LP Building Solutions 38 Series LP Smart Side Expert Finish Lap Joint Siding
Specifications
- Product: 38 Series Brushed Smooth or Cedar Texture Prefinished Lap Joint Siding
- Manufacturer: Louisiana-Pacific Corporation
- Clearance Requirement: Minimum 2 inch (51 mm) clearance of Prefinished siding from the ground
LOUISIANA-PACIFIC CORPORATION PERIODICALLY UPDATES AND REVISES ITS PRODUCT INFORMATION AND APPLICATION, CARE, AND MAINTENANCE INSTRUCTIONS. WARRANTY REMEDIES ARE NOT AVAILABLE IF THESE INSTRUCTIONS ARE NOT FOLLOWED. THE INFORMATION IN THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE.
FIND ALL LP® SMARTSIDE® PRODUCT LITERATURE AT LPCORP.COM/SMARTSIDE
- LP® SmartSide® ExpertFinish® Trim and Siding is covered under the LP® SmartSide® Prorated 50-Year and 15-Year Limited Warranty.
- Refer to the warranty, which is available online, for complete terms and conditions. Product must be transported, stored, handled, installed, finished, and maintained in accordance with all published application, finishing, care, and maintenance instructions, technical notes, and bulletins (collectively, “Instructions”) in effect at the time of installation.
- Failure to follow such Instructions will make the limited warranty inapplicable as to the products affected by such failure. No modification or exception to these Instructions and no non-published recommendations are valid unless issued in writing on a project-specific basis by LP’s Director of Technology prior to application. Always check and comply with local building codes. Even where these instructions approve installation over certain substrates or incorporate requirements of building codes, LP’s liability for the performance of the product is limited as expressly provided in the Limited Warranty.
WARNING: Drilling, sawing, sanding or machining wood products can expose you to wood dust, a substance known to the State of California to cause cancer. Avoid inhaling wood dust or use a dust mask or other safeguards for personal protection. For more information go to P65Warnings.ca.gov/wood-dust.
product legend
- A LP® SmartSide® ExpertFinish® Lap Joint Siding
- B LP® SmartSide® ExpertFinish® Panel Siding
- C LP® SmartSide® ExpertFinish® Vertical Siding
- D LP® SmartSide® ExpertFinish® Cedar Shake
- E LP® SmartSide® ExpertFinish® Trim & Fascia
- F LP® SmartSide® ExpertFinish® Soffit
- G LP® SmartSide® ExpertFinish® Accessories
- H LP® SmartSide® ExpertFinish® Nickel Gap Siding
General information
Handling
- Handle prefinished LP SmartSide ExpertFinish lap siding with extreme care during storage and application.
- When unpackaging siding, cut the clear shrink-wrap the full-length of siding to avoid dragging and scuffing of the painted surface.
- If siding is restacked after removing clear shrink-wrap, make sure to keep slip between painted surface and back of the siding.
Storage
- Store off the ground well supported, on a flat well-drained surface. If delivered without a pallet, additional support may be required to provide a minimum 2 inch (51 mm) clearance of Prefinished siding from the ground.
- Store Prefinished siding under a roof or separate waterproof covering until the siding is installed on the structure. The clear shrink-wrap is perforated and does not provide protection from water intrusion.
- Protect the Prefinished siding at the end of each installation day by moving siding back under a roof or reapply a waterproof covering.
- Do not install if any type of residue is detected on the surface. Follow Residue Removal Guidelines in Technical Bulletin #053.
Before You Begin
- At the time of manufacture, siding meets or exceeds the performance standards set forth in ICC-ES AC321 and has achieved recognition under PR-N124, ESR-1301, CCMC 11826-L, FL#9109 and HUD-MR-1318d. For copies of product approvals go online at https://lpcorp.com/product-literature or call LP Customer Support at 888-820-0325.
- Where siding butts window trim, door casings, butt joints, etc. leave a 3/16 inch (5 mm) gap and seal.
- Larger gap is required when siding is adjacent to stucco, brick, cultured stone, mortar, etc. (Figure 6c, 6d, 6e)
- Siding applied adjacent to surfaces such as porches, patios, balconies, or walking surfaces (including porch columns) must have a clearance of at least 1 inch (25 mm) above horizontal surface.
