AKO-LOGO

AKO 16526 V2 Advanced Temperature Controller

AKO-16526-V2-Advanced-Temperature-Controller-PRODUCT

Product Usage Instructions

  • Make sure to follow all safety instructions provided in the manual.
  • Regular maintenance is essential for the proper functioning of the product. Refer to the maintenance section in the manual for detailed instructions.
  • Proper connection of the product is crucial for its performance.
  • Follow the connection guidelines provided in the manual.
  • Use the keyboard to input commands and navigate through the settings.
  • Ensure sensors are properly connected and functioning to monitor temperature accurately.
  • Follow the assistant’s instructions displayed on the screen to set up and configure the product.
  • Operate the product according to the specified settings and modes mentioned in the manual.
  • Pay attention to messages displayed on the screen for important notifications and alerts.

FAQ

  • Q: How do I silence an ongoing alarm?
    • A: To silence an ongoing alarm, follow the steps outlined in the manual, usually involving pressing a specific key or combination of keys.
  • Q: How do I set the type of refrigerant gas used?
    • A: Navigate to the relevant menu on the display using the arrow keys and select the appropriate gas type from the available options. Confirm your selection by pressing the SET key.
  • Q: What should I do if there is a final defrost alert?
    • A: When you receive a final defrost alert, make sure to check and address any issues related to exceeding the defined defrost time as per the settings.

Warnings

  • If the device is used without adhering to the manufacturer’s instructions, the device safety require-ments could be compromised. Only sensors supplied by AKO must be used for the unit to operate correctly.
  • From -40°C to +20°C, if the NTC sensor is extended to 1000m with at least a 0.5mm2 cable, the maximum deviation will be 0.25°C (cable for sensor extension ref. AKO-15586 / AKO-15586H. Earth the cable mesh at one end only).
  • Pt1000 sensors can be extended up to 25m using the AKO-15586 / AKO-15586H sensor extension cable..
  • The product should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the value indicated in the technical data.
  • For the reading to be correct, the sensor should be used in a place without heat influences apart from the tem-perature you want to measure or control.
  • The IP65 protection degree is only valid with the protection cover closed.
  • The IP65 protection degree is only valid if the cables enter the device using a tube for electric conductions + gland with IP65 or above. The gland should be the right size for the diameter of the tube used.
  • Do not spray the unit directly with high-pressure hoses, as this could damage it.

IMPORTANT

  • The AUXILIARY relays are programmable, and their operation depends on the configuration.
  • The function of the digital inputs depends on the configuration.
  • The recommended currents and powers are the maximum working currents and powers.

Maintenance

  • Clean the surface of the unit with a soft cloth, water and soap.
  • Do not use abrasive detergents, petrol, alcohol or solvents, as this might damage the unit.

Wiring

  • Always disconnect the power supply to do the wiring.
  • The sensors and their cables must NEVER be installed in a conduit together with power, control or power supply cables.
  • For disconnection, the power supply circuit must be equipped with at least a 2 A, 230 V switch, located near the device. The power supply cable shall be of the H05VV-F or NYM 1×16/3 type. The section to be used will depend on current local regulations, but should never be less than 1.5mm2.
  • Cables for relay or contactor outputs should have a section of 2.5mm2, allow working temperatures equal to or over 70ºC, and be installed with as little bending as possible.
  • The 120/230 V~ wiring area must be kept clear of any other external element.
  • The wiring setup depends on the options selected in the set-up wizard and on the input and output configurations (See page 31).
  • Check the enclosed schematic and the defined configuration before wiring.
  • The parameter St (Type of connected probes) affects all probe inputs. Therefore all connected probes (NTC or Pt1000) must be the same.

 

 

Description

  • Temperature controller with output for electronic expansion valve regulation and evaporator fan speed control.
  • In addition to regulating the cooling of the cold room, the controller can be configured to control superheating and regulate the speed of the evaporator fans using an inverter or electronic fans.

