LENNOX VHEC144S4-4P VRF Hydro Unit
SUBMITTAL DATA – IN DOOR UNIT
VHEC096S4-4P VRF Hydro Unit
- Job:
- Location:
- Schedule No.:
- System Designation:
- Engineer:
- Architect:
- Location:
- Date:
- For:
- Reference
- Approval
- Review
- Construction
VRF Hydro Unit
FEATURES
- Flexible Installation Options
- Louver-less Installation
- Refrigerant R-410A
- Available in four capacities 36 – 144K
WARRANTY
10-year limited warranty.*See warranty for details.
SPECIFICATIONS
PERFORMANCE | |
Heating Capacity (Btu/h) | 108,000 |
Power Input W (Heating) | 10 |
Operating Temp. Range Heating (℉) | -4-95 |
Operating Water Temp. Range (℉) | 68~122 |
Refrigerant Type | R-410A |
Sound Pressure (dBA) | 28 |
Power Supply (Volts/ Phase/Hertz) | 208-230V-1Ph-60Hz |
Power Source Wire (No Heater) | 10 AWG |
Transmission Cable | 18 AWG |
Water Flow Rate (GPM) | 24.3 |
Flow Switch (GPM) | 7.9 |
Pipe Size | NPT1 |
Type | PHE |
DIMENSIONS | |
Unit Dimensions (in) Height
Width Depth |
24.7 |
20.4 | |
13 | |
Liquid Pipe Connection (in) | 3/8 |
Gas Pipe Connection (in) | 5/8 |
Drain Connection (in) | 3/4 |
Unit Shipping Weight (lb) | 80 |
Unit Net Weight (lb) | 75.4 |
OPTIONAL ACCESSORIES
VSTAT05P-1 Hydro Unit Wired Controller 37Y75
NOTES
- Specifications may be subject to change without prior notice for product improvement.
- Nominal cooling capacities are based on;
- Water temperature : 73.4°F(23°C) inlet, 64.4°F(18° C) outlet
- Indoor temperature : 80.6°F(27°C) DB, 66.2°F(19° C) WB
- Outdoor temperature : 95°F(35°C) DB, 75.2°F(24° C) WB
- Nominal heating capacities are based on; Water temperature : 86℉(30℃) inlet, 95℉(35℃)outlet Indoor temperature : 68°F(20°C) DB Outdoor temperature :44.6°F(7°C) DB, 42.8°F(6°C) WB 3)
- Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
- The VRF system contains R410A (GWP=2,088) which is fluorinated greenhouse gas.
- Heat Exchanger type : Plate Heat Exchanger (STS)
DIMENSIONAL DRAWINGS – MM (Inches)
No. | Name | Description | ||
VHEC036S4-4P VHEC048S4-4P | VHEC096S4-4P | VHEC144S4-4P | ||
1 | Gas Pipe Connection | Φ15.88[5/8] | Φ22.22[7/8] | Φ28.58[1 1/8] |
2 | Liquid Pipe Connection | Φ9.52[3/8] | Φ9.52[3/8] | Φ12.70[1/2] |
3 | Communication Wiring Conduits | – | – | – |
4 | Power supply conduit | – | – | – |
5 | Water outlet pipe | – | – | – |
6 | Water inlet pipe | – | – | – |
NOTE
Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency. 496294 (202412)
Frequently Asked Questions (FAQ)
- Q: Can I use this unit for cooling purposes?
A: The VHEC096S4-4P VRF Hydro Unit is designed specifically for heating purposes and is not suitable for cooling. - Q: What type of refrigerant does this unit use?
A: This unit operates using R-410A refrigerant. - Q: What should I do if I encounter an error code on the unit display?
A: Refer to the user manual for error code explanations and troubleshooting steps. If the issue persists, contact a qualified service technician for assistance.
Documents / Resources
![]() |
LENNOX VHEC144S4-4P VRF Hydro Unit [pdf] Owner's Manual VHEC036S4-4P, VHEC048S4-4P, VHEC096S4-4P, VHEC144S4-4P, VHEC144S4-4P VRF Hydro Unit, VRF Hydro Unit, Hydro Unit, Unit |