GIRA System 3000 Room Temperature Controller Display - logoSystem 3000 Room Temperature Controller Display
Instruction Manual

Room temperature controller Display
Order no.: 5393.
Room temperature controller BT
Order no.: 5394.

Safety instructions

GIRA System 3000 Room Temperature Controller Display - icon 1Electrical devices may only be mounted and connected by electrically skilled persons.
Serious injuries, fire, or property damage are possible. Please read and follow the manual fully.
The danger of electric shock. Always disconnect before carrying out work on the device or load. In so doing, take all the circuit breakers into account, which support dangerous voltages to the device and or load.
These instructions are an integral part of the product and must remain with the end customer.

Device components

GIRA System 3000 Room Temperature Controller Display - figure 1

  1. Programming menu icons
  2. Setpoint temperature, actual temperature, or current time
  3. active mode
  4. Operating area

Icons in the display
GIRA System 3000 Room Temperature Controller Display - icon 8Manual mode is active.
GIRA System 3000 Room Temperature Controller Display - icon 3The temperature value is regulated to comfort temperature
GIRA System 3000 Room Temperature Controller Display - icon 5The temperature value is regulated to reduce the temperature
GIRA System 3000 Room Temperature Controller Display - icon 4The cooling icon lights up: no cooling is taking place
Cooling icon flashes: cooling is taking place
GIRA System 3000 Room Temperature Controller Display - icon 6Heating icon lights up: no heating is taking place
Heating icon flashes: heating is taking place

Icons of the operating area (4)

GIRA System 3000 Room Temperature Controller Display - icon 7Step back / display the current time
Confirm input / display current time
GIRA System 3000 Room Temperature Controller Display - icon 8Switch between manual operation and automatic operation
With Bluetooth version: boost function (press 4 s)
– / + Increase or reduce the displayed temperatures or times/navigation in the menu
GIRA System 3000 Room Temperature Controller Display - icon 28Call up and terminate the programming menu
With Bluetooth version: Activate coupling mode (pairing) prior to commissioning (press 4 s)

Intended use

  • Manual and time-controlled regulation of the room temperature
  • Operation and programming with mobile end device (smartphone or tablet) via Bluetooth with the app (Bluetooth version only)
  • Operation on room temperature controller insert or switch insert from system 3000

Product characteristics

  • Timer with three memory areas Comfort and reduction time for Mo-Fr and Sa-Su in each memory area
  • Setting a comfort, reduction, cooling, and frost protection temperature
  • The current time can be saved as switching time, quick programming
  • Automatic summer time changeover can be switched off
  • Illuminated segment display for easy reading
  • Operating lock
  • Optimized heating up (temperature is reached at the set time), can be switched off
  • Adaptation to valves (de-energized open or de-energized closed)
  • Cooling mode possible
  • Supports internal and external temperature sensor
  • Temperature drop detection (call-up of frost protection temperature when the window is opened)
  • Offset adjustment (correction value for measured temperature)
  • Controller output working method: pulse width modulation (PWM) or two-point
  • Valve protection function (once a week opening and closing of the valve, on Saturdays at 11 a.m.)
  • Interrupts the heating process after 60 minutes for 5 minutes
  • Display switch-off after 2 minutes or permanent display available

Additional functions with the Bluetooth version

  • The entire operation and commissioning can be performed using an app via a connected smartphone or tablet
  • Weekly timer with 40 individually programmable switch points and temperatures
  • Holiday mode (start, end, temperature)
  • Boost function: fast heating up for max. 5 minutes
  • The local operations can be disabled
  • Integration of an external temperature sensor possible via Bluetooth
  • Automatic date and time update when connecting with a mobile device
  • Minimum and maximum temperature values can be set
  • Settings and time programs can be copied to other cover units

Functional description

Heating and cooling operating mode
Modern heat pump systems often also provide the option of cooling rooms. This function is supported by the cover by means of the “Heating and cooling” operating mode. In this operating mode, the system permanently regulates the temperature to the set cooling temperature. There are no time programs in cooling mode. The only way to change the cooling temperature consists in adjusting the temperature parameters, the +/- buttons cannot be used. In conjunction with a room temperature controller insert, the cooling mode is activated by applying mains power to input terminal “C”. With switch inserts, the cooling mode is activated by applying mains power to extension input “1”.

