DITEK Data and Signaling Circuit Modular Surge Protector User Guide

Data and Signaling Circuit Modular Surge Protector

Specifications:

  • Product Type: Surge Protection Device
  • Application: Commercial, Industrial, Residential
  • Maximum Continuous Operating Voltage (MCOV): Defined by product
    variant
  • Nominal Discharge Current Rating (In): 3kA, 5kA, 10kA, or
    20kA
  • Voltage Protection Rating (VPR): Not specified

Product Usage Instructions:

1. Understanding Surge Protection Basics:

Surges and spikes are instantaneous events that can damage
sensitive equipment. Conventional fuses and breakers do not protect
against surges.

2. Causes of Surges and Spikes:

  • Lightning
  • Proximity Strikes
  • Brownouts/Blackouts
  • Utility Grid Switching
  • Inductive Loads

3. Effects of Surges and Spikes:

  • Degradation
  • Destruction
  • Downtime

4. Equipment to Protect:

Install surge protection on all critical electronic systems and
their electrical paths to safeguard against power surges and
spikes.

5. Benefits of Quality Surge Protection:

  • Reduced Downtime
  • Extended Equipment Life
  • Increased Customer Satisfaction

6. Product Markings – 5th Edition:

Understand the Maximum Continuous Operating Voltage (MCOV),
Nominal Discharge Current Rating (In), and Voltage Protection
Rating (VPR) to ensure optimal performance.

Frequently Asked Questions (FAQ):

Q: How do I know if the surge protection device needs
replacement?

A: Monitor the device for any signs of physical damage, check
for proper functioning with test buttons if available, and consult
the manufacturer’s guidelines for replacement intervals.

Q: Can surge protectors be used outdoors?

A: Some surge protectors are designed for outdoor use, ensure
that the product specifications mention outdoor suitability before
installation.

“`

SURGE PROTECTION PRODUCT GUIDE
Commercial | Industrial | Residential

CONTENTS
Surge Protection Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 UL 1449 ­ Surge Protective Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Residential Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Commercial & Industrial Protection ­ Modular . . . . . . . . . . . . . . . . . . 6 Commercial & Industrial Protection ­ Non-Modular . . . . . . . . . . . 8 DIN Rail Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Branch Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 HVAC Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Fire Alarm Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Total Surge Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Network Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 IP Video Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Customizable Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Commercial A/V Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Access Control Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Gate Access Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Intrusion Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Uninterruptible Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Installation Best Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Committed to Excellence
In this digital age, we’re more dependent on electronics and electricity than ever. DITEK Surge Protection is a proactive investment to safeguard your most valuable electronic and digital assets. It’s like insurance for your communications, fire protection, security systems, home appliances — anything you plug in to connect to power.
We all experience power surges every day. Those surges can damage your electronic and digital assets even when you can’t see them. DITEK Surge Protection guards your assets against big and small surges so your business or home can stay operational without fear of damage or downtime.

DITEK Surge Protection is the first line of defense for protecting power systems from the negative impacts of power surges. For over 35 years, we have been an industry leader in the technology, design and manufacturing of surge protection solutions for facilities, businesses, homes, and more.

SURGE PROTECTION BASICS
Surges and spikes are temporary and instantaneous events that increase normal electrical line voltage, and can cause serious damage to sensitive equipment. Conventional fuses and breakers do NOT guard against power surges and spikes.

What causes surges and spikes?

Lightning: A direct hit is usually catastrophic.
Proximity Strikes: Lightning strikes several miles away, causing large voltage spikes along transmission lines.
Brownouts/Blackouts: Under-voltage or sag, that is immediately followed by an unusually high voltage transient. If your lights flicker or dim, it’s usually an indication that a brownout occurred.
Utility Grid Switching: Utility companies switching transmission lines from one supply system to another.
Inductive Loads: The switching on and off of electric motors inside or outside a facility. For example, HVAC systems or heavy machinery.

What are the effects of surges and spikes?

Degradation: Gradual deterioration of internal circuitry from repeated power surges and spikes that slowly degrade electrical components, shortening their lifespan and making them less reliable.
Destruction: Resulting in expensive equipment repair or replacement costs.
Downtime: The most costly effect, can result in the loss of data, productivity and customers.

What equipment should be protected?

Power surges and spikes can be induced onto any type of unprotected electrical cabling, including utility power lines, network and communication lines, and low voltage power feeds. Therefore, surge protection should be installed on all critical electronic systems and the electrical paths between them.

What are the benefits of investing in quality surge protection?

REDUCED DOWNTIME

EXTENDED EQUIPMENT LIFE

INCREASED CUSTOMER SATISFACTION

UL 1449 ­ Surge Protective Devices

5TH EDITION PRODUCT MARKINGS
Maximum Continuous Operating Voltage (MCOV)
The maximum voltage a device can withstand continuously before clamping begins.
Nominal Discharge Current Rating (In)
UL 1449 test encompassing 15 surge impulses at a selected level of 3kA, 5kA, 10kA or 20kA. The unit must be fully operational after completion of the test.

