TREND IQ5-IO Controller and I-O Modules

Specifications

  • Product Name: IQ5, IQ5-IO Controller & I/O Modules
  • Model: IQ5, IQ5-IO
  • Manufacturer: Trend Controls

Before Starting Configuration

Ensure you have the necessary equipment installed:

  • IQ5, I/O Modules & Adapters
  • Additional Documentation Required
  • Ethernet Network prepared with DHCP and DNS servers

Configuration
Follow these steps to configure the IQ5, IQ5-IO:

Isolate All Power
Make sure all power sources areisolated before proceeding.

Open Panel / Enclosure

Exercise caution when opening the panel to avoid exposing yourself to dangerous voltages.

Peel Off Serial Label(s) and Retain
Remove serial labels as required while retaining them for future reference.

Disconnect All I/O from I/O Modules
Disconnect all I/O connections from the modules, except for Power, Ethernet, RS-485, T1L bus, IQ3/4 IO bus, USB, and current loop.

FAQs

Q: What should I do if the equipment is used in a manner not specified by the instructions?
A: Using the equipment in a manner not specified may impair theprotection provided. It is recommended to always follow the provided instructions or consult trained service personnel.

“`

InstallationInstructions-Configuring
IQ5, IQ5-IO
Controller & I/O Modules

Important: Retain these instructions

These instructions shall be used by trained service personnel only. If the equipment is used in a manner not
specified by these instructions, the protection provided by the equipmentmaybeimpaired.


IQSETManual(TE200147)

IQ500InstallationInstructions-Mounting(TG201482) IQ528InstallationInstructions-Mounting(TG201513) IQ5-IOInstallationInstructions-Mounting(TG201484) IQ4/IO/..InstallationInstructions-Mounting(TG201342) XCITE/IO/..InstallationInstructions-Mounting(TG200627) IQ5-LAN-ADPT Current Loop LAN Adapter Installation Instructions-Mounting(TG201511)

Additional Documentation Required
IQSETManual(TE200147) IPToolManual(TE200638) IQToolMonitorAppletManual(TE201298) IQToolAddresserAppletManual(TE201299) IQ5ConfigurationManual(TE201486)

Note: PDF copies are included with IQSET installation in the following folder: C:…Trend Control SystemsDocumentation

Prepare the Ethernet Network(s)
Install DHCP Server If the IP address settings (IP address, subnet mask, default router,WINSandDNSservers’addresses)aretobesupplied by a DHCP server, ensure one is installed on the Ethernet segmenttowhichIQ5isconnected.

Install DNS Server Ifemailalarmsaretobesent,andtheemailserveraddress isidentifiedbyinternetdomainname,aDNSservermustbe installed.
Note: IQ5 does not support WINS. If hostnames are to be used, then a DNS server is recommended. For security the use of LLMNR protocol is not advised.

2 CONFIGURATION

1

Isolate All Power

IsolateallpowerincludingadditionalsuppliesI/O

devicesandCurrentLoopLANAdapters.

WARNING Connecting leads may be connected topowersupplies.Isolatebeforetouching.

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

1

IQ5, IQ5-IO

2 CONFIGURATION (continued)

2

Open Panel / Enclosure

InstallationInstructions-Configuring
WARNING Opening the panel may expose dangerousvoltages.

3

PeelOffSerialLabel(s)andRetain(leavefrontpanelprotectivefilminplace)

IQ5

IQ5-IO Modules

4

Disconnect All I/O from I/O Modules

LeaveIQ5Power,Ethernet,RS-485,T1Lbus,IQ3/4IObus, USBandcurrentloopconnected(whereappropriate).

WARNING Connecting leads may be connected topowersupplies.Isolatebeforetouching.

Removeterminalcovers

Unplugconnectors

Refitterminalcovers

2

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

InstallationInstructions-Configuring

2 CONFIGURATION (continued)

5

Set RS-485 Terminator Switches (ifRS-485networksareconnected)

IQ5, IQ5-IO

123
COM – +
RS485 n ISOLATED
Terminatorincircuit

123
COM – +
RS485 n ISOLATED
Terminatoroutofcircuit

6

ConfigureXCITE/IOModules(wherefitted)

XCITE/IO/..InstallationInstructions-Configuring(TG200627) Section 2 Only

7

ConnectEngineeringPC/Laptop(withIQSETinstalled)

Note: On IQ500 the Isolated port is disabled by default an cannot be used for the initial addressing configuration.