Frost protection / temperature drop detection GIRA System 3000 Room Temperature Controller Display - icon 10
The frost protection temperature is the minimum temperature regulated by the controller in order to avoid frost damage. In case of a significant temperature drop, e.g. after opening a window, the system regulates the frost protection temperature for a maximum of 30 minutes. This requires the temperature drop detection parameter GIRA System 3000 Room Temperature Controller Display - icon 10to be activated.

Optimized heating up GIRA System 3000 Room Temperature Controller Display - icon 12
Heating is started at most 4 hours before the switching time so that the desired temperature has been reached at the switching time rather than starting to heat up at that time.  The display icon GIRA System 3000 Room Temperature Controller Display - icon 12flashes during the heat-up phase.
Note: Optimised heating up is designed for panel heating/radiators.

Offset +/-
If the system detects that the displayed actual temperature differs from the general room temperature, this parameter can be used to enter a correction value. The actual temperature will then be corrected by this offset value.

Controller adaptation 2P
The control principle should be adjusted depending on the heating system and the insert used.
Two-point control (2P): The output remains switched on until the selected setpoint temperature has been exceeded by 0.5 °C. The output will not be switched on again until the setpoint value is undercut by 0.5 °C. Since most heating systems respond very slowly, this type of control can entail temperature overshooting.
Pulse width modulation control (PWM): Optimised for electrothermal valve drives, e.g. 2169 00.
The output is not permanently actuated, but only for a time period (pulse width) that depends on the difference between the setpoint and actual temperature. This method brings the actual temperature gradually closer to the setpoint temperature. The cycle time is 15 minutes.

Valve adaptation GIRA System 3000 Room Temperature Controller Display - icon 13
This parameter is used to adapt to the electrothermal valve drives. There are drives that are either open (de-energized open, setting NO) or closed (de-energized closed, setting  NC) when no power supply is applied.

Temperature sensor roomfloor
The room temperature controller cover features a built-in temperature sensor, which is used to detect the room temperature. With the Bluetooth version, an app can be used to integrate a brightness/temperature sensor. In this case, the internal sensor will be deactivated.
In conjunction with a room, the temperature controller inserts a remote sensor that can be connected, either to measure the room temperature or limit the maximum floor temperature.
The following settings are possible.
room: The room temperature is measured using the internal temperature sensor or the BT brightness and temperature sensor.
floor: The room temperature is measured using the remote sensor. The internal temperature sensor is deactivated.
room and floor: The room temperature is measured using the internal temperature sensor and the floor temperature is measured using the remote sensor for monitoring the floor temperature. If the maximum temperature is exceeded, the floor heating will be switched off until the floor temperature is below the maximum value again. This way, an unpleasantly hot floor is avoided.

Behavior after a mains voltage failure
Voltage failure less than power reserve

  • All data and settings are preserved

Voltage failure greater than power reserve

  • The date and time are reset and need to be set again
  • Temperature control is performed like before the power failure
  • All times set in the weekly timer are retained
  • All settings are retained

Default setting
Times for comfortGIRA System 3000 Room Temperature Controller Display - icon 3 and reduction of temperature GIRA System 3000 Room Temperature Controller Display - icon 5

Mo-Fr Sa-Su
1 6:00 8:30 7:00 22:00
2 12:00 14:00 –:– –:–
(4)3 17:00 22:00 –:– –:–
  • Automatic mode is active
  • Automatic summer time changeover is active
  • Controller output depending on insert: room temperature controller insert = pulse width
    modulation, switch insert = two-point control
  • Valve drive output is de-energized closed (NC)
  • Optimized heating up is not active
  • Temperature drop detection is active
  • The heating and cooling mode is not active
  • GIRA System 3000 Room Temperature Controller Display - icon 3Comfort temperature: 21 °C, GIRA System 3000 Room Temperature Controller Display - icon 5reduction temperature: 18 °C
    GIRA System 3000 Room Temperature Controller Display - icon 15Frost protection temperature: 7 °C, GIRA System 3000 Room Temperature Controller Display - icon 4cooling temperature: 24 °C
  • The internal temperature sensor for room temperature measurement is active
  • Display switch-off after 2 minutes of inactivity (no button actuation) is active

Commissioning

Setting date, time, and other parameters
GIRA System 3000 Room Temperature Controller Display - icon 16With the Bluetooth version of the device, commissioning can also be performed conveniently via the app using a mobile end device. Before proceeding, the app must be installed on the mobile end device and a connection to the room temperature controller cover must be established (see ‘Installing app on mobile end device’ and ‘Coupling mobile end device via Bluetooth’).