Voltage Protection Rating (VPR)
UL 1449 clamping voltage test performed with a 6kV, 3kA, 8×20 s combination waveform.
Short Circuit Current Rating (SCCR)
The level at which an SPD is suitable for use on an AC power circuit that is capable of delivering not more than a declared root-mean-square symmetrical current at a delayed voltage during a short-circuit condition.

SPD LOCATION REQUIREMENTS

Electric Meter Service Entrance

Circuit Breaker
Panel

Receptacles < 30′ From
Service Entrance

Receptacles > 30′ From
Service Entrance

Type 1 SPD

Type 2 SPD

Type 3 SPD

Line side of service panel

Load side of service panel

Type 1 SPD
A permanently connected SPD intended for installation between the secondary of the service transformer and the line side of the service equipment overcurrent device, as well as the load side, including watt-hour meter socket enclosures and Molded Case SPDs intended to be installed without an external overcurrent protective device.

Type 2 SPD
A permanently connected SPD intended for installation on the load side of the service equipment overcurrent device, including SPDs located at the branch panel and Molded Case SPDs.

Type 3 SPD
Point of utilization SPDs, installed at a minimum conductor length of 10 meters (30 feet) from the electrical service panel to the point of utilization, for example cord connected, direct plug-in, receptacle type SPDs installed at the utilization equipment being protected. The distance (10 meters) is exclusive of the conductors provided with or used to attach SPDs.

3

Residential Protection
A | DTK-120/240BK1
CIRCUIT BREAKER-STYLE ­ LOAD CENTER UL 1449 | Type 2 SPD · Fits multiple load centers w/ 1″ spacing · 50,000A surge current rating · Audible alarm with silence feature · Diagnostic LED · 5 year, $25,000 connected equipment warranty
B | DTK-120/240HD2
MAIN PANEL, METER OR TRANSFER SWITCH UL 1449 | Type 1 SPD · 100,000A/phase surge current rating · NEMA 4X enclosure · Diagnostic LED · Flush mount kit p/n DTK-FMKHD2 · 5 year $25,000 connected equipment warranty
C | DTK-120/240HD
MAIN PANEL, METER OR TRANSFER SWITCH UL 1449 | Type 1 SPD · 50,000A/phase surge current rating · NEMA 4X enclosure · Diagnostic LED · Flush mount version p/n DTK-120/240HDFM · 5 year, $10,000 connected equipment warranty
D | DTK-120/240XD
MAIN PANEL, METER OR TRANSFER SWITCH UL 1449 | Type 1 SPD · 50,000A/phase surge current rating · NEMA 4X enclosure · Diagnostic LED · Flush mount kit p/n DTK-FMK · 5 year, $10,000 connected equipment warranty
4

National Electrical Code, Article 230.67 stipulates:
All electrical services to dwellings must have surge protective devices installed at or near the service entrance SPDs “shall be an integral part of the service equipment or shall be located immediately adjacent thereto”
A D
B C
E | DTK-120/240CM+
HVAC & POOL CONTROLS UL 1449 | Type 1 SPD · 50,000A total surge current rating · NEMA 4X enclosure · Diagnostic LED · 3/4″ NPT male fitting · 3 year, $7,500 connected equipment warranty
F | DTK-MRJPOES
ETHERNET & POE CIRCUITS UL 497B | 20,000A · Protects 1 Ethernet or PoE channel · RJ45 female in/out · Rated to pass up to 10Gbps · 20kA/pair surge current rating · 10 year limited warranty
G | DTK-7VS
PLUG-IN SURGE STRIP UL 1449 | Type 3 SPD · Power strip with load-sensing technology · 120VAC, 15A · 7 outlets with 4′ cord · Illuminated load-status indicator

F E
G
5

Commercial & Industrial Protection ­ Modular
D200M Series
SERVICE ENTRANCE UL 1449 | Type 1 SPD · 200,000A/phase, 100,000A/mode · NEMA 4 enclosure · Field-replaceable surge protection module · 8 AWG­2 AWG mechanical lug connections · Minimum circuit breaker: 40A
D200MT Series
SERVICE ENTRANCE UL 1449 | Type 1 SPD · 200,000A/phase, 100,000A/mode · NEMA 4 enclosure · Field-replaceable surge protection module · 8 AWG­1/0 AWG mechanical lug connections · UL98 integral disconnect switch included · Minimum circuit breaker: 40A
D300M Series
SERVICE ENTRANCE UL 1449 | Type 1 SPD · 300,000A/phase, 150,000A/mode · NEMA 4 enclosure · Field-replaceable surge protection module · 8 AWG­2 AWG mechanical lug connections · Minimum circuit breaker: 40A
D300MT Series
SERVICE ENTRANCE UL 1449 | Type 1 SPD · 300,000A/phase, 150,000A/mode · NEMA 4 enclosure · Field-replaceable surge protection module · 8 AWG­1/0 AWG mechanical lug connections · UL98 integral disconnect switch included · Minimum circuit breaker: 40A
6