- Clearance may be reduced to 3/8 inch (10 mm) for:
- Porches, patios, balconies, or walking surfaces that slope away from the structure or the surface provides gaps that allow water to flow through so that it cannot accumulate, and is covered by a roof, not an eave or overhang; or
- Porch columns with walking surfaces that slope away from the structure or the surface provides gaps that allow water to flow through so that it cannot accumulate.
- All wood substrate directly exposed to the weather must be sealed to prevent moisture intrusion and water build up.
- Seal ALL exposed cuts of siding and trim. Field spray applied coatings on cuts are not recommended.
- Sealing can be accomplished by applying a paint or sealant according to the manufacturer’s requirements.
- See Alternate Fastening Options starting on page 8 for attaching lap to wood structural panel (WSP) sheathing, SIP assemblies, steel studs, or ICF. Lap siding installed vertically can be found on pages 8, 9 and 10.
Trim
- Use a min. 540 Series trim so the lap siding does not extend beyond the face of the trim.
- If trim is installed over lap, a thinner 440 or 190 Series trim may be used.
- Lap siding is not designed to be used as trim.
- Exception: lap joint siding may be used as fascia. Shiplap must be removed to full panel thickness. (Figure 4c)
- See page 10 for PREFERRED and ALTERNATE details for Outside and Inside Corner Trim. (Figure 10g, 10h, 10i, 10j)
Flashing
- All openings must be properly sealed or flashed in a manner that prevents moisture intrusion or buildup.
- Flashing shall be metal or another durable material that will last for not less than 50 years.
- Install step flashing at roof-to-wall intersections with a min. 4 inch (102 mm) upper leg. (Figure 2a, 2b)
- All other flashing must have a min. 4 inch (102 mm) upper leg.
- Add 4 inch (102 mm) wide adhesive flashing when upper leg is less than 4 inches (102 mm).
- Properly integrate flashing with WRB. Use WRB or flashing tape to maintain counterflashing principle.
Roof to Wall intersection
Maintain 1 inch (25 mm) clearance between siding and roofing, or trim and roofing. [Min. 50 mm (2 inch) clearance at intersection with roof line must be maintained between roof surface and cladding when installing cladding in Canada in accordance with the NBC, Section 9.27.2.4.(2) or local building code requirements.]
Kick-out flashings
- Install kick-out flashing at roof eave-to-wall intersections to direct water into gutter. (Figure 3a)
- DO NOT extend siding or trim into kick-out flashing or gutter.
- Maintain 1 inch (25 mm) clearance between the end of the gutter and the adjoining wall to allow for proper maintenance of the siding.
Moisture
- Moisture and vapor control are critical elements of proper housing design.
- Check your local building code for requirements for handling moisture and water vapor in your area.
- Do not apply engineered wood siding to a structure having excessive moisture conditions such as drying concrete, plaster or wet blown cellulose insulation.
- If such conditions exist, building should be well ventilated to allow to dry prior to siding application.
- When using wet blown cellulose insulation it must not be in direct contact with the siding, and it must be allowed to dry a min. of 24 hours or longer if specified by the insulation manufacturer.
- Siding must not be installed on green or crooked studs. Green studs must be allowed to equilibrate to ambient moisture conditions before siding is installed, and siding must be shimmed to maintain flatness if studs are crooked.
- Do not apply siding over rain-soaked or buckled sheathing.
Water-resistive Barrier (WrB)
- A properly installed WRB is required behind siding, unless exempt by building code.
- LP assumes no liability for water penetration or any other issues associated with the WRB.
Fastening instructions
Stud spacing options
- Siding may be attached direct to studs spaced max. 16 inches (406 mm) o.c.
- Siding may be attached directly to wood structural panel sheathing, min. 7/16 Performance Category, with studs spaced a max. 24 inches (610 mm) o.c.
Installation
- Begin by nailing a starter strip 3/8 inch (10 mm) thick x 1-1/2 inches (38 mm) wide, flush with bottom edge of sill plate.
- Starter strip serves two purposes
- Provides separation of siding from CMU or poured concrete foundation. (Figures 7a, 7b, 7c)
- Provides proper angle to first course of siding.
- Exception: starter strip may be omitted if separation from concrete is maintained. Separation can also be achieved by ensuring WRB is placed behind siding.
- Install siding blind-nailed, place nail a min. of 3/4 inch (19 mm) from the top edge.
- Refer to Figure 4c for fastener placement at butt joints.