When the year is flashing on the display, you must set or confirm the data listed in the table.

  • Briefly press the – or + button to change values or toggle between YES / No.
  • A long press of the – or + button accelerates value changes.
  • Press the GIRA System 3000 Room Temperature Controller Display - icon 7button to go back to the menu.
  • Press the ok button to apply the setting and call the next value. After editing the last parameter, all values will be saved and automatic mode will be invoked.
Parameters Display icon Setting option/Default setting
Year GIRA System 3000 Room Temperature Controller Display - icon 17 2019 or later
Month GIRA System 3000 Room Temperature Controller Display - icon 17 01 … 12
Day GIRA System 3000 Room Temperature Controller Display - icon 17 01 … 31
Hour GIRA System 3000 Room Temperature Controller Display - icon 17 00 … 12 … 23
Minute GIRA System 3000 Room Temperature Controller Display - icon 17 00 … 59
Automatic summertime changeover GIRA System 3000 Room Temperature Controller Display - icon 17S/WGIRA System 3000 Room Temperature Controller Display - icon 14 YES / No
Controller output 1) 2P YES / No
Valve adaptation 2) GIRA System 3000 Room Temperature Controller Display - icon 13 NO / NC
Optimized heating up GIRA System 3000 Room Temperature Controller Display - icon 18 YES / No
Temperature drop detection GIRA System 3000 Room Temperature Controller Display - icon 11 GIRA System 3000 Room Temperature Controller Display - icon 27 YES / No
Comfort temp. GIRA System 3000 Room Temperature Controller Display - icon 20 5 … 21.0 … 30 °C
Reduction temp. GIRA System 3000 Room Temperature Controller Display - icon 20 5 … 18.0 … 30 °C
Frost protection GIRA System 3000 Room Temperature Controller Display - icon 15 5 … 7.0 … 30 °C
Heating/cooling GIRA System 3000 Room Temperature Controller Display - icon 4 YES / No
3)
Cooling temp.
GIRA System 3000 Room Temperature Controller Display - icon 22 5 … 24.0 … 30 °C
Temperature sensor room room, floor or both
Max. floor temp. floor max. 10 … 35.0 … 45 °C
Offset GIRA System 3000 Room Temperature Controller Display - icon 23 -5 … 0.0 … +5 °C
  1. Pulse width modulation (PWM) = No, two-point control = YES (see functional description).
  2. NC: Valve is closed when de-energized.
  3. NO: Valve is open when de-energized.
  4. This parameter only appears if the device is set to “Heating and cooling”.
  5. This parameter only appears if the room and floor have been set for the temperature sensor.

Install the app on a mobile end device (Bluetooth version only)
The requirement for operation via the app is a mobile end device with a Bluetooth interface, running the Android operating system or iOS.