STANDARD FEATURES
· Field-replaceable surge protection module · Audible alarm with disable feature · Form C dry contacts for remote monitoring · Diagnostic health status LEDs per phase

· Surge counter with reset button · EMI/RFI filtering · Phase loss indicator · Service assurance features

D200M SERIES

Model D200M-120/2401

Integral Disconnect

D200M/120/2401T

D200M-120/2083Y

D200M-120/2083YT

D200M-277/4803Y

D200M-277/4803YT

D200M-2403D

D200M-2403DT

D200M-4803D

D200M-4803DT

Voltage 120/240V Split 120/208V Wye 277/480V Wye
240V Delta 480V Delta

Wiring 3W + G 4W + G 4W + G 3W + G 3W + G

Surge Capacity
200kA/ phase

I(n) 20kA

SCCR

NEMA

200kA

4

D300M SERIES

Model
D300M-120/2401 D300M/120/2401T D300M-120/2083Y D300M-120/2083YT D300M-277/4803Y D300M-277/4803YT D300M-2403D D300M-2403DT D300M-4803D D300M-4803DT

Integral Disconnect

Voltage 120/240V Split 120/208V Wye 277/480V Wye
240V Delta 480V Delta

Wiring 3W + G 4W + G 4W + G 3W + G 3W + G

Surge Capacity
300kA/ phase

I(n) 20kA

SCCR

NEMA

200kA

4

7

Commercial & Industrial Protection ­ Non-Modular
D200 Series
DISTRIBUTION PANELS UL 1449 | Type 1 SPD · 200,000A/phase, 100,000A/mode · NEMA 4X enclosure · 10 AWG, 30″ lead wires · 3/4″ NPT non-metallic conduit · Minimum circuit breaker: 30A · Flush mount kit, p/n D200-FMK
D150X Series
DISTRIBUTION PANELS UL 1449 | Type 1 SPD · 150,000A/phase, 50,000A/mode · NEMA 4X enclosure · 10 AWG, 30″ lead wires · 3/4″ NPT non-metallic conduit · Minimum circuit breaker: 30A · Flush mount kit, p/n D200-FMK
D100 Series
BRANCH PANELS UL 1449 | Type 1 SPD · 100,000A/phase, 50,000A/mode · NEMA 4X enclosure · 10 AWG, 30″ lead wires · 1/2″ NPT non-metallic conduit · Minimum circuit breaker: 30A · Flush mount kit, p/n DTK-FMKHD2
D50 Series
BRANCH PANELS UL 1449 | Type 1 SPD · 50,000A/phase, 25,000A/mode · NEMA 4X enclosure · 12 AWG, 30″ lead wires · 3/4″ NPT male hub · Minimum circuit breaker: 20A · Flush mount option, add “FM” to p/n
8

D200 SERIES
Model
D200-120/2401 D200-120/2083Y D200-120/240HL D200-277/4803Y D200-2403D D200-4803D

Voltage

Wiring

120/240V Split 3W + G

120/208V Wye 4W + G

120/240V Delta HL 4W + G

277/480V Wye 4W + G

240V Delta

3W + G

480V Delta

3W + G

Surge Capacity
200kA/ phase

I(n)

SCCR NEMA

LED

Audible Dry Alarm Contacts

20kA 100kA 4X

D150X SERIES
Model
D150X-120/2401 D150X-120/2083Y D150X-120/240HL D150X-2403D D150X-277/4803Y D150X-4803D

Voltage

Wiring

120/240V Split 3W + G

120/208V Wye 4W + G

120/240V Delta HL 4W + G

240V Delta

3W + G

277/480V Wye 4W + G

480V Delta

3W + G

Surge Capacity
150kA/ phase

I(n)

SCCR NEMA

20kA 100kA 4X

LED

Audible Dry Alarm Contacts

D100 SERIES
Model
D100-120/2401 D100-120/2083Y D100-120/240HL D100-277/4803Y D100-2403D D100-4803D D100-6003D

Voltage

Wiring

120/240V Split 3W + G

120/208V Wye 4W + G

120/240V Delta HL 4W + G

277/480V Wye 4W + G

240V Delta

3W + G

480V Delta

3W + G

600V Delta

3W + G

Surge Capacity
100kA/ phase

I(n)

SCCR NEMA

20kA 100kA 4X
10kA

LED

Audible Dry Alarm Contacts

D50 SERIES
Model
D50-120/2401 D50-120/2083Y D50-120/240HL D50-277/4803Y D50-2403D D50-4803D D50-347/6003Y

Voltage

Wiring

120/240V Split 3W + G

120/208V Wye 4W + G

120/240V Delta HL 4W + G

277/480V Wye 4W + G

240V Delta

3W + G

480V Delta

3W + G

347/600V Wye 4W + G

Surge Capacity
50kA/ phase

I(n)