- Overlap successive courses of lap a min. 1 inch (25 mm).
- Shim siding at studs as needed to avoid drawing siding against uneven walls.
- Nails will be exposed on siding located immediately below window sills, fascia boards, or horizontal trim and shall be spaced a max. 8 inch (203 mm) o.c. (Figure 10d)
- Use a min. 0.092 inch shank diameter, hot-dip galvanized nail (ASTM A153) or equivalent; capable of preventing rust, stain and deterioration under normal outdoor environmental conditions for a period of no less than 50 years. Penetrate studs or combination of WSP sheathing and studs a min. of 1-1/2 inches (38 mm).
- A larger 0.113 inch shank diameter nail may be required depending on the wind pressure, wind speed and wind exposure category limitations in PR-N124 or ESR-1301. Penetrate studs or combination of WSP sheathing and
studs a min. of 2 inches (51 mm).
- A larger 0.113 inch shank diameter nail may be required depending on the wind pressure, wind speed and wind exposure category limitations in PR-N124 or ESR-1301. Penetrate studs or combination of WSP sheathing and
- Install bottom side of shiplap first. (See Figures 4c, 8a)
- Avoid sliding or forcing bottom shiplap into place, if top shiplap has been installed first.
- Nail from the center of the siding toward the ends, or from one end to the other end. NEVER nail from the ends of the siding toward the middle.
- Shiplap must be removed to full panel thickness and caulked at window, door and vertical trim intersection. (Figure 4c)
- Backer rod recommended at 3/16 inch (5 mm) gap.
Figure 4c
- Painting all exposed nail heads is recommended.
- Do not overdrive nails.
- Nail head should seat snug to face of siding, but not countersunk which is considered overdriven.
- Blind nails: only correction required would be re-nailing when countersunk more than 1/8 inch. (Figure 4a)
- Face nails: will occur immediately below window sills, soffit, frieze boards and horizontal trim. Corrections detailed below. (Figure 4b)
BUTT JOINTS
- Butt joints must occur over studs. (Figure 4c)
- Exception: sheathing only applications. (Figure 8a)
- Stagger butt joints a min. of 16 inches (406 mm).
- Stacking or stair-stepping butt joints is not recommended as it may cause an undesirable appearance.
- LP® SmartSide® ExpertFinish® Prefinished Lap Joint Siding is designed with a shiplap butt joint which eliminates the need for sealant/caulk. Do not caulk butt joint.
- Provide a min. 3/16 inch (5 mm) gap at butt joint. (Figure 4d)
- Use spacing tool like SIMPLESIDER® (Figure 4e) or rafter square (Figure 4f) to achieve proper gaping.
- Rafter square thickness varies between manufacturers.
- Confirm spacing tool is a min. 3/16 inch (5 mm) in thickness before using.
- Gapping will allow for linear expansion of siding.
Fastening options over foam plastic sheathing (rigid foam insulation)
Lap siding may be installed directly over foam sheathing.
Foam plastic sheathing ≤ 1 inch (25 mm)
Increase nail length to ensure the required min. penetration into studs (Figure 5a), or combination of studs and WSP sheathing; or nail length long enough to fully penetrate sheathing a min. 1/4 inch (6 mm) for a sheathing only attachment. (Figure 5b)
Foam plastic sheathing > 1 inch (25 mm)
- Siding attachment: Refer to IRC Chapter 7, Wall Covering for prescriptive siding attachments over foam sheathing up to 4 inches (102 mm) thick, direct to wood or steel studs for support of siding weight only. Does NOT include wind loads.
- Refer to Table 703.15.1 for min. fastening requirements over foam sheathing to wood studs.
- Refer to Table 703.16.1 for min. fastening requirements over foam sheathing to steel studs.
- Fastener placement:
- Nail spacing depends on siding attachment method; Direct to Stud or wood structural panel (WSP) sheathing attachment, and
- Wind load limitations in PR-N124 or ESR-1301.
- LP assumes no liability for loss or damage associated with fastening requirements of the applicable code.
Furring over foam plastic sheathing
- Use a min. 3/4 inch (19 mm) thick x 3-1/2 inch (89 mm) wide Southern Pine furring strip with a specific gravity ≥ 0.55.
- 38 Series lap siding may be attached to furring spaced a max. 16 inches (400 mm) o.c.
- Depending on wind load limitations in PR-N124 or ESR-1301.