AKO-16526-V2-Advanced-Temperature-Controller-FIG-1AKO-16526-V2-Advanced-Temperature-Controller-FIG-2

Keypad

  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-3Press and hold for 3 seconds to activate/deactivate the Stand-By mode. In this mode, regulation is paused and the m iconAKO-16526-V2-Advanced-Temperature-Controller-FIG-8 is displayed.
  • In the programming menu, this key exits the parameter without saving changes and returns to the previous level or exits programming.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-4Pressing once without holding displays the temperature of sensor S2 for 10 seconds (if it is enabled). Pressing it for 3 seconds starts/stops the defrost.
  • In the programming menu, it allows you to scroll through the different levels, or when setting a parameter to change its value.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-5Pressing it for 3 seconds activates/deactivates the continuous cycle mode.
  • In the programming menu, it allows you to scroll through the different levels, or when setting a parameter to change its value.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-6Pressing once without holding activates/deactivates the cold room light.
  • Pressing it for 3 seconds accesses the condensed programming menu.
  • Pressing it for 6 seconds accesses the expanded programming menu.
  • In the programming menu, it accesses the level shown on the display or, during the setting of a parameter, accepts the new value.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-7Pressing it once without holding it down displays the current effective value of the temperature Set Point in the upper display and the superheating set point in the lower display, taking into considera-tion temporary changes due to other parameters.
  • When an alarm is in progress, pressing once without holding mutes the acoustic alarm.
  • Pressing for 3 seconds accesses the temperature Set Point setting.

STAND-BY

  • If the regulation cannot be stopped immediately due to its configuration, a controlled stop process starts and the m icon flashes. To stop the controlled stop process and force Stand-by, press the Stand-by key again for 3 seconds.

Probes

AKO-16526-V2-Advanced-Temperature-Controller-FIG-9

Wizard
The first time the unit receives the power supply, it will enter into Wizard mode.
The display will show the messageAKO-16526-V2-Advanced-Temperature-Controller-fig-40 flashing atAKO-16526-V2-Advanced-Temperature-Controller-fig-41.AKO-16526-V2-Advanced-Temperature-Controller-FIG-10

The buttonsAKO-16526-V2-Advanced-Temperature-Controller-FIG-11 change the value, the SET button accepts the value and moves on to the next step.

Step 1
Select the most suitable InI option based on the type of installation to be carried out and press SET.
The available options will be shown in the following table:

 

InI

Type of installation Parameters
Control of the compressor Pump Down Defrost Evap. Fans Pd o00 I00 I10 I11 I20 I21 d1 D7 F3
0 Demo mode: it displays the temperature but does not regulate the temperature
1 No No Electric Yes 0 0 2 0 0 0 0 20 0 0
2 Yes Yes Electric Yes 1 1 2 7 1 0 0 20 0 0
3 Yes No Electric Yes 0 1 2 0 0 0 0 20 0 0
4 No No Air Yes 0 0 1 0 0 0 0 20 1 1
5 Yes Yes Air Yes 1 1 1 7 1 0 0 20 1 1
6 Yes No Air Yes 0 1 1 0 0 0 0 20 1 1
7 Yes Yes Hot gas Yes 1 1 2 7 1 7 1 5 2 0
8 Yes No Hot gas Yes 0 1 2 0 0 7 1 5 2 0

If options 2, 5 or 7 are chosen, check the configuration of parameter I11 according to the pressure switch type used.

Step 2

  • Define the type of refrigerant gas used.

AKO-16526-V2-Advanced-Temperature-Controller-FIG-12

AKO-16526-V2-Advanced-Temperature-Controller-fig-42

Step 3*:

  • Define the minimum value of the pressure sensor (I62) (value at 4 mA, 0 V, 0.5 V or 1 V according to I61).

