D145H4522 Ed. 01
CE SYMBOL Quick guide

AKO D14545-C Universal Controller

AKO-D14545 AKO-D14545-C

Warnings

-If the equipment is used without adhering to the manufacturer’s instructions the device safety requirements could be compromised.
-The installation location of the equipment must be protected from vibrations, water and corrosive gases where the ambient temperature does not exceed the value featured in the technical data.
-To ensure a correct reading the probe must be located away from external effects.
-The power circuit should be equipped with a switch for its disconnection of at least 2 A, 230 V, situated near the appliance.
The cables will be fed in from the rear and will be types H05VV-F or H05V-K.
-The section to be used will depend on the local standard in force, however must never be less than 1 mm².
-The wiring cables for the contact relays must have a section of 2.5 mm².
-Make the connection before plugging in the terminals to the equipment (See Fig. A).
ATTENTION: The equipment is not compatible with AKO-14917 (external communication module) and AKO-14918 (programming key).

Installation

AKO D14545-C Universal Controller - Fig 1

Quick start

AKO D14545-C Universal Controller - Fig 2 By using keys UP and Down, select the most suitable option according to the installation type in accordance with the table in the “WIZARD” appendix and press SET. The wizard configures the equipment parameters and assigns the input and output functions according to the installation type chosen.
AKO D14545-C Universal Controller - Fig 3 Select the refrigerant gas type used from amongst the following options:
0=R404A 1=R134A 2=R407A 3=R407F 4=R410A 5=R450A 6=R513 7=R744 8=R449A
9=R290 10=R32 11=R448A 12=R1234ze 13=R23 14=R717 15=R407C 16=R1234yf 17=R22
18=R454C 19=R455A 20=R507A 21=R515B 22=R452A 23=R452b 24=R454A 25=R12 26=R114
27=R142B 28=R170 29=401A 30=R402A 31=R407B 32=R413A 33=R417A 34=R422A 35=R422D
36=R427A 37=R438A 38=R500 39=R502 40=R503 41=R600 42=R600A
AKO D14545-C Universal Controller - Fig 4 Select the primary and secondary display units from amongst the following options:
0=bar-ºC; 1=psi-ºF; 2=psi-ºC; 3=bar-ºF; 4=ºC-bar; 5=ºF-psi; 6=ºC-psi; 7=ºF-bar
AKO D14545-C Universal Controller - Fig 5 Configure the rest of the parameters to their default value? :
0=No, the configuration is kept for all the parameters except for C01, C02, C04, C05 C06, C08 and C09.
1=Yes, all the parameters are configured to their default value (see parameters table)
(This option does not affect parameters C01, C02, C04, C05 C06, C08 and C09)

“WIZARD” table

The “WIZARD” table in the appendix is divided into 3 groups of columns. The first describes the different installation types (number of compressors and fans, if they have an inverter, etc.) associated with the INI option.
The second group specifies the function assigned to each relay depending on the INI option selected.
The third group specifies the function assigned to each digital input depending on the INI option selected.

Installation type

AKO D14545-C Universal Controller - Fig 7

Relay function

AKO D14545-C Universal Controller - Fig 8

Input function

AKO D14545-C Universal Controller - Fig 9

Operation

ESC key
In the programming menu, exit the parameter without saving changes, return to previous level or exit programming.

SET key
By pressing this key for 1 second the probe display units change (according to parameter C09).
Pressing it for 10 seconds accesses the programming menu.
In the programming menu, it accesses the level shown on the display or, during the setting of a parameter accepts the new value.

UP UP key
By pressing this key for 1 second probe 2 is displayed for 5 seconds (or probe 1, according to parameter P02). By pressing a
second time the probe ambient temperature value will be shown (only if I07 or I08=3).
In the programming menu it allows scrolling around the different levels, or during the setting of a parameter, changing its value.

Down DOWN key
Pressing this key returns the equipment to its normal operation after an alarm which require a reset (the causes which triggered
the alarm must have disappeared).
In the programming menu it allows scrolling around the different levels, or during the setting of a parameter, changing its value.

Paulmann Ceiling Lighting Accessories - Icon 1 In order to start the wizard again, disconnect the unit’s power supply, reconnect it and, during the subsequent 8 seconds, press the key sequence N UP ,Down, SET.

Operation start-up

Upon being supplied with power the equipment will start up in WIZARD mode (INI / 1 flashing), press UP or Down to select the most suitable option for the installation type, check the options in the “WIZARD” appendix.
The wizard configures the equipment parameters and assigns the input and output functions according to the installation type chosen.