  • Download and install the Gira System 3000 App from the App Store (iOS) or Google Play Store (Android).
    Coupling mobile end device via Bluetooth (Bluetooth version only)
    Prerequisite: The insert must be connected. The cover is placed on the insert and the mobile end device is close to the cover.
  • In order to enter coupling mode (pairing) prior to initial commissioning, the GIRA System 3000 Room Temperature Controller Display - icon 9button must be pressed for more than 4 seconds until the GIRA System 3000 Room Temperature Controller Display - icon 24icon flashes in the display.
  • Activate coupling mode (pairing) after initial commissioning: Press the GIRA System 3000 Room Temperature Controller Display - icon 9button. GIRA System 3000 Room Temperature Controller Display - icon 141 flash in the display.
  • Use the – or + button to select the Bluetooth GIRA System 3000 Room Temperature Controller Display - icon 24menu item and confirm with ok. Then select YES and confirm once againGIRA System 3000 Room Temperature Controller Display - icon 24.
  • Start Gira System 3000 App and search for a device to be coupled (paired).
    “Thermostat” is displayed in the app.
  • Perform coupling.
    The coupling mode is automatically exited after successful coupling. When the connection between the mobile end device and the room temperature controller cover is active, the GIRA System 3000 Room Temperature Controller Display - icon 24icon in the display lights up permanently.
  • GIRA System 3000 Room Temperature Controller Display - icon 16If no coupling takes place, the coupling mode is automatically exited after approx. 1 minute.
  • GIRA System 3000 Room Temperature Controller Display - icon 16A maximum of 8 mobile end devices can be coupled with a cover. When coupling the 9th device, the least used device will be deleted.
  • GIRA System 3000 Room Temperature Controller Display - icon 16When power is applied again, the coupling can take place without a password within 2 minutes if a password has been configured via the app.

Operation

All settings and operations are also possible via the Bluetooth app.
Increasing or reducing the room temperature

  • Press the – or + button for less than 1 second.
    With every brief press of a button the setpoint temperature changes by 0.5 °C. The set value is retained in manual mode; in automatic mode, it is retained until the next switching time is reached.
    GIRA System 3000 Room Temperature Controller Display - icon 16In cooling mode, the – or + buttons cannot be used to change the setpoint temperature.
    GIRA System 3000 Room Temperature Controller Display - icon 16If the display is switched off or has been set to indicate the actual temperature or time, the – or + button will have to be pressed a second time or even more before a  change in the setpoint value takes place.
  • Press the – or + button for more than 1 second.
    In heating mode, the saved setpoint temperature is retrieved: – = reduction temperature + = comfort temperature
    GIRA System 3000 Room Temperature Controller Display - icon 16During a detected temperature drop, changing the setpoint temperature is not possible.

Activating the boost function (Bluetooth version only)
With the boost function, the output is switched on for a maximum of 5 minutes without temperature control action in order to obtain a temporary increase in temperature.

  • GIRA System 3000 Room Temperature Controller Display - icon 16The boost function can only be activated while in heating mode and no temperature drop has been detected.
  • Press the GIRA System 3000 Room Temperature Controller Display - icon 25button for longer than 4 seconds.
  • GIRA System 3000 Room Temperature Controller Display - icon 16The boost function is active. The display counts down from 300 seconds and then switches back to normal mode.
    Press the GIRA System 3000 Room Temperature Controller Display - icon 25button once again for more than 4 seconds to terminate the boost function prematurely.

Activating the holiday mode (Bluetooth version only)
The holiday mode can only be set and activated via the app.
When the holiday mode is active, the display indicates the setpoint temperature for the holiday period and switches between the GIRA System 3000 Room Temperature Controller Display - icon 3and GIRA System 3000 Room Temperature Controller Display - icon 5icons.
Briefly actuating the – or + button interrupts the holiday mode and the temperature set at that moment is maintained by the controller.
Briefly actuating the GIRA System 3000 Room Temperature Controller Display - icon 25button restarts the holiday mode.

Activate functions

Automatic operation/manual operation
Pressing the GIRA System 3000 Room Temperature Controller Display - icon 25button toggles between automatic mode and manual mode.
GIRA System 3000 Room Temperature Controller Display - icon 16If all timer blocks are deactivated, the cover will automatically switch to manual mode.
Automatic mode cannot be activated.

GIRA System 3000 Room Temperature Controller Display - figure 2Figure 2: Setpoint temperature display in automatic mode

The setpoint temperature is shown in the display. Active heating is indicated by the flashing heating icon. If heating is not active, the GIRA System 3000 Room Temperature Controller Display - icon 6icon lights up permanently. TheGIRA System 3000 Room Temperature Controller Display - icon 3 icon indicates that the system is being regulated to the saved comfort temperature.

GIRA System 3000 Room Temperature Controller Display - figure 3Figure 3: Setpoint temperature display in manual mode

In manual mode, the GIRA System 3000 Room Temperature Controller Display - icon 25icon appears in addition to the normal display.