Step 4*:

  • Define the maximum value of the pressure sensor (I63) (value at 20 mA, 5 V, 4.5 V or 10 V according to I61).
  • *Steps only visible if u02=7

Step 5:

  • Select the temperature set point.AKO-16526-V2-Advanced-Temperature-Controller-FIG-13

Step 9:

  • Set all other parameters to default.
  • dFP=0 No, the other parameters do not need to be changed
  • dFP=1 Yes, set all other parameters to their default values
  • This option only appears if this is not the first time the set-up wizard has been run.
  • The initial configuration is now complete, and the device will start to regulate the temperature.

The configuration wizard will not reactivate. To reactivate it, activate the standby mode (by pressing the m key for 3 seconds) and wait until the unit completely halts regulation (the m indicator will light up permanently) and press theAKO-16526-V2-Advanced-Temperature-Controller-FIG-14 SET buttons in this order in sequence, not at the same time.
If the Pump Down function is active, there may be a delay between the initiation of the Stand-by function and the moment the controller stops.

Operation

Messages

  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-15Pump down malfunction error (Stop). The time configured in parameter C20 has been exceeded. Only displayed on screen.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-16Pump down malfunction error (Start). The time configured in parameter C19 has been exceeded. Only displayed on screen.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-17Sensor 1, 2, 3, 4, 5, or 6 is faulty (open circuit, crossed circuit, or value outside sensor limits). Activates the alarm relay and the audible alarm.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-18Open door alarm. Only if the door stays open for a longer time than defined in parameter A12. Activates the alarm relay and the audible alarm.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-19Maximum temperature in control sensor alarm. The temperature value programmed in A1 has been reached. Activates the alarm relay and the audible alarm.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-20Minimum temperature in control sensor alarm. The temperature value programmed in A2 has been reached. Activates the alarm relay and the audible alarm.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-21External alarm activated (by digital input). Activates the alarm relay and the audible alarm.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-22Severe external alarm activated (by digital input). Activates the alarm relay and the audible alarm.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-23Defrost the time-out alert. The time set in d1 has been exceeded.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-24HACCP alarm. The temperature has reached the value of parameter h1 for a longer period than established in h2. Activates the alarm relay and the audible alarm.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-25HACCP alarm due to a fault in the electric supply. The temperature set in h1 has been reached following a fault in the electric supply. Activates the alarm relay and the audible alarm.
  • AKO-16526-V2-Advanced-Temperature-Controller-fig-44Minimum superheat alarm. The value set in A20 has been reached. Activates the alarm relay and the audible alarm.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-26Minimum superheat alert. The value defined in A23 has been reached. Only displayed on screen.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-27Maximum evaporating pressure alarm. The value defined in A26 has been reached. Activate the alarm relay and the audible alarm.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-28Minimum evaporating alarm. The value defined in A29 has been reached. Activates the alarm relay and the audible alarm.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-29Indicates that a defrost is being performed. Only displayed on screen.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-30Password request. See parameters b10 and PAS. Only displayed on screen.
  • AKO-16526-V2-Advanced-Temperature-Controller-FIG-31Shown sequentially with the temperature: the controller is in demo mode, and the configuration has not been made.

Configuration

Condensed programming menu

  • This allows for the most-used parameters to be quickly configured. Press the SET key for 3 seconds to access it.

AKO-16526-V2-Advanced-Temperature-Controller-FIG-32

Parameters

Level 2  
Description Values Min. Def. Max.
SP Temperature setting (Set Point) ºC/ºF -50 0.0 99
C1 Sensor 1 differential (Hysteresis) ºC/ºF 0.1 2.0 20.0
d0 Defrost frequency (time between 2 starts) h. 0 6 96
d1 Maximum defrost duration (0=defrost deactivated) min. 0 * 255
d4 Final defrost temperature (by the sensor) (If I00 ¹ 1) ºC/ºF -50 8.0 50
SH Superheating set point ºK 0.1 8 40
F3 Status of the fans during the defrost 0=stopped; 1=running   0 * 1
A1 Alarm for maximum in sensor 1 (it must be higher than the SP) ºC/ºF A2 99.0 99.0
A2 Alarm for minimum in sensor 1 (it must be lower than the SP) ºC/ºF -50 -50 A1

* According to the set-up wizard.