Messages

MESSAGES
AKO D14545-C Universal Controller - Symbol 1 Access code (Password) request D
AKO D14545-C Universal Controller - Symbol 2 Pump down detained due to time D
AKO D14545-C Universal Controller - Symbol 3 Low pressure alarm due to probe 1 D
AKO D14545-C Universal Controller - Symbol 4 High pressure alarm due to probe 2 D R
AKO D14545-C Universal Controller - Symbol 5 Thermal alarm 1 D R
AKO D14545-C Universal Controller - Symbol 6 Thermal alarm 2 D R
AKO D14545-C Universal Controller - Symbol 7 Thermal alarm 3 D R
AKO D14545-C Universal Controller - Symbol 8 Thermal alarm 4 D R
AKO D14545-C Universal Controller - Symbol 9 Thermal alarm 5 D R
AKO D14545-C Universal Controller - Symbol 10 Severe external alarm (input I5 or I6) D R
AKO D14545-C Universal Controller - Symbol 11 Remote regulation detained due to digital input (input I5 or I6) D
AKO D14545-C Universal Controller - Symbol 12 Low pressure alarm due to digital input (input I5 or I6) D R
AKO D14545-C Universal Controller - Symbol 13 High pressure alarm due to digital input (input I5 or I6) D R
AKO D14545-C Universal Controller - Symbol 14AKO D14545-C Universal Controller - Symbol 16 Error in probe 1, 2 or 3 (open circuit, probe crossed or out of range) D
D
D
R
R
R

D: The message is shown on the display.
R: Alarm relay activated (if available, see WIZARD table).

Table of parameters and messages

The Def. column indicates the ex-works configured default parameters. The pressure values featured on the table are expressed in bar and those for temperature in ºC. If the wizard meanwhile
selects another set of units (parameter C09), the equipment will make the conversion automatically.

Level 2

Read only parameters can only be edited using the INI wizard.

INSTALLATION CONFIGURATION
Description Units  Min.  Def Max.
AKO D14545-C Universal Controller - Symbol 22 C01 Total number of compressors (with or without inverter) bar
C02 Number of stages per compressor
C03 Polarity of the capacity reduction contact
0=Active when closing the contact; 1=Active when opening the contact
0 0 1
C04 Compressor 1 with frequency inverter  0=No; 1=Yes
C05 Total number of fans (1 inverter only is considered with inverter)
C06 Fan control type 0=ON/OFF; 1=Frequency inverter
C07 Operation type 0=Direct; 1=Inverse 0 0 1
C08 Refrigerant gas type 0=R404A, 1=R134A, 2=R407A, 3=R407F, 4=R410A, 5=R450A,6=R513, 7=R744, 8=R449A, 9=R290, 10=R32, 11=R448A, 12=R1234ze, 13=R23,14=R717, 15=R407C, 16=R1234yf, 17=R22, 18=R454C, 19=R455A, 20=R507A,21=R515B, 22=R452A, 23=R452b, 24=R454A, 25=R12, 26=R114, 27=R142B,28=R170, 9=401A, 30=R402A, 31=R407B, 32=R413A, 33=R417A, 34=R422A,35=R422D, 36=R427A, 37=R438A, 38=R500, 39=R502, 40=R503, 41=R600,42=R600A
C09 Display units (Primary-Secondary),
0=bar-ºC, 1=psi-ºF, 2=psi-ºC, 3=bar-ºF, 4=ºC-bar, 5=ºF-psi, 6=ºC-psi, 7=ºF-bar
C10 Frequency inverter output type  0=4-20 mA; 1=0-10 V 0 0 1
InI This indicates the configuration selected in the wizard (read only)
EP Output to level 1
EVAPORATION CONFIGURATION
AKO D14545-C Universal Controller - Symbol 23 E01 Pressure / evaporation temperature set point bar E03 5 E02
E02 Evaporation set point upper limit (It cannot be set above this limit) bar E03 65 65
E03 Evaporation set point lower limit (It cannot be set below this limit) bar -0.7 -0.7 E02
E04 Tipo Compressor rotation type: 0=Balancing, depending on the operation time
1=Sequential (the last in is the first out)
0 0 1
E05 Compressor control type: 0=Neutral zone; 1=Proportional 0 0 1
E06 Evaporation regulation bandwidth bar 0 2 50
E07 Integral time (PID inverter control) sec. 2 5 10
E08 Stop value for pump down (If C07=0) bar -0.7 0.1 *
E09 Maximum pump down time (If C07=0) (0= deactivated) sec.x10 0 0 255
EP Output to level 1
CONDENSATION CONFIGURATION
AKO D14545-C Universal Controller - Symbol 24 F01 Condensation pressure / temperature set point bar F03 14 F02
F02 Condensation set point upper limit (It cannot be set above this limit) bar F03 65 65
F03 Condensation set point lower limit (It cannot be set below this limit) bar -1.4 -0.7 F02
F04 Fan rotation type:
0=Balancing, depending on the operation time
1=Sequential (the last in is the first out)
0 1 1
F05 Fan control type: 0=Neutral zone; 1=Proportional 0 0 1
F06 Condensation regulation bandwidth bar 0 2 50
F07 For fans when the compressors stop  0=No; 1=Yes 0 0 1
F08 Floating condensation 0=No; 1=Yes 0 0 1
F09 Integral time (PID inverter control) sec. 2 5 10
F10 Floating condensation minimum set point value ( see remark 1) ºC -50 28 99.9
F11 Condenser temperature delta ºC 6 12 20
EP Output to level 1
PROBE CONFIGURATION
AKO D14545-C Universal Controller - Symbol 25 P01 Probe type selection 0=4-20 mA; 1=0.5 – 4.5 V; 2=NTC 0 1 2
P02 Probe to be displayed: 0=Probe 1 (Aspiration)
1=Probe 2 (Discharge);
2=Probes 1 and 2 in carousel
0 0 2
P03 Value  4 mA / 0.5 V (according to P01) probe 1 bar -60 -1 65
P04 Value  20 mA / 4.5 V (according to P01) probe 1 bar -60 9 65
P05 Probe 1 calibration (Offset) bar -20 0 20
P06 Value  4 mA / 0.5 V (according to P01) probe 2 bar -60 0 65
P07 Value  20 mA / 4.5 V (according to P01) probe 2 bar -60 34 65
P08 Probe 2 calibration (Offset) bar -20 0 20
P09 Calibration of the outside temperature probe for floating condensation ºC -20 0 20
EP Output to level 1