SCCR NEMA

20kA

100kA 4X 10kA

LED

Audible Dry Alarm Contacts

9

DIN Rail Protection
DTK-DR Series
AC POWER UL 1449 | Type 1 CA · 75,000A surge capacity · Field-replaceable protection module · 35mm DIN rail mounting configuration · Visual and remote end-of-life indicators · N-G protection module optional · 120­690VAC voltage configurations
DTK-DRB Series
LOW VOLTAGE & CONTROL CIRCUITS UL 497B | 20,000A · 20,000A surge capacity · Field-replaceable protection module · Protects 2 circuit pairs · 35mm DIN rail mounting configuration · 5­130VDC voltage configurations · Shorts to ground when compromised
DTK-DRF Series
LOW VOLTAGE & CONTROL CIRCUITS UL 497B | 20,000A · 20,000A surge capacity · Field-replaceable protection module · Protects 2 circuit pairs · 35mm DIN rail mounting configuration · 5­130VDC voltage configurations · Opens circuit when compromised
10

Branch Circuit Protection
DTK-DF120S12
CONVENIENCE STORES & MULTI-PUMP FUELING STATIONS UL 1449 | Type 2 SPD · Protects up to (12) 120VAC single phase critical loads · Audible alarm · Field-replaceable Deflector modules
DTK-120SLR
FIRE ALARM CONTROL PANELS, GATE MOTORS, ETC. UL 1449 | Type 2 SPD · UL 1283 noise filtering · 120VAC single phase, up to 20 Amps · Series-connected, removes load when
surge protection expires
DTK-HW Series
DEDICATED BRANCH CIRCUITS UL 1449 | Type 1 SPD · Compact, parallel-wired · Diagnostic LED · NEMA 4X enclosures
DTK-120HW 120VAC single phase DTK-240HW 240VAC single phase DTK-120/240HW 120/240VAC split phase
DTK-CMXPLUS Series
DEDICATED BRANCH CIRCUITS UL 1449 | Type 1 SPD · 25,000A/phase · NEMA 4X enclosure · Diagnostic LED
DTK-2403CMXPLUS 208/240VAC three phase DTK-4803CMXPLUS 480VAC three phase DTK-6003CMXPLUS 600VAC three phase
11

HVAC Protection
INTELLIGENT VOLTAGE MONITORING
KoolGuard Series: DTK-KG2
MINI-SPLITS, INVERTER DRIVEN COMPRESSOR SYSTEMS & ECM MOTORS UL 60947-1 & 60947-5-1 | Voltage Monitor · Protects against under- and over-voltage events · Safely disconnects power to the system until
input voltage returns to normal range · Diagnostic LEDs indicate voltage condition · Includes surge protection components

Voltage Condition Codes
Condition Normal / On

B

Line 1 Over or Under / Off

Line 2 Over or Under / Off

B

B

B

Recovering from Line 1 Over or Under / Delayed

B

B

Recovering from Line 2 Over or Under / Delayed

B

B

A
B = Blinking

Service Required / On

A
A = Alternating

Technical Specifications Voltage configuration . . . . . . . . . .120/240VAC Split . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120/208VAC Split Operating frequency . . . . . . . . . . . . . . . . . . . . . . . .50/60Hz Max. continuous current . . . . . . . . . . . . . . . . . . 40 Amps Undervoltage protection . . . . . . . . . . . . . 104VAC (L-G) Overvoltage protection . . . . . . . . . . . . . . . .130VAC (L-G) Short cycle delay . . . . . . . . . . . . . . . . . . . . 3 min (default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 sec (optional) Surge Current Rating . . . . . . . . . . . . . . . . . . . . . . .50,000A
Mechanical Specifications Dimensions . . . . . . . . . . . . 6.29″ L x 6.29″ W x 2.36″ H . . . . . . . . . . . . . . . . . . . . . . . . (160 mm x 160 mm x 60mm) Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 lb (1.36 kg) Housing . . . . . . . . . . . . . . . . . . . . . . . UL type 4X enclosure Connection method . . . . . . . . . . . . . . . . . . . .Series-wired Conduit size . . . . . . . . . . . . . . . . . . . . . . . . . . . . .½” or ¾” NPT Terminal lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-6 AWG

Disconnect Switch 12

DTK-KG2

Outdoor Condenser Unit

SURGE PROTECTIVE DEVICES
A | DTK-120/240CM+
CONDENSER UNIT OR AIR HANDLER UL 1449 | Type 1 SPD · 10kA Nominal Discharge Current Rating · NEMA 4X enclosure · Diagnostic LED · 3 year $7,500 warranty

B | DTK-120/240CMX
CONDENSER UNIT OR AIR HANDLER UL 1449 | Type 1 SPD · 20kA Nominal Discharge Current Rating · NEMA 4X enclosure · Diagnostic LED · 3 year $7,500 warranty