Programming menu overview

GIRA System 3000 Room Temperature Controller Display - figure 4Figure 4: Programming menu

GIRA System 3000 Room Temperature Controller Display - icon 26Three memory areas for comfort and reduction temperature for the two weekday blocks Mo – Fr and Sa – Su
GIRA System 3000 Room Temperature Controller Display - icon 24Activate coupling mode (see Commissioning section)
GIRA System 3000 Room Temperature Controller Display - icon 17Setting date, time, and automatic summer time changeover
GIRA System 3000 Room Temperature Controller Display - icon 27Setting the comfort temperature, reduction temperature, and cooling temperature, activating optimized heating up, temperature drop detection, and setting an offset value

Press the GIRA System 3000 Room Temperature Controller Display - icon 28button to call up or exit the programming menu.
Navigate through the menu with the – or + button and confirm the selection with the ok button.
Bluetooth version only: If the extended operating mode has been activated via the app, the three memory areas are hidden in the menu. Changes to the switching times can only
be made via the app then.

Setting switching times

  • Press GIRA System 3000 Room Temperature Controller Display - icon 28button.
  • Select memory areaGIRA System 3000 Room Temperature Controller Display - icon 29
  • Confirm with the ok button.
    YES or No flashes in the display.
  • No is used to deactivate all times in the selected memory area.
    GIRA System 3000 Room Temperature Controller Display - icon 16The switching times of the memory areas (ƙ, Ʀ, Ʊ) must not overlap or be set to an identical time. Otherwise, temperature control cannot be reliably performed.
    GIRA System 3000 Room Temperature Controller Display - icon 16The available memory areas are described in the table in the Default setting section.
  • Change selection with the – or + button and confirm with the ok button.
    The first switching time for the comfort temperature appears on the display.
  • The flashing switching time can be changed with the – or + button and saved with the ƨ button. The times for comfort and reduction temperature can be saved consecutively for the weekday blocks Mo-Fr and Sa-Su each.
    The menu is exited upon saving the last time setting.
    Set the clock – -:- – to deactivate individual switching times.
    GIRA System 3000 Room Temperature Controller Display - icon 16After one minute without any operation, the menu is exited automatically without saving.
  • Set date and time
  • Press GIRA System 3000 Room Temperature Controller Display - icon 28button.
  • Setting the GIRA System 3000 Room Temperature Controller Display - icon 17
  • Confirm with the ok button.
    The year flashes on the display.
  • Date, time, and automatic summer time changeover can be edited as described in the Commissioning section.
  • Changing temperature parameters
  • Press GIRA System 3000 Room Temperature Controller Display - icon 9button.
  • Setting the GIRA System 3000 Room Temperature Controller Display - icon 27
  • Confirm with the ok button.
    The setpoint value for the comfort temperature GIRA System 3000 Room Temperature Controller Display - icon 3flashes in the display.
  • Change the setpoint value with the – or + button and confirm with the ok button.
  • Use the same procedure to set the values for the reduction temperature GIRA System 3000 Room Temperature Controller Display - icon 5and, if parameterized, the cooling temperature GIRA System 3000 Room Temperature Controller Display - icon 27as well.
  • Activate/deactivate optimized heating up GIRA System 3000 Room Temperature Controller Display - icon 12and temperature drop detectionGIRA System 3000 Room Temperature Controller Display - icon 11.
    Set the offset value -/+.
    GIRA System 3000 Room Temperature Controller Display - icon 16After value changes, the device will start with the saved setpoint values.
  • Activating/deactivating the operating lock
    An activated operating lock prevents users from directly operating the system on the cover.
  • Press and hold the – and GIRA System 3000 Room Temperature Controller Display - icon 25buttons simultaneously for more than one second.
    GIRA System 3000 Room Temperature Controller Display - icon 31appears in addition to the normal display. The operating lock is active.
    Also, press and hold the – and GIRA System 3000 Room Temperature Controller Display - icon 25buttons simultaneously for more than one second to deactivate the operating lock.
  • Changing control parameters
    Various settings are made during initial commissioning in order to adapt the temperature control to local conditions. This menu item can be used to change the settings.
    Press GIRA System 3000 Room Temperature Controller Display - icon 28and GIRA System 3000 Room Temperature Controller Display - icon 7buttons simultaneously for longer than 10 seconds.
    While actuating the buttons, a countdown from 9 to 0 is displayed.
    The 2P and YES icons or No appear in the display.
    The parameters can be confirmed (Ok button) or changed (– or + button) as described in the Commissioning section.
    GIRA System 3000 Room Temperature Controller Display - icon 16After value changes, the device will start with the saved setpoint values.