Extended programming menu
Use the extended programming menu to configure all of the unit’s parameters to adapt it to your installation requirements. Press the SET key for 6 seconds to access it.

IMPORTANT: if the password function has been configured as a keypad lock (b10=2), or as an access to parameters block (b10=1), you will be requested to enter the password programmed in PAS when attempting to access either of the two functions. If the entered password is not correct, the unit will go back to showing the temperature.
IMPORTANT: certain parameters or menus may not be visible depending on the configuration of the other parameters and the options chosen during set-up.

Extended programming menu

AKO-16526-V2-Advanced-Temperature-Controller-FIG-33

Parameters
Regulation and control

AKO-16526-V2-Advanced-Temperature-Controller-fig-45

Defrost

Level 1 Level 2  
Description Values Min. Def. Max.
dEF d0 Defrost frequency (time between 2 starts) h. 0 6 96
d1 Maximum defrost duration (0=defrost deactivated) min. 0 * 255
  Type of message during the defrost: 0=sign of the real temperature; 1=sign of        
d2 the temperature at the start of the defrost;   0 2 2
  2=sample of the dEF message        
d3 Maximum message duration min. 0 5 255
(time added at the end of the defrost process)
d4 Final defrost temperature (by the sensor) (If I00¹1) ºC/ºF -50 8.0 50
d5 Defrost on connecting the unit: 0=NO, first defrost according to d0;   0 0 1
1=YES, first defrost according to d6
d6 Delay of the defrost start on connecting the unit min. 0 0 255
d7 Type of defrost: 0=resistors; 1=air/fans   0 * 2
2=hot gas
d8 Time calculation between defrost periods:   0 0 1
0=total real-time 1=sum of COOL time connected        
d9 Drip time when a defrost finishes min. 0 1 255
(stop COOL and fans)
EP Output to level 1

Evaporator fans

Level 1 Level 2  
Description Values Min. Def. Max.
FAn F0 Fans stop temperature ºC/ºF.  -50  45  50
F1 Sensor 2 differential if fans are stopped ºC/ºF 0.1 2.0 20.0
F2 Stop fans when the compressor stops 0=no 1=yes                                                 0      0      1
F3 Status of the fans during the defrost 0=stopped; 1=running   0 * 1
F4 Start-up delay after defrost (if F3=0)                                                         min.     0      2     99 Only actuates if higher than d9
F10 Fan control type 0=ON/OFF 1=frequency inverter   0 0 1
EP Output to level 1

Expansion valve

Level 1 Level 2  
Description Values Min. Def. Max.
EEV u00 Valve type: 0=solenoid + EV thermostat 1= PWM-type EEV                                      0      1      2 2=Stepper-type EEV
SH Superheating set point K 0.1 8 40
 

u02

Refrigerant gas type: 0= R-404A, 1= R-134A, 2= R-407A, 3= R-407F, 4= R-410A,

5= R-450A, 6= R-513A, 7= R-744, 8= R-449A, 9= R-290, 10= R-32, 11= R-448A,        0      *      17

12=R1234ze, 13=R23, 14=R717, 15=R407C, 16=R1234yf, 17=R22, 18=R454C,

19=R455A, 20=R507A, 21=R515B, 22=R452A, 23=R452B, 24=R454A

u03 PWM cycle time s. 2 6 10
u04 Proportional constant value (P)                                                                           1     10  100
u05 Integral constant value (I)   0 10 100
u06 Derivative constant value (D)                                                                              0      0  100
u07 Opening value of the electronic expansion valve when cooling is activated % u13 50 u12
u08 Duration of valve opening on cooling demand                                               s.       2      5  240
u09 Valve opening value with sensor error S5 or S6: 0=fixed opening according to u10; 1=average opening over the last 24 hours   0 0 1
u10 Valve opening value with sensor error S5 or S6 (if u09=0)                                %      u13  0  u12
u11 Manual valve opening value (-1=disabled), (cycles acc. to u03) Requires safety code. See user manual. % -1 -1 100
u12 Maximum valve opening value                                                                  %      u13 100 100
u13 Minimum valve opening value % 0 0 u12
u14 Valve opening value after defrost (0=disabled), (duration according to u15)         %       0/     0  u12