C | DTK-CMXPLUS Series
3 PHASE CONDENSER UNIT UL 1449 | Type 1 SPD · 25,000A/phase · NEMA 4X enclosure · Diagnostic LED
DTK-2403CMXPLUS 208/240VAC three phase DTK-4803CMXPLUS 480VAC three phase DTK-6003CMXPLUS 600VAC three phase

D | DTK-4LVLPLV
THERMOSTAT CONTROL WIRING UL 497B | 20,000A · 4-pair, 8-wire 24V · Install in series with thermostat control wires
at air handler · 30-12 AWG terminal block

Disconnect Switch

Outdoor Condenser Unit

D
DTK-4LVLPLV

A

B

C DTK-CMXPLUS SERIES

or DTK-120/240CMX

or DTK-120/240CM+

Indoor Air Handler
13

Fire Alarm Protection

A | DTK-DF120S1
120VAC POWER UL 1449 | Type 2 SPD · 120V/20A series-wired SPD · Rapid-replacement module · Audible alarm and LED status indicators · Dry contacts for remote monitoring · UL 1283 EMI/RFI filtering

B | DTK-120HWLOK
120VAC POWER UL 1449 | Type 1 SPD · 120V parallel-wired SPD · 50,000A max surge current rating · Includes NFPA 72 breaker lockout · Available w/out lockout kit: DTK-120HW

C | DTK-2MHLP Series
SLC/IDC/NAC/PIV UL 497B | 20,000A · 2-pair, multi-stage hybrid surge protectors · 20kA surge current rating, 5-130V configurations · Screw terminal connections · B series shorts to ground when compromised · F series opens circuit when compromised

D | DTK-MRJ31XWP
DIALER CIRCUITS · Single pair dialer protector
with RJ31X connection · Automatic reset handles
multiple surges
E | DTK-VSPN/ DTK-VSPSMA
EXTERNAL ANTENNA DTK-VSPN features N-type connector F/F DTK-VSPSMA features SMA-type connector M/F

E

DTK-VSPN or DTK-VSPSMA External Antenna Kit

Electrical Service

B

A

DTK-120HWLOK or DTK-DF120S1

14

Phone Lines

D

C

DTK-MRJ31XWP or DTK-2MHLP130BWB

C
DTK-2MHLPF-WB
C
DTK-2MHLPB-WB
C
DTK-2MHLPB-WB

SLC IDC/PIV
NAC

Total Surge Solutions
DTK-120X12
120VAC POWER & (12) LOW VOLTAGE CIRCUITS UL 1449, UL 1283, UL 497B | Type 2 SPD · Audible alarm with silence feature · Dry contacts for remote monitoring (Form C) · 6-position mounting base for 2MHLP modules
(sold separately) · Protects up to 12 pairs of SLC, IDC/PIV, NAC,
network or dialer circuits
DTK-TSS1
120VAC POWER & (10) LOW VOLTAGE CIRCUITS UL 1449, UL 1283, UL 497B | Type 2 CA · 5-position base for 2MHLP modules (sold separately) · Dry contacts for remote monitoring · Protects up to 10 pairs of SLC, IDC/PIV, NAC, network
or dialer circuits
DTK-TSS2/DTK-TSS2NM
120VAC POWER & (4) LOW VOLTAGE CIRCUITS UL 1449, UL 1283, UL 497B | Type 2 CA · 120V protection · NEMA 4X enclosure
DTK-TSS2 Protects up to 4 pairs of loop circuits DTK-TSS2NM Space for monitor module
DTK-TSS3
(4) LOW VOLTAGE CIRCUITS UL 497B | 20,000A · 2-position base for 2MHLP modules · Protects up to 4 pairs of
building-to-building cable runs · NEMA 4X enclosure
DTK-TSS4D
120VAC POWER UL 1449, UL 1283 | Type 2 CA · 120V protection · Dry contacts for remote monitoring · NEMA 4X enclosure
15

Network Protection
A | RMNETS & RMEXTS Series
UL 497B | 20,000A · Multi-stage, hybrid protection design · Robust 20kA per pair surge current rating · Rapid-replacement modular design · Supports up to 10Gb Ethernet speed · Compatible with both STP and UTP cabling · Designed for rack mounted systems
RMNETS: ETHERNET & POE CIRCUITS DTK-RM24NETS 24-channel, 1U rack mount DTK-RM16NETS 16-channel, 1U rack mount DTK-RM12NETS 12-channel, 1U rack mount
RMEXTS: POE EXTENDER CIRCUITS DTK-RM24EXTS 24-channel, 1U rack mount DTK-RM16EXTS 16-channel, 1U rack mount DTK-RM12EXTS 12-channel, 1U rack mount
RAPID-REPLACEMENT MODULES Mix and match replacement modules to protect Ethernet, PoE and PoE extender circuits within the same housing
DTK-NETMS For Ethernet and PoE circuits DTK-EXTMS For PoE Extender circuits