- Furring attachment direct to wood or steel studs:
- Refer to IRC Chapter 7 on Wall Covering for prescriptive furring attachment over foam sheathing up to 4 inches (102 mm) thick.
- Refer to Table 703.15.2 furring min. fastening requirements over foam sheathing to wood studs.
- Refer to Table 703.16.2 furring min. fastening requirements over foam sheathing into steel studs.
- Siding attachment to furring: (Figures 5c)
- Use a min. 0.120 inch diameter ring shank, hot-dip galvanized nail (ASTM A153) or equivalent.
- Nail length must be long enough to penetrate min. 1/2 inch (13 mm) into furring.
- Place nail 3/4 inch (19 mm) from top edge of siding. ○ Increase min. overlap to 1-1/8 inch (29 mm).
- Blind nail two fasteners per furring strip (four nails at butt joints). (Figure 5d)
Additional Fastening Options ≤ 1 inch (25 mm)
Exterior Gypsum sheathing
- Siding may be installed over exterior gypsum sheathing, according to the following:
- Adequate bracing of the wall is provided in accordance with the local building code.
- Nail length must be increased to ensure a min. 1-1/2 inch (38 mm) penetration into wood studs, or combination of WSP sheathing and wood studs.
Existing Wood siding or Wood composite siding
- Siding may be installed over existing wood or wood composite siding, if the existing siding does not affect the ability to correctly install siding.
- A properly installed WRB is required between the existing siding and the new siding.
- A uniform surface behind siding is required to avoid contouring of siding.
- Do not install over existing siding that is not flat or uniform.
- Min. nail penetration and max. stud spacing must not be compromised.
- Ensure wall assembly meets structural requirements specified in building code and by local code authority.
- Repair any areas of the existing siding that are not structurally sound, not installed correctly, or exhibit signs of decay.
Concrete masonry unit (cmu) or poured concrete Walls
- Non-Compressible Drainable Housewrap (NCDH) is required behind siding installed over CMU or poured concrete walls.
- Refer to Technical Bulletin #031 for definition of NCDH.
- Attach NCDH to wall per manufacturer’s instructions or use a min. 3/8 inch (10 mm) stub nail.
- Properly tape and/or seal wall penetrations in accordance with the NCDH manufacturer’s instructions.
- Siding attachment: Use fasteners suitable for CMU or poured concrete walls as specified by the fastener manufacturer.
- Use a fastener with a min. allowable withdrawal capacity and fastener head pull-through capacity of 62 lbf/nail (276 Nf/nail) or greater, based on load duration factor of 1.6.
- Min. shank diameter = 0.140 inch (3.6 mm).
- Min. length = 1.25 inches (32 mm).
- Commonly used concrete fasteners include, but not limited to Aerosmith® Power- Pin™ 5323HPG PT2000 plating, head diameter 0.300 inch (7.6 mm) x shank diameter 0.145 inch (3.7 mm) x length 1.25 inches (32 mm), smooth shank.
- Fastener placement:
- Install blind-nailed a max. 10 inches (254 mm) o.c. with fastener placed 3/8 inch (10 mm) from either end, a min. 3/4 inch (19 mm) from the top edge of the board.
- Immediately below window sills, frieze boards and horizontal trim nails will be exposed every 10 inches (254 mm) o.c.
- Overlap siding a min. 1 inch (25 mm).
Fire-rating
CAL FIRE WUI
- California Building Code, Chapter 7A [SFM] Materials and Construction Methods for Exterior Wildfire Exposure compliance can be achieved using LPS Smart Side lap siding installed as described in:
- CAL FIRE BML# 8140-2027:0001 over 1/2″ (13 mm) standard gypsum wallboard applied behind lap on exterior side of framing; or
- CAL FIRE BML# 8140-2027:0005 atop FlameBlock sheathing.
FIRE-RATED WALL ASSEMBLY
- LP SmartSide lap siding may be installed over the exterior portion of a I-hour fire-resistive exterior wall assembly, including assemblies using gypsum wallboard listed in the Gypsum Association Fire Resistance Design Manual.