u13

u15 Duration of valve opening after defrosting s 0 0 240
u16 Valve opening in case of LOP error (0=valve closed)                                     %       0/     0 u12 u13
EP Output to level 1

Alarms

Level 1 Level 2  
Description Values Min. Def. Max.
AL A0 Configuration of the temperature alarms 0=relative to SP 1=absolute                         0      1      1
A1 Alarm for maximum in sensor 1 (it must be higher than the SP) ºC/ºF A2 99.0 99.0
A2 Alarm for minimum in sensor 1 (it must be lower than the SP)                        ºC/ºF  -50  -50  A1
A3 Delay of temperature alarms in the start-up min. 0 0 120
A4 Delay of temperature alarms from the end of a defrost                                  min.     0      0     99
A5 Delay of temperature alarms from when the A1 or A2 value is reached min. 0 30 99
A6 Delay of external alarm/severe external alarm on receiving digital input signal    min.     0      0 120 (I10 or I20=2 or 3)
A7 External alarm deactivation delay/severe external alarm on the disappearance of the signal at digital input (I10 or I20=2 or 3) min. 0 0 120
A8 Show warning if the defrost ends for maximum time 0=no 1=yes                               0      0      1
A9 Polarity relay alarm 0=relay ON in alarm (OFF without alarm); 1=relay OFF in alarm (ON without alarm)   0 0 1
A10 The differential of temperature alarms (A1 and A2)                                           ºC/ºF  0.1  1.0 20.0
A12 Delay of open door alarm (if I10, I20 or I30=1) min. 0 10 120
A20 Minimum superheating value for LSH alarm                                                  K        0      2     SH
A21 LSH alarm activation delay sec. 0 30 240
A22 LSH alarm hysteresis                                                                                 K      0.1     2     Sh-

A20

A23 Maximum overheating value for LSH alert K sh 40 40
A24 Delayed activation of the HSH warning                                                        s        0     30  240
A25 HSH alarm deactivation hysteresis K 0.1 2 A23-

sh

A26 Maximum evaporating pressure (MOP)                                                      bar      0     60  60
A27 MOP alarm activation delay (delay time for activating alarm after the threshold has been exceeded) sec. 0 30 240
A28 MOP alarm deactivation hysteresis (when the pressure drops below the           bar     0.1     1     60 MOP-hysteresis level the alarm is deactivated)
A29 Minimum evaporating pressure (LOP) bar -1 0 8
A30 LOP alarm activation delay (delay time for activating alarm after the threshold has  sec.     0     30 240 been exceeded)
A31 LOP alarm deactivation hysteresis (when the pressure exceeds the LOP-hysteresis level the alarm is deactivated) bar 0.1 1 8
EP Output to level 1

Basic configuration

Level 1 Level 2  
Description Values Min. Def. Max.
bcn b00 Delay of all functions on receiving power supply                                          min.     0      0  255
b01 Cold room light timing min. 0 0 999
b10 Password function 0=inactive                                                                             0      0      2

1=parameter access lock 2=keypad lock

PAS Password   0 0 99
b20 MODBUS address                                                                                            1      1  247
b21 Communication speed: 0=9600 bps 1=19200 bps

