FSP PDU and Maintenance Bypass Switch Module User Guide

PDU and Maintenance Bypass Switch Module

Product Information

Specifications:

  • Model: Bypass Switch Module V. 2.0
  • Usage: External power distribution unit for UPS systems or
    voltage regulators
  • Mounting: Rack or Wall Mountable
  • Input Power: Mains power cord
  • Output Receptacles: Master for computer, Slave for
    peripherals
  • Functionality: Maintenance bypass, Power distribution, Power
    saving

Product Usage Instructions

1. Installation and Operation Inspection:

Remove the unit from the shipping package and inspect for any
damage. Contact carrier if damage found.

2. Rack Mount/Wall Mount the Unit:

The module can be mounted to a 19″ enclosure or wall. Follow the
provided instructions for installation.

3. Connect to the Wall Outlet:

Plug the input power cord into the wall outlet. Power LED
indicates normal mains power.

4. Connect UPS:

Connect UPS input/output cords to the corresponding sockets on
the unit.

5. Operation Transfer to Maintenance Bypass:

Ensure Power LED is lit, switch the bypass switch from Normal to
Bypass for utility power supply.

6. Connect Equipment:

Connect devices to Master and Slave output receptacles based on
power consumption requirements.

7. Transfer to UPS Protection:

After maintenance, reconnect UPS to the unit and switch bypass
from Bypass to Normal for UPS protection.

8. Master/Slave Function Operation:

Enable/disable Master/Slave function switch based on load
requirements. Slave LED indicates load status.

Frequently Asked Questions (FAQ)

Q: How do I know if the unit is receiving power?

A: The Power LED will indicate normal mains power by lighting
up.

Q: Can I mount the unit on a wall?

A: Yes, the unit can be wall-mounted using the provided
instructions.

Q: What is the purpose of the Master/Slave function?

A: The Master/Slave function helps in power saving by
controlling power to peripherals based on the main device
status.

“`

PDU & Maintenance

2. Product Overview

Bypass Switch Module

Quick Guide

V. 2.0

!Master output receptacle
(for connecting a computer)
$Slave output receptacles
(for connecting peripherals)
‘Socket to UPS output (Socket to UPS input

“Bypass switch #AC input %Circuit breaker &Master/Slave function switch
Power LED
Slave On LED

1. Introduction The product is used as an external power distribution unit in conjunction with UPS systems or large-scale voltage regulators. It allows to manually transfer the connected equipment to utility power via a bypass switch, permitting scheduled maintenance or UPS replacement without power interruption. Combined power distribution feature and the master-controlled design, it provides maintenance bypass function and power saving within a rack mechanism.
Rack Mount/Wall Mount the Unit The module can be mounted to a 19” enclosure or wall. Please follow below chart for rack/wall mount installation.
Wall

3. Installation and Operation Inspection Remove the unit from the shipping package and inspect it for damage that may occur during transportation. Notify the carrier and place of purchase if any damage is found. The shipping package contains: ! Maintenance bypass switch module x 1 ! Quick guide x 1 ! Mains power cord x 1 ! Screws and mounting ears
Connect to the Wall Outlet Plug the input power cord of the unit to the wall outlet. The Power LED will light up when the mains is normal. The Power LED will be off while power failure.

Chart 1: Rack mounting

Chart 2: Wall mounting

Connect UPS Connect a power cord from UPS input to UPS input socket on the unit. Use one power cord to connect UPS output to UPS output socket on the unit.
Online UPS

4. Operation Transfer to Maintenance Bypass Before transferring to maintenance bypass, make sure the Power LED is lighting. Transfer the rotary bypass switch from “Normal” to “Bypass”. At this time, all connected devices are powered by the utility power directly. You may turn off the UPS and disconnect two cables connecting to UPS. Then you may now service the UPS.

16A/16A or 16A/10A
Connect Equipment There are two types of output receptacles: Master, and Slave. To save power consumption, the unit is equipped with Master and Slave output receptacles. The Master output receptacle will sense if master device (computer) is on. If the master device is no longer drawing current, it will automatically shut down the power to the Slave output receptacles. Please refer to below charts for detailed equipment connection.
Plug computer into Master Output Receptacle
Computer

Transfer to UPS Protection After maintenance service is done, make sure the UPS operation is normal. Then, reconnect UPS to the unit by following Installation Section. Verify the Power LED is lighting. Then transfer the rotary bypass switch from “Bypass” to “Normal”. Now, all connected devices are protected by UPS.

Master/Slave Function Operation After connecting all devices to the unit, press “Master/Slave switch” to enable status ( ). The Slave On LED will light up when connecting load on master output is above 20W. Press “Master/Slave switch” to disable status ( ), the function is disabled and the Slave On LED will be on.

Status & Indicator Table Status
1. Utility is normal. 2. Utility fails but UPS is providing power. Utility fails Master/Slave function is enabled and the connecting load on master output is above 20W. Master/Slave function is enabled and the connecting load on master output is below 20W. Master/Slave function is disabled.

Indicator Power LED (Green) on Power LED (Green) off Slave On LED (Yellow) on
Slave On LED (Yellow) off Slave on LED (Yellow) on

Plug peripherals into Slave Output Receptacle
Monitor Printer
Switch NOTE: When the computer is turned off, the Master output receptacle shuts off power to the slave output receptacles. However, when the computer goes into “sleep mode” or the power consumption of connected device to Master output receptacle is below 20 W, the Master output receptacle may not properly recognize the reduced power level.

5. Important Safety Warning (SAVE THESE INSTRUCTIONS) To safely operate this unit, please read and follow all instructions carefully. Read this manual thoroughly before attempting to unpack, install, or operate. You may keep this quick guide for further reference. CAUTION: The product must be used indoor only. CAUTION: Do not place the unit near liquid or in an excessively damp environment. CAUTION: Do not place the product directly in the sun or near a hot source. CAUTION: Do not let liquid or foreign objects enter the product. CAUTION: Ground the product using a 2P + ground sockets. CAUTION: When installing the product, ensure that the sum of the leakage currents of the product and the devices it supplies not exceed 3.5mA.

Documents / Resources

FSP PDU and Maintenance Bypass Switch Module [pdf] User Guide
PDU and Maintenance Bypass Switch Module, Maintenance Bypass Switch Module, Bypass Switch Module, Switch Module, Module