Remark 1: The equivalent value in pressure is calculated depending on the refrigerant gas specified in the wizard.
* Depending on the compressor control type:
Proportional=E01; Neutral zone=E01-E06.
** If the compressor is equipped with an inverter, this period of time halves.

Level 1
DIGITAL INPUT CONFIGURATION
Description Units Min. Def. Max.
AKO D14545-C Universal Controller - Symbol 17 I01 Polarity digital input 1 (thermal stage 1): 0=Activates on closing contact; 1=Activates on opening contact 0 0 1
I02 Polarity digital input 2 (thermal stage 2): 0=Activates on closing contact; 1=Activates on opening contact 0 0 1
I03 Polarity digital input 3 (thermal stage 3): 0=Activates on closing contact; 1=Activates on opening contact 0 0 1
I04 Polarity digital input 4 (thermal stage 4): 0=Activates on closing contact; 1=Activates on opening contact 0 0 1
I05 Polarity digital input 5: 0=Activates on closing contact; 1=Activates on opening contact 0 0 1
I06 Polarity digital input 6: 0=Activates on closing contact; 1=Activates on opening contact 0 0 1
I07 Digital input 5 function:   0=Low pressure alarm 1=High pressure alarm 2=Thermal stage alarm 5 3=Ambient temperature probe 4=External alarm
5=Remote disconnection ON-OFF 6=Variation in the aspiration set point (E01) (see remark 2)
0 0 6
I08 Digital input 6 function:   0=Low pressure alarm 1=High pressure alarm 2=Thermal stage alarm 5 3=Ambient temperature probe 4=External alarm
5=Remote disconnection ON-OFF 6=Variation in the aspiration set point (E01) (see remark 2)
0 1 6
I09 Turn-on delay time of digital input 5 (not applicable if I07=2) sec. 0 0 255
I10 Turn-on delay time of digital input 6 (not applicable if I08=2) sec. 0 0 255
I11 Variation in the evaporation set point (new set point= E01+I11) (see remark 2) bar -20 0 20
I12 Duration of the variation in the evaporation set point (see remark 2) min. 0 255
EP Output to level 1
TIMING CONFIGURATION
Description Units Min. Def. Max.
AKO D14545-C Universal Controller - Symbol 18 t01 Minimum operation time for a compressor sec. x10 1 2 999
t02 Minimum disconnection time for a compressor ** sec. x10 1 2 999
t03 Delay time between the compressor start-up/stage and the next one sec. 1 30 999
t04 Delay time between the compressor stop/stage and the next one sec. 1 10 999
t05 Minimum operation time for a fan sec. x10 1 1 999
t06 Minimum disconnection time for a fan sec. x10 1 1 999
t07 Delay time between the fan start-up and the next one sec. 1 2 999
t08 Delay time between the fan stop and the next one sec. 1 2 999
EP Output to level 1
CONFIGURATION OF PROTECTIONS AND ALARMS
Description Units Min. Def. Max.
AKO D14545-C Universal Controller - Symbol 19 A01 Number of active compressor stages with error in probe 1 0 0 ***
A02 Number of active fans or inverter % with error in probe 2 Without inverter 0 C05 C05
With inverter 0 100% 100%
A03 Low pressure alarm in probe 1 bar -0.7 0 65
A04 Low pressure alarm differential bar 0.1 1.0 20
A05 High pressure alarm in probe 2 bar -0.7 20 65
A06 High pressure alarm differential bar 0.1 1.0 20
A07 Alarm delay after reaching the value sec. 0 60 999
A08 Delay of temperature alarms in the start-up. sec. 0 0 255
A09 High pressure alarm limit (per digital input) per hour without manual reset. (If I07 or I08=1) (0=deactivated) Once the limit has been exceeded a manual reset will be required for each new alarm. 0 0 255
EP Output to level 1
ACCESS AND INFORMATION CONTROL
Description Units Min. Def. Max.
AKO D14545-C Universal Controller - Symbol 20 b20 Address for units with communication 1 1 255
b21 Communication speed: 0:9600 bps; 1:19200 bps; 2:38400 bps; 3:57600 bps 0 0 3
L5 Access code (Password) 0 0 999
PU Programme version
Pr Programme revision
Psr Programme sub-revision (Information)
OPERATION TIMES
Description Units Min. Def. Max.
AKO D14545-C Universal Controller - Symbol 21 c1 This shows the operation time for the compressor or fan 1 h. x10 999
c2 This shows the operation time for the compressor or fan 1 h. x10 999
c3 This shows the operation time for the compressor or fan 1 h. x10 999
c4 This shows the operation time for the compressor or fan 1 h. x10 999
c5 This shows the operation time for the compressor or fan 1 h. x10 999
EP Output to level 1