- For information on fire-rated wall assemblies: https://lpcorp.com/products/panels-sheathing/fire-rated-osb-sheathing/assemblies
SIDING OR TRIM ADJACENT TO STUCCO/MASONRY
- Do not install trim or siding horizontally to create ledge or window sill. (Figure 6b)
- Where siding is installed directly adjacent to stucco, brick, cultured stone, mortar, etc., leave a min. 3/8 inch (10 mm) gap and caulk, backer rod recommended. (Figure 6c, 6d, 6e)
CLEARANCE & SEPARATION GUIDELINES
- Min. 6 inch (152 mm) clearance must be maintained between siding and finish grade (ground cover). [Min. 200 mm (8 inch) clearance must be maintained between cladding and finish ground when installing cladding in Canada in accordance with NBC, Section 9.27.2.4.(1) or local building code requirements
- Provide separation between back of siding and concrete or masonry foundation. Separation can be achieved using a starter strip, WRB, flashing, or similar product. (Figures 7a, 7b, 7c)
FINISHING INSTRUCTIONS
- When sealant is required, use a high-quality, non-hardening, paintable sealant meeting ASTM C920, minimum Class 25.
- Follow sealant manufacturer’s instructions for application.
- Paint all exposed surfaces, including all drip edges or where water will hang. For best results, use a high-quality 100% acrylic exterior paint specially formulated for use on wood and engineered wood substrates; oil paint is acceptable.
- DO NOT USE stain or vinyl-based paint.
- Apply paint as soon as possible or within 180 days.
- Follow paint manufacturer’s instructions for application.
- Follow LP’s Care & Maintenance Instructions.
BRUSHED SMOOTH Lap Siding:
- Either flat, satin or semi-gloss coatings can be applied to brushed smooth finish lap siding.
- Each offers different appearance & maintenance benefits.
CEDAR TEXTURE Lap Siding:
- For best results use semi-gloss finish.
- Touch up any damage to finish that may occur during application
- Apply touch up paint to cover scratches less than 1 inch (25 mm) in length and less than 1/16 inch (2 mm) wide, exposed nail heads and small nicks.
- Do not apply touch up paint to spots greater than 3/4 inch (19 mm) in diameter.
- Touch up paint should be used sparingly.
- Apply touch up paint only when air, siding and paint temperature are above 500F.
- Store touch up paint between 400F and 1000F.
- Shake touch up paint for 90 seconds before every use.
- Do not use touch up paint if you suspect it has frozen.
- Do not apply touch up paint to wet siding.
- Avoid touch up painting when condensation likely to form.
- Avoid touch up painting when precipitation is possible.
- The touch up paint is air dried, while the factory applied coating is cured using ovens.
For this reason, the touch up paint will have some minor differences initially and after time. Minimizing the use of touch up paint is the best approach to help ensure these minor differences are less noticeable. - Use the appropriate applicator provided in the Smart Side Expert Finish Touch-Up Kit.
- Nail Head Paint Applicator (Figure 7d)
- Cut End Paint Applicator (Figure 7e)
- For additional touch-up paint, please call 888-820-0325.
ALTERNATE FASTENING OPTION
WOOD STRUCTURAL PANEL (WSP) SHEATHING OR SIP ASSEMBLIES
- WSP wall sheathing must be a min. 7/16 Category with APA Trademark that contains the consensus Standard DOC PS 1 or DOC PS 2. [In Canada in accordance with CSA 0437.0]
- Siding may be nailed to SIP or WSP sheathing. (Figure 8a)
- Min. 0.092 inch diameter ring shank, hot-dip galvanized nail (ASTM A153) or equivalent.
- Nail length must be long enough to fully penetrate sheathing by at least 1/4 inch (6 mm). (Figure 8b, 8c)
- Ensure that the ring shanks of the nail fully engage the wood structural panel sheathing.
- Space fasteners depending on the wind pressure, wind speed and wind exposure category limitations in PR-N124,
Table 4a or 4b; or ESR-1301, Table 4a or 4b.
Steel Stud Framing Assemblies
- Siding must be fastened with:
- Min. #8 stainless steel or equivalent, self-drilling tapered head screw.
- Min. of 5 threads beyond the combined thickness of the siding and steel stud framing. (Figures 8d, 8e)
- Min. steel stud thickness of 0.032 inch (8 mm) or 20 gauge.
- Min. withdrawal value of steel stud must be 50 lbs. (23 kg).
- Refer to steel stud manufacturer’s evaluation report.
Insulated Concrete Forms (ICF ) Assemblies
- Web flange must be wide enough to accommodate fastener spacing requirement at butt joint. (Figures 8a)
- Siding must be fastened with:
- Min. #8 stainless steel or equivalent, self-drilling tapered head screw.
