LEFOO logoLF52 Differential Pressure Switch
Instruction ManualLEFOO LF52 Differential Pressure Switch

Product introduction:

This adjustable differential pressure switch LF52 is eveloped for sparingly using in different differential value requirements. It is widely applied for detecting the differential of water filter, pump, heat exchanger, chillers and its coil units. When the water flowing (differential) decrease or increase to the setting point, there will be an alarm or cut off output signal for the self-controlling system. It’s also available for indicating the status of pump or water filter. Double differential settings pressure switch can take the replacement of the vane flow switch and avoid changing the vane flow switch from chillers each year.
A single set point is a high/low limit that controls the differential pressure between the front and rear ends of a section of pipeline. The double set point is to control the high and low limit of the pressure difference between the front and rear ends of a pipeline, and can also control the high/low limit of the pressure difference between the front and rear ends of the two pipelines.

Reference standard:

  1. Ul508
  2. GB14048-2000 ( Low voltage switchgear and control equipment general provision )
  3. GB14048.5-2000(Low voltageswitchgear and control equipment, part 5-1 Control equipment and switching elements )
  4. ROHS certificate.

Installation dimension(mm)

LEFOO LF52 Differential Pressure Switch - Installation dimension

Wiring diagram

Adjustable Model Differential pressure adjustable range kPa Differential Lap increment
Single Set Point Working Pressure range 52-15 5—15 1—3 1
52-30 5—30 1—3 2.2
52-70 6—70 3—5 5.5
52-100 6—100 3—5 6.5
52-200 10—200 5—7 16
52-300 20—300 6—9 25
52-400 30—400 6—12 38
Dual Set Point Working Pressure range 52-30/100 5—30/6—100 1—3/3—5 2.2/6.5
52-70/100 6—70/6—100 3—5/3—5 5.5/6.5
52-100/100 6—100/6—100 3—5/3—5 6.5/6.5
52-100/200 6—100/10—200 3—5/5—7 6.5/16
52-200/200 10—200/10—200 5—7/5—7 16/16
52-300/300 20—300/20—300 6—9/6—9 25/25
52-400/400 30—400/30—400 6—12/6—12 38/38

LF52Series Order Ref NO
LE52-A-B-C-D

A Product set point B Joint thread C Instructions D Wiring protection
Single set point 7/16”Single set point(male thread) Chinese/English Rubber
Double set point G1/4”Single set point(female thread) Chinese Plastic
English Metal

Specification

Contact arrangement Non hazardous media such as water, air, oil etc…
Media One/two sets of SPDT (microswitch)
Electrical rating 3A 250VAC 5A 12 VAC
Storage temperature -29~82℃
Ambient temperature -20~71℃
Media temperature -20~93℃
High and low pressure connections 7/16″Single set point(male thread);7/16″UNF double set point(male thread)
G1/4″Single set point(female thread );G1/4″double set point(female thread )
Maximum static pressure 16bar
Maximum differential 10bar
Setting repeatability tolerance Ip54
Degree of protection ±1%
Accessories are optional (if there is no requirement, the default is selected) Converted capillary, plastic/metal/rubber/line card, manual in Chinese/English

www.lefoo.com

Documents / Resources

LEFOO LF52 Differential Pressure Switch [pdf] Instruction Manual
52-15, 52-30, 52-70, 52-100, 52-200, 52-300, 52-400, 52-30-100, 52-70-100, 52-100-100, 52-100-200, 52-200-200, 52-300-300, 52-400-400, LF52 Differential Pressure Switch, LF52, Switch, Pressure Switch, LF52 Pressure Switch, Differential Pressure Switch

References

Leave a comment

Your email address will not be published. Required fields are marked *