AKO 16526 V2 Advanced Temperature Controller
Product Usage Instructions
- Make sure to follow all safety instructions provided in the manual.
- Regular maintenance is essential for the proper functioning of the product. Refer to the maintenance section in the manual for detailed instructions.
- Proper connection of the product is crucial for its performance.
- Follow the connection guidelines provided in the manual.
- Use the keyboard to input commands and navigate through the settings.
- Ensure sensors are properly connected and functioning to monitor temperature accurately.
- Follow the assistant’s instructions displayed on the screen to set up and configure the product.
- Operate the product according to the specified settings and modes mentioned in the manual.
- Pay attention to messages displayed on the screen for important notifications and alerts.
FAQ
- Q: How do I silence an ongoing alarm?
- A: To silence an ongoing alarm, follow the steps outlined in the manual, usually involving pressing a specific key or combination of keys.
- Q: How do I set the type of refrigerant gas used?
- A: Navigate to the relevant menu on the display using the arrow keys and select the appropriate gas type from the available options. Confirm your selection by pressing the SET key.
- Q: What should I do if there is a final defrost alert?
- A: When you receive a final defrost alert, make sure to check and address any issues related to exceeding the defined defrost time as per the settings.
Warnings
- If the device is used without adhering to the manufacturer’s instructions, the device safety require-ments could be compromised. Only sensors supplied by AKO must be used for the unit to operate correctly.
- From -40°C to +20°C, if the NTC sensor is extended to 1000m with at least a 0.5mm2 cable, the maximum deviation will be 0.25°C (cable for sensor extension ref. AKO-15586 / AKO-15586H. Earth the cable mesh at one end only).
- Pt1000 sensors can be extended up to 25m using the AKO-15586 / AKO-15586H sensor extension cable..
- The product should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the value indicated in the technical data.
- For the reading to be correct, the sensor should be used in a place without heat influences apart from the tem-perature you want to measure or control.
- The IP65 protection degree is only valid with the protection cover closed.
- The IP65 protection degree is only valid if the cables enter the device using a tube for electric conductions + gland with IP65 or above. The gland should be the right size for the diameter of the tube used.
- Do not spray the unit directly with high-pressure hoses, as this could damage it.
IMPORTANT
- The AUXILIARY relays are programmable, and their operation depends on the configuration.
- The function of the digital inputs depends on the configuration.
- The recommended currents and powers are the maximum working currents and powers.
Maintenance
- Clean the surface of the unit with a soft cloth, water and soap.
- Do not use abrasive detergents, petrol, alcohol or solvents, as this might damage the unit.
Wiring
- Always disconnect the power supply to do the wiring.
- The sensors and their cables must NEVER be installed in a conduit together with power, control or power supply cables.
- For disconnection, the power supply circuit must be equipped with at least a 2 A, 230 V switch, located near the device. The power supply cable shall be of the H05VV-F or NYM 1×16/3 type. The section to be used will depend on current local regulations, but should never be less than 1.5mm2.
- Cables for relay or contactor outputs should have a section of 2.5mm2, allow working temperatures equal to or over 70ºC, and be installed with as little bending as possible.
- The 120/230 V~ wiring area must be kept clear of any other external element.
- The wiring setup depends on the options selected in the set-up wizard and on the input and output configurations (See page 31).
- Check the enclosed schematic and the defined configuration before wiring.
- The parameter St (Type of connected probes) affects all probe inputs. Therefore all connected probes (NTC or Pt1000) must be the same.
Description
- Temperature controller with output for electronic expansion valve regulation and evaporator fan speed control.
- In addition to regulating the cooling of the cold room, the controller can be configured to control superheating and regulate the speed of the evaporator fans using an inverter or electronic fans.
Keypad
Press and hold for 3 seconds to activate/deactivate the Stand-By mode. In this mode, regulation is paused and the m icon
is displayed.
- In the programming menu, this key exits the parameter without saving changes and returns to the previous level or exits programming.