2=38400 bps 3=57600 bps

bps 0 0 3
b22 Audible alarm enabled 0=no 1=yes                                                                      0      1      1
 

b23

Lower display function: 1=sensor S2, 2=sensor S3, 3=sensor S4, 4=sensor S5, 5=superheating, 6=pressure sensor, 7=% EEV, 8=% eFAN, 9=carousel, 10=off    

1

 

*

 

10

Unt Working units 0=ºC 1=ºF                                                                                  0      0      1
EP Output to level 1

Inputs and outputs

Level 1 Level 2  
Description Values Min. Def. Max.
InO St Type of probes connected: 0= NTC, 1= Pt1000   0 0 1
I00 Probes connected: 1=sensor 1 (cold room), 2=sensor 1 (cold room) + sensor                1      2      2

2 (evaporator)

 

I10

D1/S3 input configuration: 0=deactivated, 1=door contact, 2=external alarm, 3=severe external alarm, 4=change SP, 5=remote defrost,

6=defrost lockout, 7=low pressure switch, 8=remote activation in Stand-by mode, 9=product temperature

   

0

 

*

 

9

I11 Digital input polarity D1: 0=activates on closing, 1=activates on opening                      0      0      1 contact
 

I20

D2/S4 input configuration: 0=deactivated, 1=door contact, 2=external alarm, 3=severe external alarm, 4=change SP, 5=remote defrost,

6=defrost lockout, 7=high pressure switch for hot gas, 8=remote activation of Stand-by mode, 9=product temperature, 10=defrost 2nd evaporator

   

0

 

*

 

10

I21 Digital input polarity D2: 0=activates on closing, 1=activates on opening                      0      0      1 contact
 

I30

D3/S5 input configuration: 0=deactivated, 1=door contact, 2=external alarm, 3=severe external alarm, 4=change SP, 5=remote defrost,

6=defrost lockout, 7=remote activation of Stand-by mode, 8=rroduct temper- ature, 9=superheating temperature (Sh)

   

0

 

9

 

9

I31 Digital input polarity D3: 0=activates on closing, 1=activates on opening                      0      0      1 contact

Inputs and outputs

Level 1 Level 2  
Description Values Min. Def. Max.
InO I60 Pressure units: 0=bar, 1=Psi   0 0 1
I61 Pressure sensor type (S6): 0=deactivated, 1=4-20 mA, 2=0-5 V, 3=0.5-4.5 V,               0      3      5

4=0-10 V, 5=1-5 V

I62 Minimum pressure sensor value (4 mA, 0 V, 0.5 V, 1 V)   -1 -1 I63
I63 Maximum pressure sensor value (20 mA, 5 V, 4.5 V, 10 V)                                        I62     9     60
I64 Pressure sensor calibration (S2)   -10 0 10
o00 AUX 1 relay configuration: 0=deactivated, 1=compressor/crankcase resistance,        0      *       5 2=light, 3=virtual control, 4= Alarm, 5=resistor. door frame
 

o10

AUX 2 relay configuration: 0=deactivated, 1=alarm, 2=light, 3=virtual control, 4=defrost 2nd evaporator, 5=resistor. door frame, 6=equal solenoid status, 7=equal device status    

0

 

2

 

7

o20 AUX 3 relay configuration: 0=deactivated, 1=alarm, 2=light, 3=external AO                   0      0      5 controller ON/OFF, 4=defrost 2nd evaporator, 5=resistor. door frame
o30 Analog output type (AO): 0=4-20 mA, 1=0-10 V   0 0 1
EP Output to level 1

HACCP alarm

Level 1 Level 2  
Description Values Min. Def. Max.
HCP h1 HACCP alarm maximum temperature                                                            ºC/ºF  -50 99.0 99.0
h2 Maximum permitted time for activation of the HACCP alarm (0=HACCP alarm deactivated) h. 0 0 255
EP Output to level 1

Information (read-only)

