ELPRO logoELPRO 115E-2 Ethernet Networking I O and Gateway - logoELPRO 115E-2 Ethernet Networking I O and Gateway115E-2
INSTALLATION GU IDE

115E-2 Ethernet Networking I O and Gateway

WARNING EXPLOSION HAZARD
Do not disconnect the device while the circuit is live unless the area is known to be non-hazardous.
NOTE
All connections must be SELV <50 Vac and <120Vdc.
Connecting to the module for configuration.

  • Download and install configuration utility software, available from the Elpro Technolgies website. www.elprotech.com
  • Connect to PC using supplied USB cable.
  • Connect to the device by selecting USB connection and using the IP address 192.168.111.1 or 1.1.1.1 for older firmware (pre V2.28)
  • The PC will automatically be assigned an IP address from the module via DHCP. A new network adaptor will be created using IP address 192.168.1.2 (or 1.1.1.2)
  • Username: user
  • Password: user

The following illistrations show the port connections on the 115E-2.ELPRO 115E-2 Ethernet Networking I O and Gateway - port connectionsPower Supply Wiring
The ground (GND) and “SUP –“ terminals are connected internally to the ground (Earth) terminal. Connect the screw terminal on the end plate to ground (Earth) for surge protection.ELPRO 115E-2 Ethernet Networking I O and Gateway - Power Supply WiringExpansion I/O Power and RS485 serial connection
An on-board RS-485 terminating resistor provides line termination  for long runs.
Only enable terminating resistor on the last device connected on the RS-485 cable.ELPRO 115E-2 Ethernet Networking I O and Gateway - serial connectionConfiguration Switches
Use the DIP switches in the side access panel to select analog input voltage or current, and to enable default configuration.ELPRO 115E-2 Ethernet Networking I O and Gateway - Switches

DIP Description ON OFF
1 AI3 Current / Voltage Current Voltage
2 AI3 Current / Voltage Current Voltage
3 AI4 Current / Voltage Current Voltage
4 AI4 Current / Voltage Current Voltage
5 Unused
6 Default configuration Enabled Normal

Input and Output connections

The digital input/output channels can be wired as inputs or outputs.

Digital Input
ELPRO 115E-2 Ethernet Networking I O and Gateway - Input and Output connectionsDigital OutputELPRO 115E-2 Ethernet Networking I O and Gateway - Input and Output connections 1Differential 4-20mA inputs (AI1, AI2)
ELPRO 115E-2 Ethernet Networking I O and Gateway - Input and Output connections 2Single Ended 4-20mA inputs (AI3, AI4)ELPRO 115E-2 Ethernet Networking I O and Gateway - Input and Output connections 3Analog Output (0-20mA)
ELPRO 115E-2 Ethernet Networking I O and Gateway - Input and Output connections 4Single Ended voltage inputELPRO 115E-2 Ethernet Networking I O and Gateway - Input and Output connections 5CONTACT
Australia
ELPRO Technologies
29 Lathe Street
Virginia QLD 4014
T +61 7 3352 8600
E sales@elprotech.com
W elprotech.com
USA
ELPRO Technologies Inc
2028 East Ben White Boulevard
#240-5656 Austin, TX 78741-6931
T +1 855 443 5776
E sales@elprotech.com
W elprotech.com

ELPRO logoHOW TO ORDER
Simply send us an email at sales@elprotech.com
contact your local distributor, or phone +61 7 3352 8600
An envirada group company

Documents / Resources

ELPRO 115E-2 Ethernet Networking I O and Gateway [pdf] Installation Guide
115E-2 Ethernet Networking I O and Gateway, 115E-2, Ethernet Networking I O and Gateway, Networking I O and Gateway, Gateway

References

Leave a comment

Your email address will not be published. Required fields are marked *