Pressing once without holding displays the temperature of sensor S2 for 10 seconds (if it is enabled). Pressing it for 3 seconds starts/stops the defrost.
- In the programming menu, it allows you to scroll through the different levels, or when setting a parameter to change its value.
Pressing it for 3 seconds activates/deactivates the continuous cycle mode.
- In the programming menu, it allows you to scroll through the different levels, or when setting a parameter to change its value.
Pressing once without holding activates/deactivates the cold room light.
- Pressing it for 3 seconds accesses the condensed programming menu.
- Pressing it for 6 seconds accesses the expanded programming menu.
- In the programming menu, it accesses the level shown on the display or, during the setting of a parameter, accepts the new value.
Pressing it once without holding it down displays the current effective value of the temperature Set Point in the upper display and the superheating set point in the lower display, taking into considera-tion temporary changes due to other parameters.
- When an alarm is in progress, pressing once without holding mutes the acoustic alarm.
- Pressing for 3 seconds accesses the temperature Set Point setting.
STAND-BY
- If the regulation cannot be stopped immediately due to its configuration, a controlled stop process starts and the m icon flashes. To stop the controlled stop process and force Stand-by, press the Stand-by key again for 3 seconds.
Probes
Wizard
The first time the unit receives the power supply, it will enter into Wizard mode.
The display will show the message flashing at
.
The buttons change the value, the SET button accepts the value and moves on to the next step.
Step 1
Select the most suitable InI option based on the type of installation to be carried out and press SET.
The available options will be shown in the following table:
InI |
Type of installation | Parameters | ||||||||||||
Control of the compressor | Pump Down | Defrost | Evap. Fans | Pd | o00 | I00 | I10 | I11 | I20 | I21 | d1 | D7 | F3 | |
0 | Demo mode: it displays the temperature but does not regulate the temperature | |||||||||||||
1 | No | No | Electric | Yes | 0 | 0 | 2 | 0 | 0 | 0 | 0 | 20 | 0 | 0 |
2 | Yes | Yes | Electric | Yes | 1 | 1 | 2 | 7 | 1 | 0 | 0 | 20 | 0 | 0 |
3 | Yes | No | Electric | Yes | 0 | 1 | 2 | 0 | 0 | 0 | 0 | 20 | 0 | 0 |
4 | No | No | Air | Yes | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 20 | 1 | 1 |
5 | Yes | Yes | Air | Yes | 1 | 1 | 1 | 7 | 1 | 0 | 0 | 20 | 1 | 1 |
6 | Yes | No | Air | Yes | 0 | 1 | 1 | 0 | 0 | 0 | 0 | 20 | 1 | 1 |
7 | Yes | Yes | Hot gas | Yes | 1 | 1 | 2 | 7 | 1 | 7 | 1 | 5 | 2 | 0 |
8 | Yes | No | Hot gas | Yes | 0 | 1 | 2 | 0 | 0 | 7 | 1 | 5 | 2 | 0 |
If options 2, 5 or 7 are chosen, check the configuration of parameter I11 according to the pressure switch type used.
Step 2
- Define the type of refrigerant gas used.
Step 3*:
- Define the minimum value of the pressure sensor (I62) (value at 4 mA, 0 V, 0.5 V or 1 V according to I61).
Step 4*:
- Define the maximum value of the pressure sensor (I63) (value at 20 mA, 5 V, 4.5 V or 10 V according to I61).
- *Steps only visible if u02=7
Step 5:
- Select the temperature set point.
Step 9:
- Set all other parameters to default.
- dFP=0 No, the other parameters do not need to be changed
- dFP=1 Yes, set all other parameters to their default values
- This option only appears if this is not the first time the set-up wizard has been run.
- The initial configuration is now complete, and the device will start to regulate the temperature.
The configuration wizard will not reactivate. To reactivate it, activate the standby mode (by pressing the m key for 3 seconds) and wait until the unit completely halts regulation (the m indicator will light up permanently) and press the SET buttons in this order in sequence, not at the same time.