Card Swipe

C
DTK-MRJPOES

C

Dome Camera

DTK-MRJPOES

Enclosed Camera

C
DTK-MRJPOES

16

A Rack Mount Surge Protector
Network Switch & Network Server
INTERIOR

C
DTK-MRJPOES

Keypad

C
DTK-MRJPOES

PA Speaker

C

DTK-MRJPOES

Wireless Access Point

B | WMNETS & WMEXTS Series
UL 497B | 20,000A · Multi-stage, hybrid protection design · Robust 20kA per pair surge current rating · Rapid-replacement modular design · Supports up to 10Gb Ethernet speed · Compatible with both STP and UTP cabling · Designed for wall mounted systems
WMNETS: ETHERNET & POE CIRCUITS DTK-WM8NETS 8-channel, wall mount DTK-WM4NETS 4-channel, wall mount
WMEXTS: POE EXTENDER CIRCUITS DTK-WM8EXTS 8-channel, wall mount DTK-WM4EXTS 4-channel, wall mount
C | DTK-MRJPOES & DTK-MRJEXTS
ETHERNET, POE & EXTENDER CIRCUITS UL 497B | 20,000A · RJ45 female in/out · Rated to pass up to 10Gbps · 20kA/pair surge current rating · Compatible with both STP and UTP cabling
DTK-MRJPOES Ethernet and PoE circuits DTK-MRJEXTS PoE extender circuits
D | DTK-110C6A Series
CAT6A ETHERNET & POE CIRCUITS UL 497, UL 497B · Available in 110 punch down in/out
or 110 in/shielded RJ45 female out · Compatible with CAT5E, CAT6 and CAT6A circuits · Protects all four pairs · Automatically resets
DTK-110C6A Ethernet 110 block in/out DTK-110RJC6A Ethernet 110 block in/RJ45 out DTK-110C6APOE PoE 110 block in/out DTK-110RJC6APOE PoE 110 block in/RJ45 out
17

IP Video Protection

A | DTK-RMNETS Series

ETHERNET & POE SWITCHES

UL 497B | 20,000A

· Multi-stage, hybrid protection design · Robust 20kA per pair surge current rating · Available in 12-, 16- or 24-channel

DTK-RM24NETS DTK-RM12NETS

DTK-RM16NETS

B | DTK-MRJPOE Series
POE CAMERAS & DEVICES UL 497B | 20,000A · Multi-stage, hybrid protection design · Ethernet data speeds up to 10GbE
DTK-MRJPOE Unshielded RJ45 in/out DTK-MRJPOES Shielded RJ45 in/out

C | DTK-PVP Series
POE DEVICES W/ AUX POWER UL 497B | 20,000A · Ethernet data speeds up to 10GbE · Shielded RJ45 in/out connections
DTK-PVPIPS 2 pairs of 12/24V power DTK-PVP56V 2 pairs of 56V power

D | DTK-MRJPOEX
OUTDOOR POE CAMERAS & DEVICES UL 497B | 20,000A · NEMA 4X enclosure, liquid-tight cordgrips · Data speeds up to 10GbE without
signal degradation · Compatible with both STP and UTP cabling

A
DTK-RM24NETS
DTK-RM16NETS
DTK-RM12NETS

B
DTK-MRJPOES or DTK-MRJPOE
C

DTK-RMAC12 DTK-UPS+ SERIES

DTK-PVPIPS or DTK-PVP56V
D

INTERIOR

EXTERIOR

DTK-MRJPOEX

18

IP/Poe Cameras
IP Cameras w/ Aux Power
Outdoor IP/Poe Cameras

Customizable Protection

Versa-Module 2 Series
SIGNALING, DATA AND LOW VOLTAGE POWER CIRCUITS UL 497B | 20,000A · Rapid-replacement modular surge protection
system with single point ground · Multi-stage, hybrid protection design · Mix and match modules to protect 5V to 130V,
with RJ45 and screw terminal configurations · 4-, 8- or 24-channel enclosure options

RJ45 PROTECTION MODULES DTK-VM2M5 5V, RJ45 in/out DTK-VM2M12 12V, RJ45 in/out DTK-VM2M24 24V, RJ45 in/out DTK-VM2M36 36V, RJ45 in/out DTK-VM2M48 48V, RJ45 in/out DTK-VM2M75 75V, RJ45 in/out DTK-VM2M130 130V, RJ45 in/out
SCREW TERMINAL PROTECTION MODULES DTK-VM2TM5 5V, 2 pair in/out, 14AWG DTK-VM2TM12 12V, 2 pair in/out, 14AWG DTK-VM2TM24 24V, 2 pair in/out, 14AWG DTK-VM2TM36 36V, 2 pair in/out, 14AWG DTK-VM2TM48 48V, 2 pair in/out, 14AWG DTK-VM2TM75 75V, 2 pair in/out, 14AWG DTK-VM2TM130 130V, 2 pair in/out, 14AWG

