Autonics logoTHD Series Temperature and Humidity Sensor
Temperature / Humidity Sensor
THD Series
INSTRUCTION MANUAL
TCD220002AB

THD Series Temperature and Humidity Sensor

Thank you for choosing our Autonics product. Read and understand the instruction manual and manual thoroughly before using the product.
For your safety, read and follow the below safety considerations before using. For your safety, read and follow the considerations written in the instruction manual, other manuals and Autonics website.
Keep this instruction manual in a place where you can find easily.
The specifications, dimensions, etc. are subject to change without notice for product improvement. Some models may be discontinued without notice. Follow Autonics website for the latest information.

Safety Considerations

  • Observe all `Safety Considerations’ for safe and proper operation to avoid hazards.
  • symbol indicates caution due to special circumstances in which hazards may occur.

warning 2 Warning Failure to follow instructions may result in serious injury or death.

  1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss.(e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
    Failure to follow this instruction may result in personal injury, economic loss or fire.
  2. Do not use the unit in the place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present.
    Failure to follow this instruction may result in explosion or fire.
  3. Do not connect, repair, or inspect the unit while connected to a power source.
    Failure to follow this instruction may result in fire.
  4. Check `Connections’ before wiring.
    Failure to follow this instruction may result in fire.
  5. Do not disassemble or modify the unit.
    Failure to follow this instruction may result in fire.

warning 2 Caution Failure to follow instructions may result in injury or product damage.

  1. Use the unit within the rated specifications.
    Failure to follow this instruction may result in fire or shortening the life cycle of the product.
  2. Use a dry cloth to clean the unit, and do not use water or organic solvent.
    Failure to follow this instruction may result in fire.
  3. Keep the product away from metal chip, dust, and wire residue which flow into the unit.
    Failure to follow this instruction may result in fire or product damage.

Cautions during Use

  • Follow instructions in `Cautions during Use’. Otherwise, it may cause unexpected accidents.
  • Keep away from high voltage lines or power lines to prevent inductive noise. In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line. Do not use near the equipment which generates strong magnetic force or high frequency noise.
  • Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.
  • 24VDC power supply should be insulated and limited voltage/current or Class 2, SELV power supply device.
  • Do not overlapping communication line and power line. Use twisted pair wire for communication line and connect ferrite bead at each end of line to reduce the effect of external noise.
  • Do not touch THD-W/D sensor part at the bottom of the sensor pole by hands. It may cause malfunction.
  • THD-R must be installed on the wall. It may cause malfunction.
  • Make a required space around the unit for radiation of heat. For accurate temperature measurement, warm up the unit over 20 min after turning on the power.
  • Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power
  • Do not wire to terminals which are not used.
  • This unit may be used in the following environments.
    – Indoors (in the environment condition rated in `Specifications’)
    – Altitude max. 2,000 m
    – Pollution degree 2
    – Installation category II

Ordering Information

This is only for reference.
For selecting the specified model, follow the Autonics website.

Autonics THD Series Temperature and Humidity Sensor - fig 1

  1. Mounting type
    R: Room type (for indoor)
    D: Duct mounting type
    W: Wall mounting type
  2. Display
    No mark: Non-display type
    D: Display type
  3. Sensor pole length
    No mark: Built-in type
    1: 100 mm
    2: 200 mm
  4. Output
Temperature  Humidity
 C Current output
 V Voltage output
T RS485 communication output
 PT DPt1000 resistance value
 PT/C DPt100 resistance value Current output

 Product Components

  • Product
  • Instruction manual
  • Bracket (THD-W / D model)

Software

Download the installation file and the manuals from the Autonics website.
■ DAQMaster
DAQMaster is comprehensive device management program. It is available for parameter setting, monitoring.

Dimensions

  • Unit: mm, For the detailed drawings, follow the Autonics website.

Autonics THD Series Temperature and Humidity Sensor - Dimensions

BracketAutonics THD Series Temperature and Humidity Sensor - Bracket

Connections

• Check the terminal connection diagram and be careful with connecting the power. Autonics THD Series Temperature and Humidity Sensor - Dimensions 1

Case Detachment

When setting communication, turn off the power, remove the case cover, and operate the communication setting switch to set the communication address and speed. Refer to ‘RS485 Communication’ for the details.
THD-R
• Unfasten the bolt on the bottom of the product, separate the case from it.
Autonics THD Series Temperature and Humidity Sensor - botton■ THD-D/THD-W
• Unfasten 4 bolts on the top of the product, separate the case cover from it.
Autonics THD Series Temperature and Humidity Sensor - case cover

Errors

Display part (Temp. / Humi) Description Troubleshooting
Autonics THD Series Temperature and Humidity Sensor - icon 2 Light is ON when malfunction of sensor module. Contact our A/S center.
Autonics THD Series Temperature and Humidity Sensor - icon 3/ Max. value Light is ON when PV is higher than measuring range. When input is within the measuring range, this display disappears.
Autonics THD Series Temperature and Humidity Sensor - icon 5 /Min. value Light is ON when PV is lower than measuring range.