If the Pump Down function is active, there may be a delay between the initiation of the Stand-by function and the moment the controller stops.
Operation
Messages
Pump down malfunction error (Stop). The time configured in parameter C20 has been exceeded. Only displayed on screen.
Pump down malfunction error (Start). The time configured in parameter C19 has been exceeded. Only displayed on screen.
Sensor 1, 2, 3, 4, 5, or 6 is faulty (open circuit, crossed circuit, or value outside sensor limits). Activates the alarm relay and the audible alarm.
Open door alarm. Only if the door stays open for a longer time than defined in parameter A12. Activates the alarm relay and the audible alarm.
Maximum temperature in control sensor alarm. The temperature value programmed in A1 has been reached. Activates the alarm relay and the audible alarm.
Minimum temperature in control sensor alarm. The temperature value programmed in A2 has been reached. Activates the alarm relay and the audible alarm.
External alarm activated (by digital input). Activates the alarm relay and the audible alarm.
Severe external alarm activated (by digital input). Activates the alarm relay and the audible alarm.
Defrost the time-out alert. The time set in d1 has been exceeded.
HACCP alarm. The temperature has reached the value of parameter h1 for a longer period than established in h2. Activates the alarm relay and the audible alarm.
HACCP alarm due to a fault in the electric supply. The temperature set in h1 has been reached following a fault in the electric supply. Activates the alarm relay and the audible alarm.
Minimum superheat alarm. The value set in A20 has been reached. Activates the alarm relay and the audible alarm.
Minimum superheat alert. The value defined in A23 has been reached. Only displayed on screen.
Maximum evaporating pressure alarm. The value defined in A26 has been reached. Activate the alarm relay and the audible alarm.
Minimum evaporating alarm. The value defined in A29 has been reached. Activates the alarm relay and the audible alarm.
Indicates that a defrost is being performed. Only displayed on screen.
Password request. See parameters b10 and PAS. Only displayed on screen.
Shown sequentially with the temperature: the controller is in demo mode, and the configuration has not been made.
Configuration
Condensed programming menu
- This allows for the most-used parameters to be quickly configured. Press the SET key for 3 seconds to access it.
Parameters
Level 2 | |||||
Description | Values | Min. | Def. | Max. | |
SP | Temperature setting (Set Point) | ºC/ºF | -50 | 0.0 | 99 |
C1 | Sensor 1 differential (Hysteresis) | ºC/ºF | 0.1 | 2.0 | 20.0 |
d0 | Defrost frequency (time between 2 starts) | h. | 0 | 6 | 96 |
d1 | Maximum defrost duration (0=defrost deactivated) | min. | 0 | * | 255 |
d4 | Final defrost temperature (by the sensor) (If I00 ¹ 1) | ºC/ºF | -50 | 8.0 | 50 |
SH | Superheating set point | ºK | 0.1 | 8 | 40 |
F3 | Status of the fans during the defrost 0=stopped; 1=running | 0 | * | 1 | |
A1 | Alarm for maximum in sensor 1 (it must be higher than the SP) | ºC/ºF | A2 | 99.0 | 99.0 |
A2 | Alarm for minimum in sensor 1 (it must be lower than the SP) | ºC/ºF | -50 | -50 | A1 |
* According to the set-up wizard.
Extended programming menu
Use the extended programming menu to configure all of the unit’s parameters to adapt it to your installation requirements. Press the SET key for 6 seconds to access it.
IMPORTANT: if the password function has been configured as a keypad lock (b10=2), or as an access to parameters block (b10=1), you will be requested to enter the password programmed in PAS when attempting to access either of the two functions. If the entered password is not correct, the unit will go back to showing the temperature.
IMPORTANT: certain parameters or menus may not be visible depending on the configuration of the other parameters and the options chosen during set-up.