Remark 2: In the event of the energy saving and the variation in the set point per digital input being activated at the same time, the variation in the set point per digital input will always prevail.por entrada digital, prevalecerá siempre la variación del Set Point por entrada digital.
*** The number of stages depends on the configuration selected in the wizard.

Technical specifications

Power supply ………………………………………………………………………………. 90-240 V~ 50/60 Hz
Maximum voltage in the SELV circuits …………………………………………………………………….20 V
Inputs ………………………………………………………………………. 2 analog inputs + 6 digital inputs
Relays R1 to R4 ………………………………………………………… (EN60730-1: 5(4) A 250 V~ SPST)
Relay R5 …………………………………………………………………. (EN60730-1: 5(4) A 250 V~ SPDT)
No. of relay operations …………………………………………………. EN60730-1: 100.000 operations
Types of probes ……………………………………………NTC AKO-149xx, 4-20 mA, 0-5 V ratiometric
Measuring range NTC ………………………………….. -50,0 ºC to +99,9 ºC (-58,0 ºF to 211 ºF)
4-20 mA / 0-5 V …………………………………………………………… -60 to 999
Resolution NTC ………………………………………………………………………………. 0.1 ºC (0.1 ºF)
4-20 mA / 0-5 V -99.9 to 99.9 …………………………………………………….0.1
≤ 100 /≥100 ……………………………………………….1
Thermometric precision of the equipment (S1/S2) NTC …………………………………………..± 1 ºC
4-20 mA ……………………………………± 1 %
0.5 – 4.5 V …………………………………± 1 %
Working environment ………………………………………………………. -10 a 50 ºC, moisture <90 %
Storage environment ……………………………………………………….. -30 a 70 ºC, moisture <90 %
Protection degree of the front part …………………………………………………………………………IP65
Fixing ………………………………………………………………………………Panel mounting with anchors
Panel cavity dimensions ……………………………………………………………………………. 71 x 29 mm
Front part dimensions ………………………………………………………………………………. 79 x 38 mm
Depth ………………………………………………………………………………………………………….. 61 mm
Connections: ………………………….Terminal to screw for cables with a section of up to 2.5 mm2 Control device classification: Built-in assembly, with Type 1.B automatic operation action feature, for use in clean situations, logical support (Software) class A and continuous operation.
Degree of contamination 2 acc. to UNE-EN 60730-1.
Double power input insulation, secondary circuit and relay output.
Rated pulse voltage …………………………………………………………………………………………2500V Pressure ball test temperature:
Accessible parts …………………………………………………………………………………………… 75 ºC
Parts that position active elements ………………………………………………………………… 125 ºC
Voltage and current declared by the EMC tests …………………………………………… 207 V, 17 mA
Radio interference suppression test current …………………………………………………………270 mA

ako logo

AKO ELECTROMECÁNICA , S.A.L.
Avda. Roquetes, 30-38
08812 • Sant Pere de Ribes.
Barcelona • Spain.
www.ako.com

We reserve the right to supply materials that might vary slightly to those described in our Technical Sheets. Updated information is available on our website.