RACK & WALL MOUNT ENCLOSURES Also compatible with NETS and EXTS series modules
DTK-VM2R2424-channel, 1U rack mount DTK-VM2W8 8-channel, wall mount DTK-VM2W4 4-channel, wall mount

19

Commercial A/V Protection
DTK-VM2 Series
CUSTOMIZABLE PROTECTION FOR SIGNALING, DATA & LOW VOLTAGE POWER CIRCUITS UL 497B | 20,000A · Mix and match protection modules allow
complete customization · Ideal for lighting control systems and 70V
audio systems · RJ45 and screw terminal configurations
available from 5V­130V
DTK-LC2
120VAC PLUG-IN UL 1449, UL 1283 | Type 3 SPD · EMI/RFI noise filtering ensures clean power
to connected equipment · Incorporates 2 protected 120VAC NEMA
5-15R outlets · LED health status indicator and audible alarm
sounds if protection is compromised · Single channel Ethernet and PoE protection module
DTK-HDMI Series
HDMI CABLE CONNECTIONS EN 55035:2017 · HDMI 2.0a and HDCP 2.2 compatible · Supports up to 4K UHD · Includes mounting bracket
DTK-HDMI1 Single channel DTK-HDMI2 Dual channel
DTK-2MHLP75BWB
SPEAKERS & AUDIO EQUIPMENT UL 1449 | 20,000A · 2-pair, 70V surge protector with hardwired base · Multi-stage, hybrid protection design · Field-replaceable protection module · 20kA surge current rating
20

Access Control Protection

A | DTK-2MHLP Series
OSDP READERS UL 497B | 20,000A · Multi-stage, hybrid protection design · Compatible with Open Supervised Device
Protocol (OSDP) · Field-replaceable module
DTK-2MHLP12BWB 2- or 4-wire OSDP readers (12V power) DTK-2MHLP24BWB 2- or 4-wire OSDP readers (24V power)

B | DTK-4LVLP Series
WIEGAND & OSDP READERS UL 497B | 5,000A · Multi-stage, hybrid protection design · Compatible with Open Supervised Device
Protocol (OSDP) and Wiegand · Small form factor
DTK-4LVLPCR Protects 12V or 24V power, 5V data and LED connections DTK-4LVLPX Protects up to (4) pairs of 0-12V power and data connections

C | DTK-MRJPOES
ETHERNET & POE CONNECTIONS UL 497B | 20,000A · Multi-stage, hybrid protection design · Ethernet data speeds up to 10GbE · Shielded RJ45 connections
A

D | DTK-ESS
DOOR FRAMES & CONTROL PANELS Protects low voltage mag-lock and control panel (2/pkg ­ both ends of circuit)
E | DTK-8FF
AC POWER & TELCO/FAX LINES Protects 8 AC outlets and up to 6 transformers; EMI/RFI noise filtering

DTK-2MHLP Series or DTK-4LVLP Series

D

Access Control

B

Card Reader / Key Pad

DTK-ESS

DTK-ESS

Mag Lock or Door Strike

PoE Injector & PoE Power

C
DTK-MRJPOES

E DTK-8FF

Electrical Outlet

120 VAC Power

21

Gate Access Protection

A | DTK-4LVLP Series
TELEPHONE ENTRY & KEYPADS UL 497B | 5,000A
DTK-4LVLPCR Protects 12V or 24V power, 5V data and LED connections DTK-4LVLPX Protects up to 4 pairs of 0-12V power and data connections DTK-4LVTEP Protects entry system power, telco and door release circuits

B | DTK-2MHLP5BWB
EXIT & SAFETY LOOPS UL 497B | 20,000A · 2-pair, 5V exit and safety loop circuit surge
protector with hardwired base · Multi-stage, hybrid protection design · Field-replaceable protection modules · 20kA surge current rating

C | DTK-HW Series
GATE MOTOR AC POWER UL 1449 | Type 1 SPD · Parallel-wired · NEMA 4X enclosure · Diagnostic LED
DTK-120HW 120VAC single phase (2W + G) DTK-120/240HW 120/240VAC split phase (3W + G)

D | DTK-120SLR
GATE MOTOR AC POWER UL 1449 | Type 2 SPD · Protects 120VAC single phase circuits 20 Amps · Series-connected design for fast response
time and maximum protection · Load removal feature disconnects power
to equipment if compromised · UL 1283 EMI/RFI noise filtering

Telephone System

Telephone Entry Panel
AC Power
22

A
DTK-4LVTEP
C

B
DTK-2MHLP5BWB
D

DTK-120HW, DTK-120/240HW or DTK-120SLR

Power Disconnect

A

A

DTK-4LVLPCR or DTK-4LVLPX

Keypad

Exit Loop

Safety Loop

B
DTK-2MHLP5BWB

Intrusion Protection
A | DTK-MRJ31XWP
TELCO CIRCUIT UL 497B | 5,000A · RJ45 connection with external grounding screw · Patch cord included