Extended programming menu
Parameters
Regulation and control
Defrost
Level 1 | Level 2 | |||||
Description | Values | Min. | Def. | Max. | ||
dEF | d0 | Defrost frequency (time between 2 starts) | h. | 0 | 6 | 96 |
d1 | Maximum defrost duration (0=defrost deactivated) | min. | 0 | * | 255 | |
Type of message during the defrost: 0=sign of the real temperature; 1=sign of | ||||||
d2 | the temperature at the start of the defrost; | 0 | 2 | 2 | ||
2=sample of the dEF message | ||||||
d3 | Maximum message duration | min. | 0 | 5 | 255 | |
(time added at the end of the defrost process) | ||||||
d4 | Final defrost temperature (by the sensor) (If I00¹1) | ºC/ºF | -50 | 8.0 | 50 | |
d5 | Defrost on connecting the unit: 0=NO, first defrost according to d0; | 0 | 0 | 1 | ||
1=YES, first defrost according to d6 | ||||||
d6 | Delay of the defrost start on connecting the unit | min. | 0 | 0 | 255 | |
d7 | Type of defrost: 0=resistors; 1=air/fans | 0 | * | 2 | ||
2=hot gas | ||||||
d8 | Time calculation between defrost periods: | 0 | 0 | 1 | ||
0=total real-time 1=sum of COOL time connected | ||||||
d9 | Drip time when a defrost finishes | min. | 0 | 1 | 255 | |
(stop COOL and fans) | ||||||
EP | Output to level 1 |
Evaporator fans
Level 1 | Level 2 | |||||
Description | Values | Min. | Def. | Max. | ||
FAn | F0 | Fans stop temperature ºC/ºF. -50 45 50 | ||||
F1 | Sensor 2 differential if fans are stopped | ºC/ºF | 0.1 | 2.0 | 20.0 | |
F2 | Stop fans when the compressor stops 0=no 1=yes 0 0 1 | |||||
F3 | Status of the fans during the defrost 0=stopped; 1=running | 0 | * | 1 | ||
F4 | Start-up delay after defrost (if F3=0) min. 0 2 99 Only actuates if higher than d9 | |||||
F10 | Fan control type 0=ON/OFF 1=frequency inverter | 0 | 0 | 1 | ||
EP | Output to level 1 |
Expansion valve
Level 1 | Level 2 | |||||
Description | Values | Min. | Def. | Max. | ||
EEV | u00 | Valve type: 0=solenoid + EV thermostat 1= PWM-type EEV 0 1 2 2=Stepper-type EEV | ||||
SH | Superheating set point | K | 0.1 | 8 | 40 | |
u02 |
Refrigerant gas type: 0= R-404A, 1= R-134A, 2= R-407A, 3= R-407F, 4= R-410A,
5= R-450A, 6= R-513A, 7= R-744, 8= R-449A, 9= R-290, 10= R-32, 11= R-448A, 0 * 17 12=R1234ze, 13=R23, 14=R717, 15=R407C, 16=R1234yf, 17=R22, 18=R454C, 19=R455A, 20=R507A, 21=R515B, 22=R452A, 23=R452B, 24=R454A |
|||||
u03 | PWM cycle time | s. | 2 | 6 | 10 | |
u04 | Proportional constant value (P) 1 10 100 | |||||
u05 | Integral constant value (I) | 0 | 10 | 100 | ||
u06 | Derivative constant value (D) 0 0 100 | |||||
u07 | Opening value of the electronic expansion valve when cooling is activated | % | u13 | 50 | u12 | |
u08 | Duration of valve opening on cooling demand s. 2 5 240 | |||||
u09 | Valve opening value with sensor error S5 or S6: 0=fixed opening according to u10; 1=average opening over the last 24 hours | 0 | 0 | 1 | ||
u10 | Valve opening value with sensor error S5 or S6 (if u09=0) % u13 0 u12 | |||||
u11 | Manual valve opening value (-1=disabled), (cycles acc. to u03) Requires safety code. See user manual. | % | -1 | -1 | 100 | |
u12 | Maximum valve opening value % u13 100 100 | |||||
u13 | Minimum valve opening value | % | 0 | 0 | u12 | |