Saving current time as switching time, quick programming
Switching times can also be saved without calling up the programming menu. The current time is saved as the switching time for Mo-Fr and Sa-So.
GIRA System 3000 Room Temperature Controller Display - icon 16Quick programming overwrites the existing reduction or comfort temperature in the first memory areaGIRA System 3000 Room Temperature Controller Display - icon 14. The switching times from memory areas 2 and 3 are deactivated.

  • Press and hold the ok button and additionally press the + button for the comfort temperature GIRA System 3000 Room Temperature Controller Display - icon 3for more than 1 second. or
  • Press and hold the ok button and additionally press the – button for the reduction of temperature GIRA System 3000 Room Temperature Controller Display - icon 5for more than 1 second.
    SAVE appears in the display. The current time is saved as the new switching time for the comfort GIRA System 3000 Room Temperature Controller Display - icon 3or reduction of temperatureGIRA System 3000 Room Temperature Controller Display - icon 5.
    GIRA System 3000 Room Temperature Controller Display - icon 16Bluetooth version only: If the extended operating mode has been activated via the app, the quick saving option is not available.

Display: setpoint temperature, actual temperature, or current time
After commissioning, the device indicates the setpoint temperature and switches off the display after 2 minutes without any operation. Alternatively, the actual temperature or current time can be displayed.
The display can also remain switched on continuously.

  • Press the ok and GIRA System 3000 Room Temperature Controller Display - icon 25buttons simultaneously for longer than 10 seconds.
    A countdown runs on the display. When “0” is reached, the actual temperature is shown in the display.
    The active temperature sensor is shown in the display when the actual temperature indication is selected. room or floor and floor: The measured value is provided by the internal sensor or the Bluetooth sensor.
    floor: The measured value is provided by the remote sensor connected to the insert.
  • Press the ƨ and Ƙ buttons simultaneously again for more than 10 seconds. A countdown runs in the display. When “0” is reached, the current time is displayed.
    GIRA System 3000 Room Temperature Controller Display - icon 16Use the same operating step to switch back to the setpoint temperature display.
  • Press the ƨ and Ƨ buttons simultaneously for longer than 10 seconds. A countdown runs on the display. When “0” is reached, the display is switched on continuously.
    GIRA System 3000 Room Temperature Controller Display - icon 16Use the same operating step to switch the display off again after 2 minutes.  The display briefly turns dark to indicate confirmation.

In setpoint or actual temperature display mode, the ok or GIRA System 3000 Room Temperature Controller Display - icon 7button can be pressed for more than 1 second to display the current time as long as the button is actuated.

Resetting the cover to the default setting

  • Press the GIRA System 3000 Room Temperature Controller Display - icon 7and GIRA System 3000 Room Temperature Controller Display - icon 25buttons simultaneously for 10 seconds.
    A countdown runs on the display. The reset is performed with “0”.
    The default setting is restored. The year flashes in the display and the device must be recommissioned (see Commissioning section).
    GIRA System 3000 Room Temperature Controller Display - icon 16With the Bluetooth cover version, resetting to default settings can only be performed during the first 2 minutes after switching on mains voltage.
    GIRA System 3000 Room Temperature Controller Display - icon 16After resetting to the default settings, the Bluetooth device has to be removed from the app. On iOS equipment, the device also has to be removed from the list of paired Bluetooth devices (Settings/Bluetooth). Otherwise, re-pairing will not be possible.

Information for electrically skilled persons

GIRA System 3000 Room Temperature Controller Display - icon 30This device includes an integrated battery. At the end of its useful life, dispose of the device together with the battery in accordance with the environmental regulations. Do not throw devices into household waste. Consult your local authorities about environmentally friendly disposal. According to statutory provisions, the end consumer is obligated to return the device. 

DANGER!
Mortal danger of electric shock
Disconnect the device. Cover up live parts.

Fitting the device
Switch or room temperature controller inserts are mounted and connected properly (see instructions of the relevant inserts).

  • Fit the cover with the frame on the insert.
  • Switch on mains voltage.
    All display icons are briefly actuated and the software version is displayed for approx. 3 seconds. Subsequently, the year flashes in the display and the device must be commissioned (Commissioning).

If Err appears in the display, the cover was previously connected to another insert. To enable operation again, either place the cover onto the correct insert or press the + and –  buttons for more than 4 seconds.
After changing the insert, the year flashes in the display and all settings must be confirmed (see Commissioning section).

Overview of button combinations

Button combination Length of button press Display Reading What happens
— andGIRA System 3000 Room Temperature Controller Display - icon 25 Longer than one second is shown or hidden Button lockout is activated or deactivated
GIRA System 3000 Room Temperature Controller Display - icon 28andGIRA System 3000 Room Temperature Controller Display - icon 7 Longer than 10 seconds Countdown from 9 to 0 Parameters for control can be changed
ok and – or + Longer than one second SAVE The current time is saved as the switching time.
ok and GIRA System 3000 Room Temperature Controller Display - icon 2 Longer than 10 seconds Countdown from 9 to 0 Display: toggling between setpoint temperature, actual temperature, and current time
ok andGIRA System 3000 Room Temperature Controller Display - icon 7 Longer than 10 seconds Countdown from 9 to 0 Display: toggling between display permanently on and switch-off after 2 minutes
GIRA System 3000 Room Temperature Controller Display - icon 7 andGIRA System 3000 Room Temperature Controller Display - icon 25 Longer than 10 seconds Countdown from 9 to 0 The default selling for the device is restored
+ and — Longer than 4 seconds Err Canceling of lockout when changing cover or insert

Technical data

Ambient temperature -5 … +45 °C
Storage/transport temperature -20 … +70 °C
Accuracy per month ± 10 s
Power reserve > 4 h
Additional specifications for the Bluetooth version
Radiofrequency 2.400 … 2.483 GHz
Transmission capacity max. 2.5 mW, Class 2

The parameter list (Bluetooth version only)

Adjustable parameters via app
Device parameters

Parameters Setting options Default setting Explanations
Setting the operating mode Comfort and standby, ex- tended mode
Default setting: comfort and standby
Comfort and standby:
Timer with three memory areas; comfort and reduction time for Mo-Fr and Sa-Su in each memory area
Extended mode:
Weekly timer with 40 individually programmable switch points and temperatures
Note: In extended mode, the switching points can only be displayed and changed via the app.
Note: When switching from extended mode to comfort and standby, the switching times defined in the device will be lost.
Cooling On, Off
Default setting: Off
When the parameter is switched on, the cooling input on the insert can be used to activate the cooling mode.
Note: If the cooling mode cannot be activated via the insert, a jumper can be installed on the insert between L and the cooling input. This will enable the cooling mode to be activated or deactivated via this parameter.
Setting temperatures Comfort, standby, frost protection, and cooling The setpoint values for the temperatures can be set and changed.
Maximum and minimum temperature values 5 °C … 30 °C This parameter is used to limit the range in which temperature setpoint values can be set.
The limits apply to the comfort temperature, reduction temperature, and holiday temperature.
Regardless of the set minimum temperature, the frost protection temperature is the lowest temperature the controller can adjust.
Teaching in a temperature sensor The input of the MAC address After the MAC address of the BT brightness/ temperature sensor has been entered, the transmitted temperature is used for measuring the room temperature.
The internal temperature sensor in the cover is inactive.
Note: When selecting the temperature sensor, the internal sensor must be an active, room icon.
Temperature sensor operating mode Room, floor, room, and floor Default setting: room Room:
The room temperature is measured using the internal temperature sensor or the brightness/ temperature sensor if taught.
Parameters Setting options Default setting Explanations
Floor:
The room temperature is measured using the remote sensor. The internal temperature sensor is deactivated.
Room and floor:
The room temperature is measured using the internal temperature sensor or the brightness/ temperature sensor if taught in. The floor temperature is measured using the remote sensor in order to allow for monitoring of the maximum floor temperature.
Temperature
sensor offset
Offset setting:
– 5 °C … +5 °C
If the system detects that the displayed actual temperature differs from the general room temperature, this parameter can be used to enter a correction value. The actual temperature will then be corrected by this offset value.
Valve control, control method PWM control, two-point control
Default setting depending on insert: PWM control for room temperature controller insert, two-point control for switch insert
Pulse width modulated control (PWM):
The output is not permanently actuated, but only for a time period (pulse width) that depends on the difference between the setpoint and actual temperature. This method brings the actual temperature gradually closer to the setpoint temperature. The cycle time is 15 minutes.
Two-point control:
The output remains switched on until the selected setpoint temperature has been exceeded by 0.5 °C. The output will not be switched on again until the setpoint value is undercut by 0.5 °C.
Valve control, valve type Active closing (NC), active opening (NO)
Default setting: Active closing (NC)
This parameter is used to adapt to the electrothermal valve drives.
Active closing (NC):
The available drive is closed when de-energized.
Active opening (NO):
The available drive is open when de-energized.
Temperature drop detection On, Off
Default setting: On
In case of a significant temperature drop, e.g. after opening a window, the system regulates the frost protection temperature for a maximum of 30 minutes.
Optimized heating up On, Off
Default setting: Off
Heating is started at most 4 hours before the switching time so that the desired temperature has been reached at the switching time. Optimized heating up is optimized for panel heating/radiators.
Local display Setpoint temperature, ac- tual temperature, time
Default setting: setpoint temperature
Setpoint temperature:
The cover displays the setpoint temperature.
Actual temperature:
The cover displays the actual temperature. When pressing the — or + button, the display briefly switches to the setpoint temperature.
Parameters Setting options Default setting Explanations
The room or floor sensor icon is shown in the display when the actual temperature indication is selected.
Time:
The device displays the current time of day. When pressing the — or + button, the display briefly switches to the setpoint temperature.
Display Automatic, permanently ac- tivated
Default setting: automatic
Automatic:
The display remains switched on for 2 minutes after the last operation and then switches off.
Permanently activated
The display remains permanently switched on.
Operation No lock, operating lock, device lock
Default setting: no lock
Operating lock:
An activated operating lock prevents users from directly operating the system on the cover. Operation via the app remains possible. 8 appears on the cover in addition to the normal display. The operating lock can also be deactivated on the cover.
Device lock:
An activated device lock prevents users from directly operating the system on the cover. Operation via the app remains possible. 8 appears on the cover in addition to the normal display. The device lock cannot be deactivated on the cover.

Conformity

  • Gira Giersiepen GmbH & Co. KG hereby declares that the radio system type art. no. 5394 .. meets the directive 2014/53/EU. You can find the full article number on the device. The complete text of the EU Declaration of Conformity is available under the Internet address: www.gira.de/konformitaet
  • Warranty
  • The warranty is provided in accordance with statutory requirements via the specialist trade.
    Please submit or send faulty devices postage paid together with an error description to your responsible salesperson (specialist trade/installation company/electrical specialist trade). They will forward the devices to the Gira Service Center.

Gira
Giersiepen GmbH & Co. KG
Elektro-InstallationsSysteme
Industriegebiet Mermbach
Dahlienstraße
42477 Radevormwald
Postfach 12 20
42461 Radevormwald
Deutschland
Tel +49(0)21 95 – 602-0
Fax +49(0)21 95 – 602-191
www.gira.de
info@gira.de

Documents / Resources

GIRA System 3000 Room Temperature Controller Display [pdf] Instructions
System 3000, Room Temperature Controller Display
GIRA System 3000 Room Temperature Controller [pdf] Instruction Manual
System 3000, Room Temperature Controller
GIRA System 3000 Room Temperature Controller [pdf] Instruction Manual
System 3000 Room Temperature Controller, System 3000, Room Temperature Controller, Temperature Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *