Danfoss logoMCD 202 Series
VLT®
COMPACT STARTER MCD 202

Danfoss VLT MCD 202 Series Compact StarterOPERATING INSTRUCTIONS

VLT MCD 202 Series Compact Starter

MCD 202 Series
MountingDanfoss VLT MCD 202 Series Compact Starter - Mounting

mm (inch)

Dimensions

Danfoss VLT MCD 202 Series Compact Starter - Dimensionsmm (inch)

MCD 202 A B C D E F
MCD 202-007 98 (3.86) 203 (7.99) 165 (6.50) 55 (2.17) 82 (3.23) 188 (7.4)
MCD 202-015
MCD 202-018
MCD 202-022
MCD 202-030
MCD 202-037 145 (5.71) 215 (8.46) 193 (7.60) 124 (4.88) 196 (7.72)
MCD 202-045
MCD 202-055
MCD 202-075 202 (7.95) 240 (9.45) 214 (8.43) 160 (6.30) 204 (8.03)
MCD 202-090
MCD 202-110

Cable Termination

Danfoss VLT MCD 202 Series Compact Starter - Cable Termination 4 Danfoss VLT MCD 202 Series Compact Starter - Cable Termination 5
MCD 202−007 ~
MCD 202−030
MCD 202−037 ~ MCD 202−0ff MCD 202−07f ~ MCD 202−110 MCD 202−007 ~
MCD 202−110
Danfoss VLT MCD 202 Series Compact Starter - Cable Termination 10 − 3f
(8 − 2)
Danfoss VLT MCD 202 Series Compact Starter - Cable Termination 6 2f − f0 (t − 1/0) Danfoss VLT MCD 202 Series Compact Starter - Cable Termination 7 N.A. Danfoss VLT MCD 202 Series Compact Starter - Cable Termination 8 0.1t − 1.f (26 − 16) Danfoss VLT MCD 202 Series Compact Starter - Cable Termination 9

Danfoss VLT MCD 202 Series Compact Starter - Cable Termination 1

10 − 3f
(8 − 2)
2f − f0 (t − 1/0) N.A. 0.1t − 1.f (26 − 16)

Danfoss VLT MCD 202 Series Compact Starter - Cable Termination 2

Torx (T20) 3 Nn
2.2 f1−lb
Torx (T20) t Nn
2.9 f1−lb
N.A. N.A.
Danfoss VLT MCD 202 Series Compact Starter - Cable Termination 3 7 nn
3 Nn
2.2 f1−lb
7 nn t Nn
2.9 f1−lb
N.A. 3.f nn
0.f Nn nax
t.t lb−in nax

75 ºC Wire – Use copper conductors only

Specifications

Danfoss VLT MCD 202 Series Compact Starter - Symbol

Model kW @ 400 VAC A AC53b
007 7.5 18 A AC53b 4-6:354
015 15 34 A AC53b 4-6:354
018 18 42 A AC53b 4-6:354
022 22 48 A AC53b 4-6:354
030 30 60 A AC53b 4-6:354
037 37 75 A AC53b 4-6:594
045 45 85 A AC53b 4-6:594
055 55 100 A AC53b 4-6:594
075 75 140 A AC53b 4-6:594
090 90 170 A AC53b 4-6:594
110 110 200 A AC53b 4-6:594
007 7.5 17 A AC53b 4-20:340
015 15 30 A AC53b 4-20:340
018 18 36 A AC53b 4-20:340
022 22 40 A AC53b 4-20:340
030 30 49 A AC53b 4-20:340
037 37 65 A AC53b 4-20:580
045 45 73 A AC53b 4-20:580
055 55 96 A AC53b 4-20:580
075 75 120 A AC53b 4-20:580
090 90 142 A AC53b 4-20:580
110 110 165 A AC53b 4-20:580
T4 3Ø, 200-440 VAC
45-66 Hz
T6 3Ø, 200-575 VAC
45-66 Hz
CV1 24 VAC
24 VDC
CV3 110-240 VAC &
380-440 VAC

Wiring

Danfoss VLT MCD 202 Series Compact Starter - Wiring

¹6A @ 30 VDC resistive / 2A 400 VAC, AC11
² 6A @ 30 VDC resistive / 2A 400 VAC, AC11Danfoss VLT MCD 202 Series Compact Starter - Wiring 1³ Auxiliary Relay Function = Trip

2 Wire 3 Wire
Danfoss VLT MCD 202 Series Compact Starter - Wiring 2 Danfoss VLT MCD 202 Series Compact Starter - Wiring 3

* Also resets trip conditions
Warning-icon.png Always apply control voltage before (or with) mains voltage.
Warning-icon.png With 24 VAC/VDC use contacts rated for low voltage and low current (gold flash or similar).
Electric Warning Icon Disconnect from the power source before installing or servicing
Warning-icon.png This product has been designed for Class A environments. Use of this product in domestic environments may causeradio interference.

Motor Thermistor

Danfoss VLT MCD 202 Series Compact Starter -

Adjustments

Par.  Example
Motor FLC Danfoss VLT MCD 202 Series Compact Starter - Adjustments Danfoss VLT MCD 202 Series Compact Starter - Adjustments 1
Current Limit Danfoss VLT MCD 202 Series Compact Starter - Adjustments 2 Danfoss VLT MCD 202 Series Compact Starter - Adjustments 3
Current Ramp Danfoss VLT MCD 202 Series Compact Starter - Adjustments 4 Danfoss VLT MCD 202 Series Compact Starter - Adjustments 5
Soft Stop Danfoss VLT MCD 202 Series Compact Starter - Adjustments 6 Danfoss VLT MCD 202 Series Compact Starter - Adjustments 7
Motor Trip Class Danfoss VLT MCD 202 Series Compact Starter - Adjustments 8 Danfoss VLT MCD 202 Series Compact Starter - Adjustments 9
Excess Start Time Danfoss VLT MCD 202 Series Compact Starter - Adjustments 10 Danfoss VLT MCD 202 Series Compact Starter - Adjustments 11
Phase Rotation Protection Danfoss VLT MCD 202 Series Compact Starter - Adjustments 12 Danfoss VLT MCD 202 Series Compact Starter - Adjustments 13 Danfoss VLT MCD 202 Series Compact Starter - Adjustments 14
Auxiliary Relay Function Danfoss VLT MCD 202 Series Compact Starter - Adjustments 15 Danfoss VLT MCD 202 Series Compact Starter - Adjustments 16

Indication

Danfoss VLT MCD 202 Series Compact Starter - Indication Danfoss VLT MCD 202 Series Compact Starter - Symbol 10Off, Danfoss VLT MCD 202 Series Compact Starter - Symbol 11On, Danfoss VLT MCD 202 Series Compact Starter - Symbol 12Flash
No control power Ready Starter tripped
Motor not running Motor running at full speed Motor starting or stopping

Trouble Shooting

Ready Description
Danfoss VLT MCD 202 Series Compact Starter - Symbol 12 x 1 Power Circuit: Check mains supply L1, L2 & L3, motor circuit T1, T2 & T3 and soft starter SCRs.
Danfoss VLT MCD 202 Series Compact Starter - Symbol 12 x 2 Excess Start Time: Check load, increase Current Limit or adjust Excess Start Time setting.
Danfoss VLT MCD 202 Series Compact Starter - Symbol 12 x 3 Motor Overload: Allow motor to cool, reset soft starter and restart. Soft starter cannot be reset until motor has cooled.
Danfoss VLT MCD 202 Series Compact Starter - Symbol 12 x 4 Motor Thermistor: Check motor ventilation and thermistor connection 05 & 06. Allow motor to cool.
Danfoss VLT MCD 202 Series Compact Starter - Symbol 12 x 5 Phase Imbalance: Check line current L1, L2 & L3.
Danfoss VLT MCD 202 Series Compact Starter - Symbol 12 x 6 Supply Frequency: Check supply frequency is in range.
Danfoss VLT MCD 202 Series Compact Starter - Symbol 12 x 7 Phase Rotation: Check for correct phase rotation.
Danfoss VLT MCD 202 Series Compact Starter - Symbol 12 x 8 Network Comms Failure (between accessory module and network): Check network connections and settings.
Danfoss VLT MCD 202 Series Compact Starter - Symbol 12 x 9 Starter Comms Failure (between starter and accessory module): Remove and refit accessory module.

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.
This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Danfoss logoENGINEERING
TOMORROW
M0027001 — VLT is a registered Danfoss trademark
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vit-drives.danfoss.com
Danfoss A/S © 2020.02
Danfoss VLT MCD 202 Series Compact Starter - Symbol 13
AQ35792881056301-000101 / 130R0985

Documents / Resources

Danfoss VLT MCD 202 Series Compact Starter [pdf] Instruction Manual
007, 015, 018, 022, 030, 037, 045, 055, 075, 090, 110, VLT MCD 202 Series Compact Starter, VLT MCD 202 Series, Compact Starter, Starter

References

Leave a comment