u14 | Valve opening value after defrost (0=disabled), (duration according to u15) % 0/ 0 u12
u13 |
|||||
u15 | Duration of valve opening after defrosting | s | 0 | 0 | 240 | |
u16 | Valve opening in case of LOP error (0=valve closed) % 0/ 0 u12 u13 | |||||
EP | Output to level 1 |
Alarms
Level 1 | Level 2 | |||||
Description | Values | Min. | Def. | Max. | ||
AL | A0 | Configuration of the temperature alarms 0=relative to SP 1=absolute 0 1 1 | ||||
A1 | Alarm for maximum in sensor 1 (it must be higher than the SP) | ºC/ºF | A2 | 99.0 | 99.0 | |
A2 | Alarm for minimum in sensor 1 (it must be lower than the SP) ºC/ºF -50 -50 A1 | |||||
A3 | Delay of temperature alarms in the start-up | min. | 0 | 0 | 120 | |
A4 | Delay of temperature alarms from the end of a defrost min. 0 0 99 | |||||
A5 | Delay of temperature alarms from when the A1 or A2 value is reached | min. | 0 | 30 | 99 | |
A6 | Delay of external alarm/severe external alarm on receiving digital input signal min. 0 0 120 (I10 or I20=2 or 3) | |||||
A7 | External alarm deactivation delay/severe external alarm on the disappearance of the signal at digital input (I10 or I20=2 or 3) | min. | 0 | 0 | 120 | |
A8 | Show warning if the defrost ends for maximum time 0=no 1=yes 0 0 1 | |||||
A9 | Polarity relay alarm 0=relay ON in alarm (OFF without alarm); 1=relay OFF in alarm (ON without alarm) | 0 | 0 | 1 | ||
A10 | The differential of temperature alarms (A1 and A2) ºC/ºF 0.1 1.0 20.0 | |||||
A12 | Delay of open door alarm (if I10, I20 or I30=1) | min. | 0 | 10 | 120 | |
A20 | Minimum superheating value for LSH alarm K 0 2 SH | |||||
A21 | LSH alarm activation delay | sec. | 0 | 30 | 240 | |
A22 | LSH alarm hysteresis K 0.1 2 Sh-
A20 |
|||||
A23 | Maximum overheating value for LSH alert | K | sh | 40 | 40 | |
A24 | Delayed activation of the HSH warning s 0 30 240 | |||||
A25 | HSH alarm deactivation hysteresis | K | 0.1 | 2 | A23-
sh |
|
A26 | Maximum evaporating pressure (MOP) bar 0 60 60 | |||||
A27 | MOP alarm activation delay (delay time for activating alarm after the threshold has been exceeded) | sec. | 0 | 30 | 240 | |
A28 | MOP alarm deactivation hysteresis (when the pressure drops below the bar 0.1 1 60 MOP-hysteresis level the alarm is deactivated) | |||||
A29 | Minimum evaporating pressure (LOP) | bar | -1 | 0 | 8 | |
A30 | LOP alarm activation delay (delay time for activating alarm after the threshold has sec. 0 30 240 been exceeded) | |||||
A31 | LOP alarm deactivation hysteresis (when the pressure exceeds the LOP-hysteresis level the alarm is deactivated) | bar | 0.1 | 1 | 8 | |
EP | Output to level 1 |
Basic configuration
Level 1 | Level 2 | |||||
Description | Values | Min. | Def. | Max. | ||
bcn | b00 | Delay of all functions on receiving power supply min. 0 0 255 | ||||
b01 | Cold room light timing | min. | 0 | 0 | 999 | |
b10 | Password function 0=inactive 0 0 2
1=parameter access lock 2=keypad lock |
|||||
PAS | Password | 0 | 0 | 99 | ||
b20 | MODBUS address 1 1 247 | |||||
b21 | Communication speed: 0=9600 bps 1=19200 bps
2=38400 bps 3=57600 bps |
bps | 0 | 0 | 3 | |
b22 | Audible alarm enabled 0=no 1=yes 0 1 1 | |||||
b23 |