B | DTK-MRJPOES
ETHERNET & POE CONNECTIONS UL 497B | 20,000A · Multi-stage, hybrid protection design · Ethernet data speeds up to 10GbE · Shielded RJ45 connections

C | DTK-2MHLP12BWB
REMOTE ZONE SIGNAL LOOP UL 497B | 20,000A · Protects 2 pairs · Multi-stage, hybrid protection design · Field-replaceable protection modules · 20kA surge current rating

D | DTK-1F
120VAC PLUG-IN UL 1449 | Type 3 SPD · Center screw secures to outlet and can also
secure a transformer to prevent accidental disconnections · Diagnostic LED

Telco

A
DTK-MRJ31XWP

Ethernet or PoE

B
DTK-MRJPOES

C
DTK-2MHLP12BWB

Remote Zone Notification and
Signal Loops

D
DTK-1F

120VAC Power
23

Uninterruptible Power Supplies

DTK-UPS+ Series
ONLINE UNINTERRUPTIBLE POWER SUPPLY cTUVus | UL 1778 · Online double conversion UPS technology · Invisible transitioning between AC and battery · Intuitive LCD display · USB and Ethernet interfaces available on all models · Compliant to U.S. DOE Energy Conservation
Standard efficiency requirements
DTK-UPS1000R+ 1kVA, 8 x 15A outlets DTK-UPS1500R+ 1.5kVA, 8 x 15A outlets DTK-UPS2000R+ 2kVA, 8 x 20A outlets DTK-UPS3000R+ 3kVA, 1 x 30A outlet,
6 x 20A outlets

DTK-UPS Series
LINE INTERACTIVE UNINTERRUPTIBLE POWER SUPPLY cTUVus | UL 1778 · Built-in boost and buck AVR for voltage
stabilization · Built-in protection for an Ethernet circuit · Embedded microprocessor control · Touch screen LCD · Auto restart while AC is recovering · Compliant to U.S. DOE Energy Conservation
Standard efficiency requirements
DTK-UPS600 600VA, 6 outlets, RJ45 protection DTK-UPS1000 1000VA, 8 outlets, RJ45 protection

UPS ACCESSORIES
DTK-UETH1 SNMP web card allows you to monitor and manage UPS devices in a network

DTK-URK1 Rack mounting rails (included with 1.5kVA, 2kVA and 3kVA models)

24

INSTALLATION BEST PRACTICES

1

2

3

Conductor Length 3 ft
The conductor length between the SPD and the equipment being protected should be a minimum of three feet in length to allow enough time for the SPD to react. The conductors can be greater than three feet as long as they are isolated and are not subjected or directly exposed to internally- or externally-generated transient voltage spikes and/or surges.

Utilize separate conduit feeds
Always make sure that the field wiring (unprotected wires) and the protected wiring occupy separate conduit feeds. When unprotected and protected wires occupy the same conduit, surge energy can be induced on to the protected wiring and completely bypass the surge protective device.

Use grounding bus bars
The use of a grounding bus bar is strongly recommended as a means of terminating SPD ground wires to existing electrical grounding leads. This will ensure a solid mechanical connection of all grounding wires.
The use of twist-on wire connectors (“wire nuts”) is not recommended for termination of SPD ground wires to existing electrical grounding leads. Twist-on wire connectors can increase ground resistance, may become loose and/or corroded over time, and can also unnecessarily extend the length of the grounding conductor. This would degrade the performance of the SPD due to the lack of a short, low impedance ground path.
Use dedicated enclosures
Whenever possible, Surge Protective Devices should be installed in a dedicated enclosure outside of the equipment being protected. This will prevent physical damage to the electronic circuit board, power supply and/or wiring inside of the equipment panel due to a potential catastrophic failure of the SPD.
Use a dedicated ground wire
When installing multiple SPDs and terminating to a common electrical ground, a dedicated ground wire running from each individual SPD to a common grounding bus bar is strongly recommended. “Daisy-chaining” multiple SPD ground wires together via the SPD grounding terminals, or by using twist-on wire connectors, is not recommended as this increases the resistance and extends the length of the ground path.

CONTACT US
SALES 800-753-2345 TECH SUPPORT 888-472-6100

Try our online product selector tool to help find the right surge protection devices.
www.DITEKsurgeprotection.com

1720 Starkey Road Largo, FL 33771 SALES 800-753-2345 TECH SUPPORT 888-472-6100
SMS-100017-001 (920-017) REV26 05/25

Documents / Resources

DITEK Data and Signaling Circuit Modular Surge Protector [pdf] User Guide
Data and Signaling Circuit Modular Surge Protector, Signaling Circuit Modular Surge Protector, Circuit Modular Surge Protector, Modular Surge Protector, Surge Protector

References

Leave a comment

Your email address will not be published. Required fields are marked *