VTS Group LS G100 Control and Modbus Communication Instructions

LS G100 Control and Modbus Communication

Specifications:

  • Model: LS G100
  • Control Type: Modbus Communication
  • Communication Protocol: Modbus RS-485
  • Communication Speed: 9600 bps
  • Rated Frequency: 100 Hz
  • U/f Ratio: 1 (Square characteristic)
  • Number of Motor Poles: 2-12

Product Usage Instructions:

1. Configurations Set Common Parameter List:

For all configurations, set the common parameter list as
follows:

Parameter Code Value Comments

2. Configurations Without VTS Controls:

2.1 Local Control Using Integrated Control Panel:

To set up local control using the integrated control panel,
follow these steps:

  1. Set Start/Stop Source to 0.
  2. Set Frequency Source to 0.
  3. Utilize the RUN and STOP/RST buttons on the control panel for
    drive control.

2.2 Remote Control with Three Speeds:

To enable remote control with three speeds, follow these
steps:

  1. Set Start/Stop Source to desired value.
  2. Set Frequency Source to desired value.
  3. Assign Constant Speeds 1, 2, and 3 accordingly.

3. Exhaust Unit with VTS Control System:

If using an exhaust unit with a VTS control system, set the
parameters as per user preferences.

4. AHU with VTS Controls Type uPC3:

To control the G100 frequency drivers in AHU with VTS controls
type uPC3, follow these steps:

  • Set VFD type to G100 in uPC3 settings (HMI Advanced mask
    I03).
  • Set additional parameters for communication.

Frequently Asked Questions (FAQ):

Q: How do I restore G100 to default settings?

To restore G100 to default settings, set dr-93 = 1 and switch
off the power supply.

CONTROL AND MODBUS COMMUNICATION APPENDIX TO THE LS G100 MANUAL ITEMS AS FOLLOW:
THE FOLLOWING MANUAL ASSUMES GOOD KNOWLEDGE OF TECHNICAL DOCUMENTATION INCLUDED WITH THE AIR HANDLING UNIT (AHU). THIS MANUAL CONSIDERS ONLY THE CONTROL AND COMMUNICATION CIRCUITS. THE INSTALLATION OF THE FREQUENCY CONVERTER AND INSTALLATION OF MAINS AND MOTOR CABLES SHOULD BE DONE ACCORDING TO THE LS G100 MANUAL.

1. FOR ALL CONFIGURATIONS SET THE COMMON PARAMETER LIST

Parameter

Code

Value

Comments

Ramp up time

ACC

45

Recommended 45 s.

Ramp down time

dEC

45

Recommended 45 s.

Maximum frequency

dr-20

100

Rated frequency

dr-18

*

U/f ratio

Ad-01

1

Square characteristic

Load type

Pr-04

0

Light / fan duty

Overload protecion

Pr-40

2

Active

Number of motor poles

bA-11

*

2-12

Rated current

bA-13

*

Idle run current

bA-14

**

P5 input function

IN-69

4

Limit switch

* – as per motor data ** – parameter to be calculated: idle run current = 0,3 * rated current

2. CONFIGURATIONS WITHOUT VTS CONTROLS

2.1 Local control using integrated control panel

Set additional parameters:

Parameter

Code

Value

Start / stop source

drv

0

Frequency source

Frq

0

Use the RUN and STOP/RST buttons to control the drive

Use buttons / potentiometer to set frequency

Comments Keypad
Potentiometer

2.2 Remote control with three speeds Set additional parameters:

Parameter

Code

Start / stop source

drv

Frequency source

Frq

Constant speed 1

St1

Constant speed 1

St2

Constant speed 1

St3

* – as per user preferences

Value 1 4 * * *

Comments Programmable inputs
Constant speeds 0-100 Hz 0-100 Hz 0-100 Hz

v1.02 (03.2025)

Use P1/P3/P4/P5 inputs to set desired drive function (1=on,0=off)

0000 = STOP 1100 = START, 1ST SPEED 1110 = START, 2ND SPEED 1111 = START, 3RD SPEED

3. EXHAUST UNIT WITH VTS CONTROL SYSTEM Set additional parameters:

Parameter

Code

Value

Start / stop source

drv

1

Frequency source

Frq

5

Constant speed 1

St1

*

Constant speed 1

St2

*

Constant speed 1

St3

*

* – as per user preferences

Comments Programmable inputs
Constant speeds 0-100 Hz 0-100 Hz 0-100 Hz

Use P1/P3/P4/P5 inputs to set desired drive function (1=on,0=off)

0000 = STOP 1100 = START, 1ST SPEED 1110 = START, 2ND SPEED 1111 = START, 3RD SPEED

4. AHU WITH VTS CONTROLS TYPE uPC3

NOTE! To allow control of the G100 frequency drivers, set VFD type to G100 in uPC3 settings (HMI Advanced mask I03).

Set additional parameters: Parameter
Start / stop source Frequency source
Address
Comm. protocol Comm. speed Comm. parameters

Code drv Frq
CM-01
CM-02 CM-03 CM-04

Value 3 6
41,42,43…40 51,52,53…50
0 3 0

Comments Modbus RS-485 Modbus RS-485
Supply Exhaust Modbus RS-485 9600 bps
8N1

NOTE! To restore G100 to default settings set dr-93 = 1 and switch off the power supply.