Lindab logoPerforated Diffuser
Instruction Manual

Lindab PCS Perforated Diffuser -

Description

PCS is a circular diffuser wan with an integrated box for visible installation. The diffuser has a perforated face plate and can be used for both supply and extract air. The diffuser has a built-in damper and a measuring device for adjustment. PCS is equipped with an M8 threaded rod at the top for suspending the diffuser. The diffuser is suitable for the horizontal supply of cooled air.

  • Can be used for both supplies and extracting air.
  • Can be connected regardless of straight ducting before the diffuser.
  • Supplied with integrated M8 rivet nut for suspension.
  •  Detachable damper for cleaning of duct.

Maintenance

The face plate can be detached and the damper removed to enable cleaning of the internal parts or the duct. The visible parts of the diffuser can be wiped with a damp cloth. Order cod

Lindab PCS Perforated Diffuser - Fig 13

Dimensions

Lindab PCS Perforated Diffuser - Fig

Size[mm] ØD [mm] Ød1  [mm] L[mm] H[mm] Weight ]kg]
125 240 125 340 215 4,6
160 300 160 360 260 6,9
200 360 200 390 300 9,6
250 460 250 420 350 11,4
315 540 315 460 420 11,4

Materials and finish

Material: Galvanised
Standard finish: Powder-coated
Standard color: White, RAL 9003 or 9010,  loss  30

The diffuser is available in other colors or unpainted. Please contact Lindab’s sales department for further information.

Perforated diffuser

Technical data
Capacity
Volume flow qv [l/s] and [m 3 /h], total pressure Δpt [Pa], throw l0.2 [m] and sound power level LWA [dB(A)] can be seen in the diagrams.
The frequency-related sound effect level
The sound effect level in the frequency band is defined as LWA + Kok Kok values are given in charts beneath the diagrams on the following pages.

Quick selection
Supply air

Minimum
Pi=5 Pa
pt=50 Pa
LWA=30dB(A)
pt=50 Pa
LWA=35dB(A)
Size l/s m3 /h l/s m3 /h l/s m3 /h
125 20 73 30 106 36 131
160 34 122 48 173 59 212
200 53 190 65 235 81 292
250 79 286 109 393 135 484
315 121 437 188 675

Extract

Minimum
Pi=5 Pa
pt=50 Pa
LWA=30dB(A)
pt=50 Pa
LWA=35dB(A)
Size l/s  m3 /h l/s  m3 /h l/s  m3 /h
125 20 73 30 104 43 156
160 34 122 48 117 62 222
200 53 190 65 225 104 376
250 79 286 109 391 146 525
315 121 437 191 687

Throw l0.2
The throw is specified at a terminal velocity of 0.2 m/s.

Lindab PCS Perforated Diffuser - Fig 2

Sound attenuation
Sound attenuation of the diffusers ΔL from duct to room, including end reflection, see table below.

Center frequency Hz
Size 63 125 250 500 1K 2K 4K 8K
125 21 16 6 19 14 12 11 17
160 15 11 9 21 15 12 13 16
200 12 8 6 15 15 9 11 14
250 19 15 12 17 12 9 11 14
315 16 13 11 14 12 9 12 13

Balancing
Balancing data is contained in a separate brochure.

Technical data

Supply air

Lindab PCS Perforated Diffuser - Fig 3

Hz 63 125 250 500 1K 2K 4K 8K
Kok 6 3 1 -4 -5 -10 -15 -17

Lindab PCS Perforated Diffuser - Fig 4

Hz 63 125 250 500 1K 2K 4K 8K
Kok 6 3 -1 -4 -5 -9 -16 -17

Lindab PCS Perforated Diffuser - Fig 5

Hz 63 125 250 500 1K 2K 4K 8K
Kok 3 0 -2 -3 -4 -9 -17 -19

Lindab PCS Perforated Diffuser - Fig 6

Hz 63 125 250 500 1K 2K 4K 8K
Kok 6 3 2 -3 -6 -10 -13 -16

Lindab PCS Perforated Diffuser - Fig 7

Hz 63 125 250 500 1K 2K 4K 8K
Kok 5 2 0 -6 -5 -8 -13 -18

Lindab PCS Perforated Diffuser - Fig 8

Hz 63 125 250 500 1K 2K 4K 8K
Kok 7 4 -1 -3 -4 -9 -15 -19

Supply air

Lindab PCS Perforated Diffuser - Fig =9

Hz 63 125 250 500 1K 2K 4K 8K
Kok 4 1 -3 -3 -4 -9 -17 -18

Lindab PCS Perforated Diffuser - Fig 11

Hz 63 125 250 500 1K 2K 4K 8K
Kok 5 2 -2 -1 -5 -11 -17 -16

Extract air

Lindab PCS Perforated Diffuser - Fig 10

Hz 63 125 250 500 1K 2K 4K 8K
Kok 8 5 -2 -3 -5 -9 -14 -16

Lindab PCS Perforated Diffuser - Fig 12

Hz 63 125 250 500 1K 2K 4K 8K
Kok 6 3 -4 -3 -4 -8 -16 -22

Lindab logoLindab reserves the right to make changes without prior notice
2020-12-16

Documents / Resources

Lindab PCS Perforated Diffuser [pdf] Instruction Manual
PCS, Perforated Diffuser, PCS Perforated Diffuser, Diffuser

References

Leave a comment