Lower display function: 1=sensor S2, 2=sensor S3, 3=sensor S4, 4=sensor S5, 5=superheating, 6=pressure sensor, 7=% EEV, 8=% eFAN, 9=carousel, 10=off |
1 |
* |
10 |
||
Unt | Working units 0=ºC 1=ºF 0 0 1 | |||||
EP | Output to level 1 |
Inputs and outputs
Level 1 | Level 2 | |||||
Description | Values | Min. | Def. | Max. | ||
InO | St | Type of probes connected: 0= NTC, 1= Pt1000 | 0 | 0 | 1 | |
I00 | Probes connected: 1=sensor 1 (cold room), 2=sensor 1 (cold room) + sensor 1 2 2
2 (evaporator) |
|||||
I10 |
D1/S3 input configuration: 0=deactivated, 1=door contact, 2=external alarm, 3=severe external alarm, 4=change SP, 5=remote defrost,
6=defrost lockout, 7=low pressure switch, 8=remote activation in Stand-by mode, 9=product temperature |
0 |
* |
9 |
||
I11 | Digital input polarity D1: 0=activates on closing, 1=activates on opening 0 0 1 contact | |||||
I20 |
D2/S4 input configuration: 0=deactivated, 1=door contact, 2=external alarm, 3=severe external alarm, 4=change SP, 5=remote defrost,
6=defrost lockout, 7=high pressure switch for hot gas, 8=remote activation of Stand-by mode, 9=product temperature, 10=defrost 2nd evaporator |
0 |
* |
10 |
||
I21 | Digital input polarity D2: 0=activates on closing, 1=activates on opening 0 0 1 contact | |||||
I30 |
D3/S5 input configuration: 0=deactivated, 1=door contact, 2=external alarm, 3=severe external alarm, 4=change SP, 5=remote defrost,
6=defrost lockout, 7=remote activation of Stand-by mode, 8=rroduct temper- ature, 9=superheating temperature (Sh) |
0 |
9 |
9 |
||
I31 | Digital input polarity D3: 0=activates on closing, 1=activates on opening 0 0 1 contact |
Inputs and outputs
Level 1 | Level 2 | |||||
Description | Values | Min. | Def. | Max. | ||
InO | I60 | Pressure units: 0=bar, 1=Psi | 0 | 0 | 1 | |
I61 | Pressure sensor type (S6): 0=deactivated, 1=4-20 mA, 2=0-5 V, 3=0.5-4.5 V, 0 3 5
4=0-10 V, 5=1-5 V |
|||||
I62 | Minimum pressure sensor value (4 mA, 0 V, 0.5 V, 1 V) | -1 | -1 | I63 | ||
I63 | Maximum pressure sensor value (20 mA, 5 V, 4.5 V, 10 V) I62 9 60 | |||||
I64 | Pressure sensor calibration (S2) | -10 | 0 | 10 | ||
o00 | AUX 1 relay configuration: 0=deactivated, 1=compressor/crankcase resistance, 0 * 5 2=light, 3=virtual control, 4= Alarm, 5=resistor. door frame | |||||
o10 |
AUX 2 relay configuration: 0=deactivated, 1=alarm, 2=light, 3=virtual control, 4=defrost 2nd evaporator, 5=resistor. door frame, 6=equal solenoid status, 7=equal device status |
0 |
2 |
7 |
||
o20 | AUX 3 relay configuration: 0=deactivated, 1=alarm, 2=light, 3=external AO 0 0 5 controller ON/OFF, 4=defrost 2nd evaporator, 5=resistor. door frame | |||||
o30 | Analog output type (AO): 0=4-20 mA, 1=0-10 V | 0 | 0 | 1 | ||
EP | Output to level 1 |
HACCP alarm
Level 1 | Level 2 | |||||
Description | Values | Min. | Def. | Max. | ||
HCP | h1 | HACCP alarm maximum temperature ºC/ºF -50 99.0 99.0 | ||||
h2 | Maximum permitted time for activation of the HACCP alarm (0=HACCP alarm deactivated) | h. | 0 | 0 | 255 | |
EP | Output to level 1 |
Information (read-only)
Technical specifications
- Power supply……………………………………………………………………………………………………… 100 – 240 V ~ 50/60 Hz
- Maximum input power in the operation…………………………………………………………………………………………..8.1 VA