Specifications

Model THD-R-PT
Sensor type Temperature sensor
Display type Non-display type
Temp. measuring range -19.9 to 60.0 °C
Temp. accuracy < +0 8 °C
Temp. output DPt100 Q resistance value (TCR: 3850 ppm/°C)
Protection structure IP10 (IEC standards)
Ambient temperature -20 to 60 °C, Storage: -20 to 60 °C (rated at no freezing or condensation)
Approval Autonics THD Series Temperature and Humidity Sensor - icon
Model THD-R-PT/C THD-R-C
THD-R-V
THD-R-T
THD-DH-❑-❑………………………………..THD-WL-❑-❑
THD-WD❑-❑………………………………….THD-DD❑-❑
Power supply 24 VDC= ±10 %
Power consumption 2.4W
Sensor type Temperature/Humidity Sensor
Sensor response time 10 sec
Display type Non-display type 7 seg. LED display
Display digit Each 3 digits for temp. / humi.
Temp. measuring range -19.9 to 60.0 °C
Humi. measuring range 0.0 to 99.9 %RH (THD-R is required to attend for using over 90 %RH)
Temp. accuracy ± 1.0 °C (at room temp.)
Humi. accuracy ± 3 %RH (30 to 70 %RH, at room temp.)
± 4 %RH (10 to 90 %RH)
Typ.
(10 ± 2to 90 WO %RH
RH, at room temp.)
± 2.5 WoRH
Temp. output DPt100 0 resistance value (TCR: 3850 pp m/°C) DC 4-20 mA (allowable impedance: 600 0),
1-5 VDC=, RS485 Communication (Modbus RTU)
Humi. output DC 4-20 mA (allowable impedance: < 600 0)
Resolution 1/1000
Sampling period 0.5 sec
Insulation resistance 100 M0 (500 VDC= megger)
Dielectric strength 500 VAC— 50/60 Hz for 1 min
Noise immunity ±0.3 kV the square wave noise (pulse width: 1 ps) by the noise simulator
Vibration 0.75 mm amplitude at frequency of 10 to 55 Hz (for 1 min) in each X, Y, Z direction for 1 hour
Vibration (Malfunction) 0.5 mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 1 hour
Shock 300 m/s’ (——- 30 G) in each X, Y, Z direction for 3 times
Shock (Malfunction) 100 m/s’ (#c—- 10 G) in each X, Y, Z direction for 3 times
Protection structure I P10 (IEC standards) IP65 (except sensor part, IEC standards)
Ambient temperature -20 to 60 °C, Storage: -20 to 60 °C (rated at no freezing or condensation)
Cable spec. 04 mm, 4-wire, length: 2 m
Wire spec. AWG22 (0.08 mm, 60-wire), Insulator diameter:01.25 mm
Approval Autonics THD Series Temperature and Humidity Sensor - icon 1 (only for THD-❑-T model) SENNHEISER HD 400 PRO Headphone - erc

Communication Interface

RS485

Comm. protocol Modbus RTU
Application standard Compliance with EIA RS485
Max. Connection 31 units (address: 01 to 31)
Synchronous method Asynchronous
Comm. method 2-wire half duplex
Comm. distance < 800 m
Comm. speed 1200 to 115200 bps (selectable)
Start bit 1 bit (fixed)
Data bit 8 bit (fixed)
Parity bit None (fixed)
Stop bit 1 bit (fixed)
  • It is not allowed to change parameter related to THD communication under the communication with high order system. (THD and upper system are available to change the address at communication status.)
  •  Match the parameter of THD communication to be same as the high order system.
  • It is not allowed to set overlapping communication address at the same communication line.
  • Use twisted pair wire which is appropriate communication cable for RS485 communication.

Autonics logo18, Bansong-ro 513Beon-gil, Haeundae-gu,
Busan, Republic of Korea, 48002
www.autonics.com 
+82-2-2048-1577
sales@autonics.com