AKO-16526-V2-Advanced-Temperature-Controller-fig-46

Technical specifications

  • Power supply……………………………………………………………………………………………………… 100 – 240 V ~ 50/60 Hz
  • Maximum input power in the operation…………………………………………………………………………………………..8.1 VA
  • Maximum nominal current……………………………………………………………………………………………………………….15 A DEF relay – SPDT – 20 A NO (EN 60730-1: 15 (15) A 250 V~ )
  • NC…………………………………………………… (EN 60730-1: 15 (13) A 250 V~)
  • FAN relay – SPST – 16 A ……………………………………………………………………………… (EN 60730-1: 12 (9) A 250 V~)
  • Relay COOL – SPST – SSR 2 A ………………………………………………………………………………. Vmax: 275 V~, Imax: 2 A
  • AUX relay 1 – SPDT – 20 A NO…………………………………………………… (EN 60730-1: 15 (15) A 250 V~)
  • NC…………………………………………………… (EN 60730-1: 15 (13) A 250 V~)
  • AUX relay 2 – SPDT – 16 A NO…………………………………………………….. (EN 60730-1: 12 (9) A 250 V~)
  • NC…………………………………………………….. (EN 60730-1: 10 (8) A 250 V~)
  • AUX relay 3 – SPST – 16 A NO…………………………………………………….. (EN 60730-1: 12 (9) A 250 V~)
  • No. of relay operations………………………………………………………………………………EN 60730-1:100,000 operations
  • Temperature range of probes (NTC/Pt1000)…………………………………………………………………….-50.0 ºC to 99.9 ºC
  • Resolution, adjustment, and differential……………………………………………………………………………………………. 0.1ºC
  • Thermometric accuracy…………………………………………………………………………………………………………………..±1ºC
  • Tolerance of the (NTC/Pt1000) probes at 25°C………………………………………………………………………………..±0.4ºC
  • Inputs S1 to S4 …………………………………………………………………………….. NTC probe AKO-14901 or probe Pt1000
  • Inputs S5……………………………………………………………………….. NTC probe AKO-14950 / 14950-8 o probe Pt1000
  • Working ambient temperature …………………………………………………………………………………………….-10ºC to 50ºC
  • Ambient storage temperature………………………………………………………………………………………………-30ºC to 60ºC
  • Protection degree ………………………………………………………………………………………………………………………… IP 65
  • Installation category………………………………………………………………………………………………… II as per EN 60730-1
  • Degree of pollution…………………………………………………………………………………………………. II as per EN 60730-1
  • Grade as per UNE-EN 60730-1: Built-in control device, with Type 1. B automatic action operation feature, for use in clean situations, logical support (software) class A, and continuous operation.
  • Degree of pollution 2.
  • Double isolation between power supply, secondary circuit, and relay output.
  • Accessible parts pressure ball test temperature…………………………………………………………………………………. 75 °C
  • Parts positioning active elements………………………………………………………………………………………………….. 125 ºC
  • Radio interference suppression test current…………………………………………………………………………………….270 mA
  • Voltage and current delayed by the EMC tests:…………………………………………………………………………207 V, 17 mA
  • Type of mounting………………………………………………………………………………………………………………. Fixed interior
  • MODBUS address…………………………………………………………………………………………………… indicated on the label
  • Dimensions………………………………………………………………………………….. 290mm (W) x 141mm (H) x 84.4mm (D) Internal buzzer

For further information, refer to the user manual available at: https://help.ako.com/assets/uploads/351652662.pdf

CONTACT

  • AKO ELECTROMECÁNICA , S.A.
  • Avda. Roquetes, 30-38
  • 08812 Sant Pere de Ribes.
  • Barcelona Spain
  • www.ako.com

We reserve the right to supply materials that might vary slightly from those described in our Technical Sheets. Updated information is available on our website.

Documents / Resources

AKO 16526 V2 Advanced Temperature Controller [pdf] Instruction Manual
16526 V2 Advanced Temperature Controller, 16526 V2, Advanced Temperature Controller, Temperature Controller, Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *