RBM-HY1043E Branching Header Installation Guide
RBM-HY1043E Branching Header

Please read “Safety Cautions” described in the Installation Manual of the Air Conditioner.

  • Check the following parts in the package.
  • For piping material and size of the refrigerant pipes, refer to the Installation Manual of the Air Conditioner.

PARTS

NOTE :

  1. All dimensions are in millimeters. In the following tables, ( ) indicates diameter of the indicated position, and others indicate diameter of the connecting pipe.
  2. Please connect pipe to the side with a projection of the socket. ( 51 ,,,,,,,, 52 54 58 59 61 62 70 89 : without projection)
MODEL NAME RBM-HY1043E RBM-HY1083E RBM-HY2043E RBM-HY2083E
Branching pipe gas side PARTS1pc PARTS1pc PARTS1pc PARTS1pc
Branching pipe liquid side PARTS1pc PARTS1pc PARTS PARTS
Heat insulator(gas side/liquid side) PARTS1pc PARTS1pc PARTS1pc PARTS1pc
Socket Gas side diameter of the connected pipe  
  
external diameter of socket
No. No. No. No. No. No. No. No.
14187085 Ø15.9×(Ø22.2) 1pc Ø19.1×(Ø22.2) 1pc Ø28.6×(Ø22.2) 1pc Ø12.7×(Ø22.2) 1pc 0609 Ø 9.5 ×(Ø15.9) 4pcs Ø12.7×(Ø15.9) 4pcs 14187085 Ø15.9×(Ø22.2) 1pc Ø19.1×(Ø22.2) 1pc Ø28.6×(Ø22.2) 1pc Ø12.7×(Ø22.2) 1pc 0609 Ø 9.5 ×(Ø15.9) 8pcs Ø12.7×(Ø15.9) 8pcs 275923 Ø28.6×(Ø31.8) 1pc Ø34.9×(Ø31.8) 1pc Ø22.2×(Ø31.8) 1pc 0609 Ø 9.5 ×(Ø15.9) 2pcs Ø12.7×(Ø15.9) 2pcs 275923 Ø28.6×(Ø31.8) 1pc Ø34.9×(Ø31.8) 1pc Ø22.2×(Ø31.8) 1pc 0609 Ø 9.5 ×(Ø15.9) 7pcs Ø12.7×(Ø15.9) 7pcs
Liquid side 0609 Ø 9.5 ×(Ø15.9) 1pc Ø12.7×(Ø15.9) 1pc 01 Ø 6.4 ×(Ø 9.5) 4pcs 0609 Ø 9.5 ×(Ø15.9) 1pc Ø12.7×(Ø15.9) 1pc 01 Ø 6.4 ×(Ø 9.5) 8pcs 5191 Ø 19.1 ×(Ø15.9) 1pc (Ø15.9)ר12.7ר9.5 1pc 01 Ø 6.4 ×(Ø 9.5) 2pcs 5191 Ø 19.1 ×(Ø15.9) 1pc (Ø15.9)ר12.7ר9.5 1pc 01 Ø 6.4 ×(Ø 9.5) 7pcs
Outlet sealed pipe at gas side Header sealed pipe at liquid side (Ø15.9) 1pc (Ø15.9) 1pc (Ø15.9) 3pcs (Ø15.9) 1pc (Ø15.9) 1pc (Ø15.9) 1pc (Ø15.9) 3pcs (Ø15.9) 1pc
Outlet sealed pipe at liquid side (Ø 9.5) 1pc (Ø 9.5) 3pcs (Ø 9.5) 1pc (Ø 9.5) 3pcs

CONNECTING METHOD

Select and install the socket that matches the diameter of a pipe to be connected to the indoor unit

Gas side
CONNECTING METHOD

Liquid side
CONNECTING METHOD

  • If the number of indoor units to be connected is fewer than the maximum number of units that can be connected to the branching header, attach a sealed pipe to the unused connectors.
    CONNECTING METHOD
    CONNECTING METHOD
  • Install the branching header so that it branches horizontally.

Gas side
CONNECTING METHOD

Liquid side
CONNECTING METHOD

When arranging the branching header at the liquid side, attach a header sealed pipe on the sealing side of the header as shown in the fiqure at right. Be sure to install the branch pipe downward. Horizontal viewed from D point should be within ±10 degrees same as view B.
CONNECTING METHOD

  • Supporting branching heade
    CONNECTING METHOD

After applying the insulation, set the hanging metals as support. (in use on the site)

NOTE : 

  1. Install the branching header so that it branches horizontally. It cannot be used in a vertical position.
  2. Do not use T-type pipe for the branching section.

REQUIREMENT

Condensation may occur on the heat insulator according to the atmosphere inside of the ceiling.
If the inside of the ceiling is subject to high temperature and high humidity,please add the glass wool (16 to 20 kg/m3, 10mm thick or more) on the heat insulator described above for the perfect heat insulation.