- Min. penetration of 3/8 inch (10 mm) beyond thickness of the nailing flange.
- L arger screws may be required by ICF Manufacturer based on the following min. withdrawal requirements.
- Min. withdrawal value of ICF nailing flange must be 50 lbs. (23 kg) with max. 12 inches (305 mm) o.c. spacing.
- Min. withdrawal value of ICF nailing flange must be 31 lbs. (14 kg) with max. 6 inches (152 mm) o.c. spacing.
Lap Siding Installed Vertically
- Siding must be installed in a sheathing only attachment method over min. 7/16 Category WSP sheathing with an APA Trademark that contains the consensus Standard DOC PS 1 or DOC PS 2. [In Canada in accordance with CSA O437.0]
- Exception: can be installed over LP® FlameBlock® Fire-Rated OSB Sheathing.
- The edges of lap siding installed vertically must be spaced a min. of 3/16 inch (5 mm) from each other. (Figures 10a, 10b)
- Due to expected plate shrinkage, each vertical application of battens or lap siding is not to span beyond one floor to ceiling distance, or one floor to top of gable distance. (Figures 9b, 9c)
- Exception: residing existing structures.
- Sliding may be applied over an entangled mat. Ensure mat is rigid enough to receive siding to avoid a wavy or inconsistent appearance.
- Exception: lap siding installed horizontally is not approved for use over entangled mat products.
- Remove shiplap to full panel thickness at top and bottom of wall. (See Figures 8f, 8g)
- DO NOT bridge floors with lap installed vertically or battens. (Figures 9c)
- Create a horizontal joint between floors.
- Joint must be flashed with sloped Z-flashing, remove shiplap edges of siding at horizontal joint. (Figures 9a)
- Siding nail requirements:
- Use a min. 0.092 inch diameter ring shank, hot-dip galvanized nail (ASTM A153) or equivalent.
- Nail shall be long enough to fully penetrate WSP sheathing by at least 1/4 inch (6 mm). Ensure that the ring shanks of the nail fully engage the WSP sheathing.
- Caution: nail length should be chosen to reduce possible damage to wiring or utilities in wall.
- Place nails 3/8 inch (10 mm) from ends and edges.
- Nail spacing for lap siding installed vertically or lap over lap:
- P l ace with two nails at both ends, with additional nails spaced a max. of 6 inches (152 mm) o.c. along alternating edges (Figure 9d)
- Batten nail requirements:
- Use a min. 0.092 inch diameter ring shank, hot-dip galvanized
nail (ASTM A153) or equivalent.
- Use a min. 0.092 inch diameter ring shank, hot-dip galvanized
- Rising Shank nails provide superior resistance to nail pull-through. In Hurricane-Prone Regions or locations where negative wind loads are a concern, ring shank nails should be used.
- Finish nails may be used in other locations with the following cautions: Do not overdrive or counter sink the fastener, nail snug with the surface of batten.
- Place nails 3/8 inch (10 mm) from ends and edges.
- Nail Spacing for Battens: Place two nails at both ends, with additional nails spaced a max. 12 inches (309 mm) o.c. along alternating edges the length of batten. (Figure 9e)
- Exception: for battens 1-1/2 inches (38 mm) wide or less, one nail is required at each end with additional nails spaced a max. 24 inches (305 mm) o.c. along alternating edges. (Figure 9f)
- Batten may be a min. 1/2 inch (13 mm) x 1-1/2 inch (38 mm) wide.
- Caution: when selecting batten less than 2-1/2 inches (64 mm) wide, it may be difficult for batten to conceal nail heads.
- Visible nail heads that are not covered by battens are an aesthetic issue and not covered under Limited Warranty.
- Detachment of batten is not covered by the LP Smarts ide limited warranty whether ring shank or finish nails are used.
General Information
Wood Framed and CMU , Poured Concrete Wall Assemblies – Examples
WRB location in wall assembly may vary depending on climate zone or other factors.
©2024 Louisiana-Pacific Corporation. All rights reserved. LP and SmartSide are registered trademarks of Louisiana-Pacific Corporation. Printed in U.S.A.
LP® SmartSide® ExpertFinish® Lap Joint Siding
Application Tips
IMPORTANT Always refer to the complete application instructions for the product you are installing. The application tips provided below are not intended to replace such instructions. Application instructions can be found at LPCorp.com. Failure to follow the full application instructions could cause personal injury or property damage, affect system performance, void any applicable warranty and/or violate applicable building codes.
Exercise safe practices at all times while handling and using this product. Refer to the relevant Safety Data Sheet (SDS) for important information on the safe handling and use of this product. These can be found at LPCorp.com.
- Lap siding may be attached Direct to Studs or Direct to Wood Structural Panel (WSP) Sheathing:
- Direct to Stud – nails must penetrate structural framing, or combination of WSP and structural framing min. 1-1/2” (38 mm), some installations may require 2” (51 mm) penetration see PR-N124 or ESR-1301
- Direct to WSP Sheathing – nails must be long enough to penetrate beyond WSP by 1/4″ (6 mm)
- Stud spacing – see application instructions for spacing from 16″ (406 mm) o.c. to 24” (610 mm) o.c.
- See application instructions for alternative nailing options for: SIP, steel studs, ICF’s and lap siding installed vertically
- Nail size:
- Direct to Stud – a min. 0.092” shank diameter hot-dip galvanized (ASTM A153) nail may be used, some installations may require a larger 0.113” shank diameter depending on wind pressure, wind speed and wind exposure limitations in PR-N124 or ESR-1301
- Direct to WSP Sheathing – a min. 0.092” shank diameter hot-dip galvanized (ASTM A153) ring shank nail
- Nail placement – 3/8” (10 mm) from siding end and edges and a min. of 3/4″ (19 mm) down from top edge of siding
- Nail spacing:
- Direct to Stud – one nail every 16” (406 mm) o.c.
- Direct to WSP Sheathing – nailing pattern varies from 8” (203 mm) o.c. to 12” (305 mm) o.c. depending on the wind pressure, wind speed and wind exposure limitations in PR-N124 or ESR-1301
- Overlap – min. of 1” (25 mm), siding shall not project beyond the face of trim
- Do not overdrive nails – nail head should seat snug to the face of siding, if overdriven – see Application Instructions
- Caulk – use a high-quality, non-hardening, paintable exterior sealant meeting ASTM C920, min. Class 25
- Seal all exposed substrate – sealing can be accomplished by applying a paint or caulk
- Provide a min. 3/16 inch (5 mm) gap at butt joint
- Use spacing tool like SIMPLESIDER® or rafter square to achieve proper gaping
- Where siding butts up against a window, door, and corner trim space – min. 3/16” (5 mm) gap
- Siding clearance at finish grade (ground cover) – min. 6” (152 mm) [Min. 200 mm (8 inch) when installing in Canada]
- Siding clearance adjacent to surfaces such as porches, patios, or porch columns, etc. – min. 1” (25 mm):
- May be reduced to 3/8” (10 mm) – see Application Instructions
- Siding must not be in direct contact with CMU, poured concrete, brick, cultured stone, stucco, mortar, etc.
- Flashing is required above all windows, doors and horizontal trim per manufacturer’s instructions:
- Flashing shall be metal or another durable material that will last for not less than 50 years
- Provide 3/8” (10 mm) gap above any drip cap flashing, do not caulk gap
- The piece of lap siding below a windowsill or frieze board will require face-nailing – see Application Instructions
- Siding over foam plastic sheathing adds complexity to siding installation – see Application Instructions
- For Limitations of Use – see Application Instructions, Technical Notes, Technical Bulletins and NSA Bulletins
- See Application Instructions for Storage and Handling guidelines
FAQ
- Q: Is it necessary to use a dust mask when working with wood products?
- A: Yes, it is recommended to use a dust mask or other safeguards for personal protection when drilling, sawing, sanding, or machining wood products to avoid inhaling wood dust.
- Q: What should I do if I encounter wood dust exposure?
- A: If you suspect wood dust exposure, refer to P65Warnings.ca.gov/wood-dust for more information and take necessary precautions.
Documents / Resources
![]() |
LP Building Solutions 38 Series LP Smart Side Expert Finish Lap Joint Siding [pdf] Installation Guide 38 Series LP Smart Side Expert Finish Lap Joint Siding, 38 Series, LP Smart Side Expert Finish Lap Joint Siding, Expert Finish Lap Joint Siding, Finish Lap Joint Siding, Lap Joint Siding, Joint Siding |