CERBERUS LogoXLD-1
“X” Series Loop Driver

ENGINEER AND ARCHITECT SPECIFICATIONS

CERBERUS PYROTRONICS XLD 1 X Series Loop Driver

  • X” Devices To MXL Interface
  • Allows XL-3 to MXL System Conversion
  • (4) Style 4 (Class B) or Style 6 (Class A) Loops
  • 30 “X” Series Devices Per Loop
  • Full MOM Card Slot
  • Supports All “X” Devices (TRX, PEX, DI-X3, PAX, etc.)
  • Allows MXL Operation with “X” Devices
  • CERBERUS PYROTRONICS XLD 1 X Series Loop Driver - IconListed, ULC Listed, CSFM, NYMEA Approved

Description

The XLD-1 is an optional MXL network module that connects XL-3 analog addressable devices to the MXL system. By using the XLD-1, existing XL-3 systems can be replaced by MXL systems, yet continue to use all “X” Series devices that are installed on the XL-3.
Each XLD-1 provides (4) analog loops for connection to “X”, “I” or “IL” Series devices. Each of the XLD-1 circuits supports up to 30 alarm causing, trouble causing and supervisory type devices, as well as intelligent output devices (such as TRX relays, relay and audible bases.) Each XLD-1 analog loop is capable of being wired for either Style 4 (Class B) or Style 6 (Class A.)
The MXL can support up to 8 XLD-1 modules (960 “X” devices.) The XLD-1 provides the same device and loop capacity as the XL-3 module INX.
An XL-3 system with (8) INX modules (fully loaded XL3 – 960 devices) being replaced by an MXL would require (8) XLD-1s to utilize all existing “X” field device.

Engineer and Architect Specification

The XLD-1 shall be an analog loop driver with the ability to supervise and communicate with all Cerberus Pyrotronics “X”, “I” or “IL” Series devices (excluding the CZM-1 and ICP). XLD-1 shall provide (4) MXL network analog loops each capable of supporting up to 30 “X”, “I” or “IL” Series devices. The XLD-1 shall occupy one full card slot in the MOM-2 or MOM-4 card cages. Each XLD-1 network analog loop shall be capable of being wired for either style 4 (Class B) or style 6 (Class A.) The XLD-1 module shall contain an on board microprocessor which provides it with the ability to function and to initiate alarm conditions even if the main MXL processor fails.

Electrical Ratings

MODULE RATINGS:

Supervisory: 24VDC, 200mA max.
Alarm: 24VDC, 200mA max.
INITIATING CIRCUITS ARE RATED:
Supervisory 24VDC peak, 40mA max.
Alarm: 24VDC peak, 40mA max.
(30 devices in alarm)
Total Circuit Resistance: 100 Ohms max.
Total Circuit Capacitance: .4 uF line to line
.8 uF line to ground

Ordering Information

Model Description Part Number
XLD-1 “X” Device Loop Driver 500-893383
Installation Instructions 315-093385
XEA-1 Small XL-3 Enclosure Adapter Plate 500-893604
XED-1 Small XL-3 Enclosure Door (Black) 500-893605
XEA-2 Large XL-3 Enclosure Adapter Plate 500-893606
XED-2 Large XL-3 Enclosure Door (Black) 500-893607

XLD-1 Module Diagram

CERBERUS PYROTRONICS XLD 1 X Series Loop Driver - Diagram

XLD-1 Wiring Diagram
CERBERUS PYROTRONICS XLD 1 X Series Loop Driver - Diagram 1Compatibility Table for XLD-1

Compatible
Devices
Installation
Instructions
Compatible 
Devices

Installation
Instructions

DI-AX3 P/N 315-085388F I LP-1 P/N 315-092994-2
DI-AX3H P/N 315-086588B ILPT-1 P/N 315-092994-2
DI-6X3 P/N 315-086590-7 I LT-1 P/N 315-093336-1
P/N 315-086592-5 MS1-10/20 P/N 315-090903-3
DI-BX3H P/N 315-086590-7 M SI-10B/20B P/N 315-093329-1
P/N 315-086592-5 MSX-1 P/N 315-183043C
DI-X3 P/N 315-083534D MSX-2 P/N 315-088528B
DI-X3H P/N 315-086587B PAX-1 P/N 315-084615C
DP-X3 P/N 315-083406A PAX-3 P/N 315-087558-3
DT-X3-135 P/N 315-0841250 P EX-3000 P/N 315-0865520
ID-601/601H P/N 315-090287-2 P EX-3000T P/N 315-0865520
ID-601A/601AH P/N 315-090287-2 SAX-1 P/N 315-0846140
ID-601 B/60I BH P/N 315-086590-7 SAX-3 P/N 315-087791A
P/N 315-086529-5 TRI-2/2 R/2D P/N 315-090556-5
ID-60P/60PT P/N 315-090289-3 TR1-60/60R/60D P/N 315-092329-2
ID-60T-135 P/N 315-090288A TRI-B6/B6R/B6D P/N 315-093315-1
I LI-1/1H/1A/1AH P/N 315-092724-2 TRX-1 P/N 315-183462E
ILI-1B/IBH P/N 315-093234-1 TRX-2/2 D/2 R P/N 315-086678-4
P/N 315-093235-1 TRX-3 P/N 315-086288A

CERBERUS Logo 1Cerberus Pyrotronics 8 Ridgedale Avenue
Cedar Knolls, NJ 07927
Tel: 201-267-1300
FAX: 201-397-7008
Website: www.cerbpyro.com
4/97 5M CPY-IG
Printed in U.S.A.
Cerberus Pyrotronics 50 East Pearce Street
Richmond Hill, Ontario L4B, 1B7 CN
Tel: 905-764-8384
FAX: 905-731-9182
April 1997 Supersedes sheet dated 4/96
firealarmresources.com

Documents / Resources

CERBERUS PYROTRONICS XLD-1 X Series Loop Driver [pdf] Owner's Manual
XLD-1 X Series Loop Driver, XLD-1, X Series Loop Driver, Loop Driver, Driver

References

Leave a comment

Your email address will not be published. Required fields are marked *