- Maximum nominal current……………………………………………………………………………………………………………….15 A DEF relay – SPDT – 20 A NO (EN 60730-1: 15 (15) A 250 V~ )
- NC…………………………………………………… (EN 60730-1: 15 (13) A 250 V~)
- FAN relay – SPST – 16 A ……………………………………………………………………………… (EN 60730-1: 12 (9) A 250 V~)
- Relay COOL – SPST – SSR 2 A ………………………………………………………………………………. Vmax: 275 V~, Imax: 2 A
- AUX relay 1 – SPDT – 20 A NO…………………………………………………… (EN 60730-1: 15 (15) A 250 V~)
- NC…………………………………………………… (EN 60730-1: 15 (13) A 250 V~)
- AUX relay 2 – SPDT – 16 A NO…………………………………………………….. (EN 60730-1: 12 (9) A 250 V~)
- NC…………………………………………………….. (EN 60730-1: 10 (8) A 250 V~)
- AUX relay 3 – SPST – 16 A NO…………………………………………………….. (EN 60730-1: 12 (9) A 250 V~)
- No. of relay operations………………………………………………………………………………EN 60730-1:100,000 operations
- Temperature range of probes (NTC/Pt1000)…………………………………………………………………….-50.0 ºC to 99.9 ºC
- Resolution, adjustment, and differential……………………………………………………………………………………………. 0.1ºC
- Thermometric accuracy…………………………………………………………………………………………………………………..±1ºC
- Tolerance of the (NTC/Pt1000) probes at 25°C………………………………………………………………………………..±0.4ºC
- Inputs S1 to S4 …………………………………………………………………………….. NTC probe AKO-14901 or probe Pt1000
- Inputs S5……………………………………………………………………….. NTC probe AKO-14950 / 14950-8 o probe Pt1000
- Working ambient temperature …………………………………………………………………………………………….-10ºC to 50ºC
- Ambient storage temperature………………………………………………………………………………………………-30ºC to 60ºC
- Protection degree ………………………………………………………………………………………………………………………… IP 65
- Installation category………………………………………………………………………………………………… II as per EN 60730-1
- Degree of pollution…………………………………………………………………………………………………. II as per EN 60730-1
- Grade as per UNE-EN 60730-1: Built-in control device, with Type 1. B automatic action operation feature, for use in clean situations, logical support (software) class A, and continuous operation.
- Degree of pollution 2.
- Double isolation between power supply, secondary circuit, and relay output.
- Accessible parts pressure ball test temperature…………………………………………………………………………………. 75 °C
- Parts positioning active elements………………………………………………………………………………………………….. 125 ºC
- Radio interference suppression test current…………………………………………………………………………………….270 mA
- Voltage and current delayed by the EMC tests:…………………………………………………………………………207 V, 17 mA
- Type of mounting………………………………………………………………………………………………………………. Fixed interior
- MODBUS address…………………………………………………………………………………………………… indicated on the label
- Dimensions………………………………………………………………………………….. 290mm (W) x 141mm (H) x 84.4mm (D) Internal buzzer
For further information, refer to the user manual available at: https://help.ako.com/assets/uploads/351652662.pdf
CONTACT
- AKO ELECTROMECÁNICA , S.A.
- Avda. Roquetes, 30-38
- 08812 Sant Pere de Ribes.
- Barcelona Spain
- www.ako.com
We reserve the right to supply materials that might vary slightly from those described in our Technical Sheets. Updated information is available on our website.
Documents / Resources
![]() |
AKO 16526 V2 Advanced Temperature Controller [pdf] Instruction Manual 16526 V2 Advanced Temperature Controller, 16526 V2, Advanced Temperature Controller, Temperature Controller, Controller |