two hands.LS-ELECTRIC-XBL-EIMT-Programmable-Logic-Controller-FIG (3)

(Do not detach the product by force)

Wiring

Wiring for Communication

  1. 10/100BASE-TX’s max.extended length between nodes is 100m.
  2. This switch module provides Auto Cross Over function so the user can use both cross and direct cable.

LS-ELECTRIC-XBL-EIMT-Programmable-Logic-Controller-FIG (4)

Warranty

  • The warranty period is 36 months from the date of manufacture.
  • The initial diagnosis of faults should be conducted by the user. However, upon request, LS ELECTRIC or its representative(s) can undertake this task for a fee. If the cause of the fault is found to be the responsibility of LS ELECTRIC, this service will be free of charge.
  • Exclusions from warranty
    1. Replacement of consumable and life-limited parts (e.g. relays, fuses, capacitors, batteries, LCDs, etc.)
    2. Failures or damages caused by improper conditions or handling outside those specified in the user manual
    3. Failures caused by external factors unrelated to the product
    4. Failures caused by modifications without LS ELECTRIC’s consent
    5. Use of the product in unintended ways
    6. Failures that cannot be predicted/solved by current scientific technology at the time of manufacture
    7. Failures due to external factors such as fire, abnormal voltage, or natural disasters
    8. Other cases for which LS ELECTRIC is not responsible
  • For detailed warranty information, please refer to the user’s manual.
  • The content of the installation guide is subject to change without notice for product performance improvement.

LS ELECTRIC Co., Ltd

  • www.ls-electric.com
  • 10310001140 V4.6 (2024.6)
  • E-mail: automation@ls-electric.com
  • Headquarters/Seoul Office Tel: 82-2-2034-4033,4888,4703
  • LS ELECTRIC Shanghai Office (China) Tel: 86-21-5237-9977
  • LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China) Tel: 86-510-6851-6666
  • LS-ELECTRIC Vietnam Co., Ltd. (Hanoi, Vietnam) Tel: 84-93-631-4099
  • LS ELECTRIC Middle East FZE (Dubai, U.A.E.) Tel: 971-4-886-5360
  • LS ELECTRIC Europe B.V. (Hoofddorf, Netherlands) Tel: 31-20-654-1424
  • LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan) Tel: 81-3-6268-8241
  • LS ELECTRIC America Inc. (Chicago, USA) Tel: 1-800-891-2941
  • Factory: 56, Samseong 4-gil, Mokcheon-eup, Dongnam-gu, Cheonan-si, Chungcheongnamdo, 31226, Korea

QR Code

LS-ELECTRIC-XBL-EIMT-Programmable-Logic-Controller-FIG (1)

Documents / Resources

LS ELECTRIC XBL-EIMT Programmable Logic Controller [pdf] User Guide
XBL-EIMT, EIMH, EIMF, XBL-EIMT Programmable Logic Controller, XBL-EIMT, Programmable Logic Controller, Logic Controller, Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *