Product Information

Product Specifications

  • Model Numbers: FVM4X2400B, FVM4X3600B, FVM4X4800B, FVM4X6000B
  • Tons: 2, 3, 4, 5
  • Nominal BTU: 24,000, 36,000, 48,000,
    60,000
  • CFM (L/s) Range:
    • Low: 350 (165) – 540 (255)
    • High: 1200 (566) – 2000 (944)
  • Dimensions H x W x D:
    • 2 Tons: 42-11/16 x 17-5/8 x 22-1/16 in. (1084 x 448 x 560 mm)
    • 3 Tons: 53-7/16 x 21-1/8 x 22-1/16 in. (1357 x 537 x 560 mm)
    • 4 Tons: 53-7/16 x 21-1/8 x 22-1/16 in. (1357 x 537 x 560 mm)
    • 5 Tons: 59-3/16 x 24-11/16 x 22-1/16 in. (1503 x 627 x 560 mm)
  • Filter Size:
    • 2 Tons: 16-3/8 x 21-1/2 in. (416 x 546 mm)
    • 3 Tons: 19-7/8 x 21-1/2 in. (505 x 546 mm)
    • 4 Tons: 19-7/8 x 21-1/2 in. (505 x 546 mm)
    • 5 Tons: 23-5/16 x 21-1/2 in. (592 x 546 mm)
  • Ship Weight: 135 lbs (61 kg), 150 lbs (68 kg), 172 lbs (78 kg), 207 lbs (94 kg)

FAQ

  • Q: How often should I replace the filters?
    • A: Filters should typically be replaced every 3 to 6 months, depending on usage and air quality.

Product Usage Instructions

Installation

Follow the installation guide provided with the product carefully. Ensure proper positioning and secure installation.

Maintenance

Regular maintenance is essential for optimal performance. Clean or replace filters as recommended in the manual.

Troubleshooting

If you encounter any issues with the product, refer to the troubleshooting section of the manual or contact customer support for assistance.

ALL MODELS

  • 2, 3, 4, and 5 Tons
  • Supports two−stage outdoor units
  • Available for environmentally balanced R−410A systems
  • Bolt−on, hard shut−off TXV metering device factory installed on all models
  • Sweat connections
  • Primary and secondary drain fittings with brass inserts
  • Time delay relay (TDR)
  • Field-installed heater packages from 5 kW − 30 kW available separately
  • HUD-approved for manufactured housing
  • 208/230−1−60 supply voltage
  • Multiposition installation − upflow or horizontal left standard, horizontal right with minor modification (field convertible to downflow with accessory kits)
  • Filter (washable) factory supplied
  • Heat staging option
  • Dehumidification function with standardized logic (same as furnaces and SPP).
  • 1 inch (25mm) thick insulation with R value of 4.2

PERFORMANCE

  • Variable speed ECM motor on all models
  • Adjustable cooling and heating ON/OFF delay
  • Heat Pump Comfort option to provide higher than normal heating air delivery temperature
  • Assembled at the factory compliant with low leak requirements of less than 2% cabinet leakage rate at 0.5 inches W.C. and 1.4% cabinet leakage rate at 0.5 inches W.C. when tested in accordance with ASHRAE 193 standard.

EASY TO INSTALL AND SERVICE

  • Multiple electrical entry locations
  • TXV and manifold positioned to the side for easier cleaning
  • Zero clearance without heaters

WARRANTY

  • 10 year No Hassle replacement limited warranty
  • 5-year parts limited warranty
  • With timely registration, an additional 5 year parts limited warranty
  • For owner-occupied, residential applications only. See warranty certificate for complete details and restrictions, including warranty coverage for other applications.

Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org.

Model Number  

Tons

Nominal BTU CFM (L/s) Range Dimensions

H x W x D in. (mm)

 

Filter Size in. (mm)

Ship Wt. lbs. (kg)
Low High
FVM4X2400B** 2 24,000 350 (165) 1200

(566)

42−11/16 x 17−5/8 x 22−1/16 (1084 x 448 x 560) 16−3/8 x 21−1/2 (416 x 546) 135 (61)
FVM4X3600B** 3 36,000 415 (196) 1400

(661)

53−7/16 x 21−1/8 x 22−1/16

(1357 x 537 x 560)

19−7/8 x 21−1/2

(505 x 546)

150 (68)
FVM4X4800B** 4 48,000 425 (201) 1600

(755)

53−7/16 x 21−1/8 x 22−1/16

(1357 x 537 x 560)

19−7/8 x 21−1/2

(505 x 546)

172 (78)
FVM4X6000B** 5 60,000 540 (255) 2000

(944)

59−3/16 x 24−11/16 x 22−1/16 (1503 x 627 x 560) 23−5/16 x 21−1/2 (592 x 546) 207 (94)
  • B = Copper Tube, Aluminum Fin Evaporator
  • BL = Aluminum Tube, Aluminum Fin Evaporator
  • BT = Tin Coated Copper Tube, Aluminum Fin Evaporator

PRODUCT SPECIFICATIONSFVM4X-B-FVM4X2400B-Variable-Speed-Fan-Coils-FIG-1

ACCESSORIES PART NUMBER IDENTIFICATION GUIDEFVM4X-B-FVM4X2400B-Variable-Speed-Fan-Coils-FIG-2

ELECTRIC HEATER MODEL NUMBER IDENTIFICATION GUIDEFVM4X-B-FVM4X2400B-Variable-Speed-Fan-Coils-FIG-3

FVM4X-B-FVM4X2400B-Variable-Speed-Fan-Coils-FIG-4 FVM4X-B-FVM4X2400B-Variable-Speed-Fan-Coils-FIG-5

Dimensions Inches

FVM4X-B-FVM4X2400B-Variable-Speed-Fan-Coils-FIG-8 FVM4X-B-FVM4X2400B-Variable-Speed-Fan-Coils-FIG-9

 

FVM4X-B-FVM4X2400B-Variable-Speed-Fan-Coils-FIG-10 FVM4X-B-FVM4X2400B-Variable-Speed-Fan-Coils-FIG-11

DIMENSIONAL DATA (refer to drawings on previous pages)
FVM4X

Model

Size (tons) Dimensions Inches (English) Coil Type
A B C D E F G H J
2400 2 42−11/16 17−5/8 15−3/4 15−3/8 10−3/4 18−9/16 18−1/4 N/A N/A “A”
3600 3 53−7/16 21−1/8 19−1/4 19−1/8 19−3/16 26−15/16 27−1/2 N/A 19 Slope
4800 4 53−7/16 21−1/8 19−1/4 19−1/8 19−1/2 27−1/4 26−15/16 N/A N/A “A”
6000 5 59−3/16 24−11/16 22−3/4 22−11/16 25−1/4 32−15/16 32−5/8 34−1/16 N/A “A”

 

FVM4X

Model

Size (tons) Dimensions mm (SI Metric) Coil Type
A B C D E F G H J
2400 2 1084 448 400 397 273 472 464 N/A N/A “A”
3600 3 1357 537 489 486 487 684 699 N/A 483 Slope
4800 4 1357 537 489 486 495 692 684 N/A N/A “A”
6000 5 1503 627 578 576 641 837 829 865 N/A “A”
PHYSICAL DATA
 

FVM4X

Model Size
2400 3600 4800 6000
Blower Data
Motor type Variable Speed ECM motor
HP 1/2 1/2 1/2 3/4
Filter Data (factory supplied, washable)
Filter Size in. (mm) 16−3/8 x 21−1/2 (416 x 546) 19−7/8 x 21−1/2 (505 x 546) 23−5/16 x 21−1/2 (592 x 546)
Coil Data (all coils are 3 row, 141/2 fins per inch, wavy lanced bare aluminum fin)
Face Area ft2 (m2) 3.46 (0.32) 3.46 (0.32) 5.93 (0.55) 7.42 (0.69)
Refrigerant Line Connections (sweat)
Liquid in. (mm) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10)
Suction in. (mm) 3/4 (19) 7/8 (22) 7/8 (22) 7/8 (22)
ELECTRICAL DATA, FAN COIL ONLY WITHOUT ELECTRIC HEAT
 

 

FVM4X Model

208/230V, single phase, 60 Hz
Motor Full Load Amps (FLA) Minimum Circuit Ampacity (MCA) Maximum Fuse/Ckt Bkr Amps (Max OverCurrent Protection − MOCP)
2400 4.3 5.4 15
3600 4.3 5.4 15
4800 4.3 5.4 15
6000 6.8 8.5 15
AIRFLOW PERFORMANCE CFM RANGE
FVM4X Model Use with Outdoor Unit Size CFM (L/s) Range
2400 18, 24, 30, 36 350−1200 (165 − 566)
3600 24, 30, 36, 42 415−1400 (196 − 661)
4800 30, 36, 42, 48 425−1600 (201 − 755)
6000 36, 42, 48, 60 540−2000 (255 − 944)
AIRFLOW PERFORMANCE CFM IN COOLING MODE (A/C or Heat Pump)
 

FVM4X

Model

Outdoor Unit Size Single Stage

Cooling

TwoStage Cooling  

Fan Only

High Low
Nominal Dehum Nominal Dehum Nominal Dehum Low Med Hi
 

2400

18 525 420 Two−Stage outdoor unit not offered 350 420 525
24 700 560 700 560 560 450 350 560 700
30 875 700 Two−Stage outdoor unit not offered 440 700 875
36 1050 840 1050 840 840 670 525 840 1050
 

3600

24 700 560 700 560 560 450 415 560 700
30 875 700 Two−Stage outdoor unit not offered 440 700 875
36 1050 840 1050 840 840 670 525 840 1050
42 1225 980 Two−Stage outdoor unit not offered 615 980 1225
 

4800

30 875 700 Two−Stage outdoor unit not offered 440 700 875
36 1050 840 1050 840 840 670 525 840 1050
42 1225 980 Two−Stage outdoor unit not offered 615 980 1225
48 1400 1120 1400 1120 1120 900 700 1120 1400
 

6000

36 1050 840 1050 840 840 670 540 840 1050
42 1225 980 Two−Stage outdoor unit not offered 615 980 1225
48 1400 1120 1400 1120 1120 900 700 1120 1400
60 1750 1400 1750 1400 1400 1120 875 1400 1750

NOTES:

  1. The above airflows result with the AC/HP CFM ADJUST select jumper set on NOM.
  2. Airflow can be adjusted +15% or −10% by selecting Hi or Lo respectively for all modes except fan only.
  3. Dry coil at 230 volts and with 10kW heater and filter installed.
  4. Airflows shown are valid for systems with total external static pressure between 0.1 and 0.7 inches water column
AIRFLOW PERFORMANCE CFM IN HEAT PUMP HEATING MODE ONLY
 

FVM4X

Model

Outdoor Unit Size Single Stage HP

Heating

TwoStage HP Heating  

Fan Only

High Low
Comfort Eff Comfort Eff Comfort Eff Low Med Hi
 

2400

18 475 525 Two−Stage outdoor unit not offered 350 380 475
24 630 700 630 700 505 560 350 505 630
30 785 875 Two−Stage outdoor unit not offered 440 630 785
36 945 1050 945 1050 755 840 525 755 945
 

3600

24 630 700 630 700 505 560 415 505 630
30 785 875 Two−Stage outdoor unit not offered 440 630 785
36 945 1050 945 1050 755 840 525 755 945
42 1100 1225 Two−Stage outdoor unit not offered 615 880 1100
 

4800

30 785 875 Two−Stage outdoor unit not offered 440 630 785
36 945 1050 945 1050 755 840 525 755 945
42 1100 1225 Two−Stage outdoor unit not offered 615 880 1100
48 1260 1400 1260 1400 1010 1120 700 1010 1260
 

6000

36 945 1050 945 1050 755 840 540 755 945
42 1100 1225 Two−Stage outdoor unit not offered 615 880 1100
48 1260 1400 1260 1400 1010 1120 700 1010 1260
60 1575 1750 1575 1750 1260 1400 875 1260 1575

NOTES:

  1. The above airflows result with the AC/HP CFM ADJUST select jumper set on NOM.
  2. Airflow can be adjusted +15% or −10% by selecting Hi or Lo respectively for all modes except fan only.
  3. Dry coil at 230 volts and with 10kW heater and filter installed.
  4. Airflows shown are valid for systems with total external static pressure between 0.1 and 0.7 inches water column
AIRFLOW DELIVERY (CFM)
 

 

FVM4X

Model

Outdoor Unit Capacity

(BTUH)

Electric Heater kW Range
0 5 0 10 0 15 0 20
LO NOM HI LO NOM HI LO NOM HI LO NOM HI
 

2400

18 625 625 625 675 675 675 * * * * * *
24 650 725 835 * 725 835 875 875 875 * * *
30 815 905 1040 * 905 1040 900 900 1040 1100 1100 1100
36 980 1085 1250 980 1085 1250 980 1085 1250 1100 1100 1250
 

3600

24 675 725 835 875 875 * * * * * * *
30 815 905 1040 875 905 1040 1100 1100 1100 * * *
36 980 1085 1250 980 1085 1250 1100 1100 1250 1225 1225 1250
42 1140 1270 1460 1140 1270 1460 1140 1270 1460 1225 1270 1460
0 10 0 15 0 20 0 30
 

4800

30 975 975 1040 1100 1100 1100 * * * * * *
36 980 1085 1250 1100 1100 1250 1250 1250 1250 * * *
42 1140 1270 1460 1140 1270 1460 1250 1270 1460 * * *
48 1305 1450 1665 1305 1450 1665 1305 1450 1665 1500 1500 1665
 

6000

36 1100 1100 1250 1350 1350 1350 * * * * * *
42 1140 1270 1460 1350 1350 1460 1525 1525 1525 * * *
48 1305 1450 1665 1350 1450 1665 1525 1525 1665 1750 1750 1750
60 1630 1810 2085 1630 1810 2085 1630 1810 2085 1750 1810 2085
  • Airflow not recommended for heater/system size

NOTE: LO, NOM, and HI refer to AC/HP CFM ADJUST selection on the control board.

HEAT PUMP MINIMUM CFM WHEN USING ELECTRIC HEAT (CFM)
FVM4X

Model

Outdoor Unit Size Heater Size kW
5 8, 9, 10 15 18, 20 24, 30
 

2400

18 625 625 −− −− −−
24 650 725 875 −− −−
30 800 875 875 1040 −−
36 970 970 970 1040 −−
 

3600

24 675 875 −− −− −−
30 800 875 1100 1150 −−
36 975 975 1100 1225 −−
42 1125 1125 1125 1225 −−
 

4800

30 800 875 875 1150 −−
36 975 975 1100 1225 −−
42 1125 1125 1125 1225 −−
48 1305 1305 1305 1305 1400
 

6000

36 1100 1100 1350 1350 −−
42 1125 1125 1350 1350 −−
48 1300 1300 1350 1465 1750
60 1625 1625 1625 1750 1750
A/C MINIMUM CFM WHEN USING ELECTRIC HEAT (CFM)
 

FVM4X Model

Heater Size kW
5 8, 9, 10 15 18, 20 24, 30
2400  

Heater Only

625 625 725 875 −−
3600 675 700 850 1050 −−
4800 675 700 850 1050 1400
6000 1050 1050 1050 1050 1750

NOTES:

  1. Heater Only−Air conditioner with electric heater application.
  2. These airflows are minimum acceptable airflows as UL listed. Actual airflow delivered will be per airflow delivery chart for Electric Heating Modes.
ELECTRIC HEATER ELECTRICAL DATA
 

 

 

 

 

Heater Model

 

 

 

 

Heater kW

 

 

 

 

 

 

PHASE

 

 

 

 

INTERNAL CIRCUIT PROTECTION

 

 

HEATER AMPS 208/230V

BRANCH CIRCUIT
Min Ampacity * 208/230V Min Wire Size (AWG) 208/230V 1 Min Gnd Wire Size 208/230V Max Fuse/Ckt Bkr Amps 208/230V Max Wire Length 208/230V (Ft)‡‡
Single Circuit Dual Circuit Single Circuit Dual Circuit Single Circuit Dual Circuit Single Circuit Dual Circuit Single Circuit Dual Circuit Single Circuit Dual Circuit
230v 208v L1,l2 L3,L4 L1,L2 L3,L4 L1, L2 L3, L4 L1, L2 L3,L4 L1,L2 L3,L4 L1,L2 L3,L4
EHK05AKN* 5 3.8 1 None 18.1/20.0 26.0/28.4 10/10 10/10 30/30 66/66
EHK05AKN** 5 3.8 1 None 18.1/20.0 31.2/33.5 8/8 10/10 35/35 85/88
EHK05AKB* 5 3.8 1 Ckt Bkr 18.1/20.0 26.0/28.4 10/10 10/10 30/30 66/66
EHK05AKB** 5 3.8 1 Ckt Bkr 18.1/20.0 31.2/33.5 8/8 10/10 35/35 85/88
EHK07AKN 8 6.0 1 None 28.9/32.0 44.7/48.5 8/8 10/10 45/50 59/60
EHK07AKB 8 6.0 1 Ckt Bkr 28.9/32.0 44.7/48.5 8/8 10/10 45/50 59/60
EHK09AKCNt 9 6.8 1 None 32.8/36.0 49.5/53.5 8/6 10/10 50/60 54/87
9 6.8 3 None 18.8/20.8 32.0/34.5 8/8 10/10 35/35 83/85
EHK10AKN 10 7.5 1 None 36.2/40.0 53.8/58.5 6/6 10/10 60/60 78/80
EHK10AKB 10 7.5 1 Ckt Bkr 36.2/40.0 53.8/58.5 6/6 10/10 60/60 78/80
EHK15AKF 15 11.3 1 Fuse 54.2/59.9 36.2/40.0 18.1/20.0 76.3/83.4 53.8/58.5 22.7/25.0 4/4 6/6 10/10 8/8 10/10 10/10 80/90 60/60 25/25 88/89 78/80 75/76
EHK15AKB 15 11.3 1 Ckt Bkr 36.2/40.0 18.1/20.0 53.8/58.5 22.7/25.0 6/6 10/10 10/10 10/10 60/60 25/25 78/80 75/76
EHK15AHN 15 11.3 3 None 31.3/34.6 47.7/51.8 8/6 10/10 50/60 56/90
EHK18AHN 18 13.5 3 None 37.6/41.5 55.5/60.4 6/6 10/8 60/70 76/77
EHK20AKF 20 15.0 1 Fuse 72.3/79.9 36.2/40.0 36.2/40.0 98.9/108.4 53.8/58.5 45.3/50.0 3/2 6/6 8/8 8/6 10/10 10/10 100/110 60/60 50/50 85/109 78/80 59/59
EHK20AKB 20 15.0 1 Ckt Bkr 36.2/40.0 36.2/40.0 53.8/58.5 45.3/50.0 6/6 8/8 10/10 10/10 60/60 50/50 78/80 59/59
EHK25AHCF+ 24 18.0 3 Fuse 50.1/55.4 71.2/77.8 4/4 8/8 80/80 94/95
24 18.0 1 Fuse 86.7/95.5 116.9/127.9 1/1 6/6 125/150 115/116
EHK30AHCF+ 30 22.5 3 Fuse 62.6/69.2 86.8/95.0 3/3 8/8 90/100 97/98
30 22.5 1 Fuse 109.0/120.0 144.8/158.5 0/00 6/6 150/175 117/150
FIELD MULTIPOINT WIRING OR 24 AND 30 KW SINGLE PHASE
 

 

 

 

Heater Model

 

 

Heater kW

P H A S

E

 

Heater Amps 208/230V

Minimum Circuit Ampacity 208/230V * Minimum Wire Size (AWG) 208/230V+  

 

Min Gnd Wire Size 208/230V

Max Fuse/Ckt Bkr Amps 208/230V Max Wire Length 208/230V (FT)++
 

L1, L2

 

L3, L4

 

L5, L6

 

L1, L2

 

L3, L4

 

L5, L6

 

L1, L2

 

L3, L4

 

L5, L6

 

L1, L2

 

L3, L4

 

L5, L6

 

L1, L2

 

L3, L4

 

L5, L6

230V 208V
EHK25AHCF+ 24 18.0 1 28.9/32.0 28.9/32.0 28.9/32.0 44.7/48.5 36.2/40.0 36.2/40.0 8/8 8/8 8/8 10/10 45/50 40/40 40/40 59/60 73/73 73/73
EHK30AHCF+ 30 22.5 1 36.2/40.0 36.2/40.0 36.2/40.0 53.8/58.5 45.3/50.0 45.3/50.0 6/6 8/8 8/8 10/10 60/60 50/50 50/50 78/80 59/59 59/59

Notes:

Copper wire must be used. If other than uncoated (non-plated), 75° C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the National
Electric Code (ANSI/NFPA 70).

  • When used with Fan Coil model sizes 2400, 3600.
  • When used with Fan Coil model sizes 4800, 6000.
  • Includes blower motor amps of largest Fan Coil used with heater.
  • Supplied as single phase, field convertible to 3-phase.
  • Supplied as 3-phase, field convertible to single phase, single or multiple supply circuits.
  • Length shown is as measured one way along wire path between unit and service panel for a voltage drop not to exceed 2%.
ACCESSORIES
Part Number Description Use with Model Sizes
EBAC01DSC Disconnect Kit use with All single phase Heaters 5 kW thru 10 kW
EBAC02NCB  

Downflow Base Kit

2400B
EBAC03NCB 3600B, 4800B
EBAC04NCB 6000B
EBAC01DFS Downflow Conversion Kit − Slope Coil 3600B
EBAC02DFA Downflow Conversion Kit − “A” Coil 2400B, 4800B, 6000B
EBAC01SPK Single Point Wiring Kit only for use with 15 kW & 20 kW fused heaters
Square D® part # QOU14100JBAF Single Point Wiring Kit − Square D® Jumper Bar Assembly Only for use with

EHK15AKB and EHK20AKB breaker heaters

EBAC01FKM Filter Kit (washable, box of 12) Factory Supplied 2400B  

Factory Supplied

EBAC01FKL 3600B, 4800B
EBAC01FKX 6000B
NASA00201FR Standard Filter Rack (16 x 20 x 1 filter required) 2400B
NASA00301FR Standard Filter Rack (20 x 20 x 1 filter required) 3600B, 4800B
NASA00401FR Standard Filter Rack [quantity 2] (12 x 20 x 1 filter required) 6000B
EBAC01PLG No Heat (Plug) Kit (box of 6) ALL

(Factory Installed)

EBAC01CTK PVC Condensate Trap Kit (box of 50) ALL
EBAC01GSK Horizontal/Downflow Gasket Kit ALL

(required for horizontal right and downflow)

NAEA20101TX  

TXV Kit, R−22, Copper or Tin Coil Only

2400, 3600
NAEA20201TX 4800
NAEA20301TX 6000
NAEB20101TX  

TXV Kit, R−22, Aluminum Coil Only

2400BL, 3600BL
NAEB20201TX 4800BL
NAEB20301TX 6000BL
1191140 Door Gasket Kit ** ALL
  • This kit is for replacement of factory installed gaskets if they are damaged or removed from the fan coil.
ELECTRIC HEATERS
Part Number Description Use with Model Sizes
EHK05AKN 5 kW, single phase, no internal circuit protection ALL
EHK05AKB 5 kW, single phase, with circuit breakers ALL
EHK07AKN 8 kW, single phase, no internal circuit protection ALL
EHK07AKB 8 kW, single phase, with circuit breakers ALL
EHK09AKCN 9 kW, supplied as single phase, field convertible to

3−phase, no internal circuit protection

3600B, 4800B, 6000B
EHK10AKN 10 kW, single phase, no internal circuit protection ALL
EHK10AKB 10 kW, single phase, with circuit breakers ALL
EHK15AKF 15 kW, single phase, with fuses ALL
EHK15AKB 15 kW, single phase, with circuit breakers ALL†
EHK15AHN 15 kW, 3−phase, no internal circuit protection ALL†
EHK18AHN 18 kW, 3−phase, no internal circuit protection 4800B, 6000B
EHK20AKF 20 kW, single phase, with fuses ALL†
EHK20AKB 20 kW, single phase, with circuit breakers ALL†
EHK25AHCF 24 kW, supplied as 3−phase, field convertible to single phase, with fuses 4800B, 6000B
EHK30AHCF 30 kW, supplied as 3−phase, field convertible to single phase, with fuses 4800B, 6000B

15kW & 20kW are not recommended for specific heat pump applications, see AIRFLOW DELIVERY (CFM)

Copyright 2019 International Comfort Products Lewisburg, Tennessee 37091 USA