Either:viaEthernetHub/Switch

Or:usingdirectconnection

IQ500only StandardEthernetcable (Cat5etwistedpair) max100m(109yds)
EthernetNetwork
Hub/Switch

IQ500only StandardEthernetcable (Cat5etwistedpair) max100m(109yds)
Note: A connection via the USB Local Engineering Port cannot be used at this point.

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

3

IQ5, IQ5-IO

InstallationInstructions-Configuring

2 CONFIGURATION (continued)

8

Switch On Power to IQ5 (includinganyadditionalPSUs)

9

Wait for Controller to Boot Up

30s

45s

Gotostep10

10 Check IQ5 Status Indicator

Expected indications ControllerisrunningOK. Proceedtostep11.
OneormoremodulesontheT1Lbusor IQ3/4 IO bus is not addressed correctly. This can be ignored at this stage – proceedtostep11.
Fault indications Normal for 30 seconds on power up or reboot. If displayed for longer than 60 seconds the controller has encountered aproblemandhasstopped.Tryresetting the IQ5 to default settings. (see page 23). Nopower-checkinputpowersupply

4

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

InstallationInstructions-Configuring

IQ5, IQ5-IO

2 CONFIGURATION (continued)

11

ConfigureIQ5-IOHOAModules(ifrequired)
IMPORTANT:IfOfflinemodeisselectedtheIQ5-IOmodule will NOT be configurable for the controller. To change to Onlinemodeseepage26.
Note: To reconfigure after initial setup, reset the module by following the procedure in section 7 on page 24.
Note: In online mode the language of HOA IO modules is set by the controller, any language setting made here will be overridden by the controller.

SelectDisplayLanguage
English Deutsch Français
Configuration file not detected Press dial to start the offline setup

1
Auto

Select Mode Online mode
2
Configuration file not detected Press dial to start the offline setup
Offlinemode
Configuration file not detected Press dial to start the offline setup

2
Addressmodule Gotostep12
DO NOT PRESS
2
Gotosection5

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

5

IQ5, IQ5-IO

InstallationInstructions-Configuring

2 CONFIGURATION (continued)

12

CheckStatusofT1LBus(onlyifT1Ldevicesareconnected)

IQ5 IQ5-IO Modules
IQ5-LAN-ADPT

T1L

Normal operation indication Busisconnectedandworkingcorrectly.
Busisnotconnected(noT1Ldevices).
Fault indication Bus is connected but not working correctly. Check the bus wiring and that all T1L devices arepoweredON.

Normal operation indication BusisactiveonbothsidesoftheT1Ldevice

Busisactiveon Validforthelastmoduleon leftsideonly thebus.

Busisactiveon rightsideonly

For all others, check wiring onthesidethatisunlit.

Fault indication
Busisconnectedonrightsidebutnotworking correctly.CheckthebuswiringandthatallT1L devicesarepoweredON.
Bus is connected on lef t side but not working correctly.CheckthebuswiringandthatallT1L devicesarepoweredON.
No valid T1L connection (wiring error or communicateerror).Checkthebuswiring.
Bus is not connected (no T1L devices) on eitherside.

6

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

InstallationInstructions-Configuring

IQ5, IQ5-IO

2 CONFIGURATION (continued)

13

Check Ethernet Indicators (foranyconnectedports)

Normal operation indication 1000Mbpslinkdetected
100Mbpslinkdetected
10Mbpslinkdetected

IQ500only

Note: The indicator will flash when data is being transmitted or received.

14

ConnecttoIQ5usingIPTool
Note: On IQ500 the Isolated port is disabled by default an cannot be used for the initial addressing configuration.

UsingthePC/laptop(seestep7)runIQSET/IPTool

IQSETManual(TE200147) IPToolManual(TE200638)

ThenfindtheIQ5byitsMACaddress,asshownonthe seriallabel

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

7

IQ5, IQ5-IO

InstallationInstructions-Configuring

2 CONFIGURATION (continued)

15

SetupAddressingDetails(IQ5Mode)
This step describes how to set up the addressing details when the IQ5 is to operate in IQ5 mode. For details of settinguptheaddressingdetailsforCompatibilityModeseestep16.

Note:OnIQ500theIsolatedportisdisabledbydefaultancannotbeusedfortheinitialaddressingconfiguration.Oncetheinitial addressinginformationhasbeensetuptherequiredEthernetportscanbeenable/disabledandconfiguredasrequiredinthe controller’sstrategy.

WiththeIQ5selectedintheIPTooldeviceslist,checkthefollowingparametersandsetasrequired.

IMPORTANT: The Network Key, lan and node parameters MUST be set.

Parameter

Setting/Value

*IQ4Compatibility = operate in IQ5 mode Mode

NetworkMode -Networked*

=buildTrendnetworkwithotherdevices (default)
= operate in standalone mode

Further Details
For the IQ5 to operate in IQ5 mode this check box must beunchecked .
In standalone mode the IQ5 will not build a LAN or internetworkwithotherdevices.

NetworkMode -Auto-ip-DHCP*

=dynamicIPDHCP(default) =staticIPaddressing

If set to DHCP mode but no DHCP server is found, the IQ5willoperateinlink/localmodewhereitautonegotiates itsIPaddresswithotherdevicesonitsEthernetsegment.

IPAddress*, SubnetMask*, DefaultRouter* Hostname
UDP
NetworkKey

Note: It is recommended that link/local only be used on a single segment system.

IfstaticIPaddressingisselectedenterthe WINS is not supported by IQ5. If hostnames are to be

requiredvaluesintheformat:

used, then a DNS server is recommended. The use of

xxx.xxx.xxx.xxx

LLMNRprotocolisnotadvised.

Defaultis`Trend-‘plusthelastthreeoctets The hostname may comprise upper or lowercase fromtheMACaddress.Changeifrequired. charactersAtoZ,digits0to9,underscoreorhyphen,with
nospaces.

Default is 57612. If required, this can be All IQ5 controllers that are required to be part of the

changedtoavalueintherange0and65535 same Trend network must have the same udp port

(recommendedrange49152to65535).

number and the same network key. Multiple Trend

Enter a suitable key comprising at least networkscanexistonthesamephysicalnetwork,inwhich 10 alphanumeric characters (no spaces). caseeachseparateTrendnetworkwillrequireadifferent
networkkey.

Do not forget the Network Key!

HINT: For consistency, type the network key into a text editor (e.g. Notepad), then copy and paste it for each

device.

virtualCNCs*
LAN* OS*

Note: If the network is on the same Ethernet network as a legacy Trend network the two networks MUST NOT share the same UPD port.

Click Auto Number vCNCs or double-click TheIQ5hasfourvCNCs(oreightwhenlicencedasanNC

onavCNCinthevirtualCNCslistandenter device).AllvCNCsarealldisabledbydefault.Atleastone

thefollowing:

vCNCmustbeenabledtoallowasupervisor,toolorlocal

node-thevCNCaddress1,4to9,11to119 displaytomakeaconnectiontotheTrendsystem.

(0=vCNCdisabled) port-thevCNCportnumber1to32767 Note: If Use Default Port is checked the port
number will be set to 10000 plus the node
address (e.g. node 23 = port 10023).

For most systems it is recommended to have vCNCs on at least two separate devices on each LAN in order to provide continuity of communications (if one device is offline) and to provide load sharing during intensive data transferoperations(e.g.whendownloadingplotdata).

EntertherequiredlocalLANnumber: 1,4to9,11to119

IQ5 controllers are given a default device address of 20 andLANnumberof20inthefactory.

Note: This must be the same for all devices required to form a LAN.
Entertherequireddeviceaddress: 1,4to9,11to119

Identifier

Note: This must be unique on a LAN.

Enter a name that identifies the controller Toavoidpotentialconfusion,itisgenerallyrecommended

withinthesystem.

thatthisismadethesameasthehostname.

ClicktheWRITE DATAbuttontosavethenewsettings. *IndicatestheIQ5willrebootwhentheparameterissaved.

8

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

InstallationInstructions-Configuring

IQ5, IQ5-IO

2 CONFIGURATION (continued)

16

SetupAddressingDetails(CompatibilityMode)
This step describes how to setup the addressing details when the IQ5 is to operate in Compatibility Mode.For detailsofsettinguptheaddressingdetailsforIQ5Modeseestep15.

OnIQ500stheisolatedportisnotsupportedincompatibilitymode.Oncetheinitialaddressinginformationhasbeensetupthe requiredEthernetportscanbeenable/disabledandconfiguredasrequiredinthecontroller’sstrategy.WiththeIQ5selectedin theIPTooldeviceslist,checkthefollowingparametersandsetasrequired.

IMPORTANT: The lan and node parameters MUST be set.

Parameter

Setting/Value

*IQ4Compatibility =operateinCompatibilitymode Mode*

NetworkMode -Networked*

=buildTrendnetworkwithotherdevices (default)
= operate in standalone mode

Further Details
For the IQ5 to operate in Compatibility mode this check boxmustbeunchecked .
In standalone mode the IQ5 will not build a LAN or internetworkwithotherdevices.

NetworkMode -Auto-ip-DHCP*

=dynamicIPDHCP(default) =staticIPaddressing

If set to DHCP mode but no DHCP server is found, the IQ5willoperateinlink/localmodewhereitautonegotiates itsIPaddresswithotherdevicesonitsEthernetsegment.

Note: It is recommended that link/local only be used on a single segment system.

IPAddress*, SubnetMask*, DefaultRouter* Hostname
UDP
RemoteDevices

IfstaticIPaddressingisselectedenterthe requiredvaluesintheformat:

xxx.xxx.xxx.xxx

Defaultis`Trend-‘plusthelastthreeoctets The hostname may comprise upper or lowercase fromtheMACaddress.Changeifrequired. charactersAtoZ,digits0to9,underscoreorhyphen,with
nospaces.

Default is 57612. If required, this can be All IQ5 controllers that are required to be part of the

changedtoavalueintherange0and65535 same Trend network must have the same udp port

(recommendedrange49152to65535).

number. Multiple Trend networks can exist on the same

physical network, in which case each separate Trend

networkwillrequireadifferentudpport.

Enter up to 20 remote Trend devices by Ifa TrendLANistobebuiltacrossarouter(s)detailsof

clicking and entering the following for devicesoneachsubnetmustbespecifiedtoenablecross-

eachdevice:

router communications. It is recommended that at least

twodevicesfromeachsubnetarespecified.Forincreased

IP Address and Subnet Mask in the reliabilitydetailsofupto20devicesshouldbespecified.

format: xxx.xxx.xxx.xxx

IfstaticIPaddressingisbeingusedthelistshouldcontain thedeviceswiththelowestIPaddresses.

Note: If Use Hostname is checked the device can be specified by entering its hostname instead of IP Address. If using
DHCP it is advisable to use hostnames.

ThesamelistmustbecopiedtootherIQ5sonthenetwork. HINT: Ticking the check box next to the Remote Trend Devices list retains the list in IPTool, allowing it to be easily copied to other devices.

virtualCNCs*

Click Auto Number vCNCs or double-click TheIQ5hasfourvCNCs(oreightwhenlicencedasanNC

onavCNCinthevirtualCNCslistandenter device).AllvCNCsarealldisabledbydefault.Atleastone

thefollowing:

vCNCmustbeenabledtoallowasupervisor,toolorlocal

node-thevCNCaddress1,4to9,11to119 displaytomakeaconnectiontotheTrendsystem.

(0=vCNCdisabled) port-thevCNCportnumber1to32767

For most systems it is recommended to have vCNCs on at least two separate devices on each LAN in order

Note: If Use Default Port is checked the port toprovidecontinuityofcommunications(ifonedeviceis

number will be set to 10000 plus the node offline)andtoprovideloadsharingduringintensivedata

address (e.g. node 23 = port 10023).

transferoperations(e.g.whendownloadingplotdata).

LAN*

EntertherequiredlocalLANnumber: 1,4to9,11to119

IQ5 controllers are given a default device address of 20 andLANnumberof20inthefactory.

Note: This must be the same for all devices required to form a LAN.

OS*

Entertherequireddeviceaddress:

1,4to9,11to119

Identifier

Note: This must be unique on a LAN.

Enter a name that identifies the controller Toavoidpotentialconfusion,itisgenerallyrecommended

withinthesystem.

thatthisismadethesameasthehostname.

ClicktheWRITE DATAbuttontosavethenewsettings.
*Indicates the IQ5 will reboot when the parameter is saved. If an IQ5-LAN-ADPT is connected the IQ5’s the Type 1 (IQ LAN) Network module will be enabled when the IQ5 is put into compatibility mode.

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

9

IQ5, IQ5-IO

InstallationInstructions-Configuring

2 CONFIGURATION (continued)
17 Record the Address Details of the Controller

Deviceaddress(O/S) LANnumber FixedIPAddressorHostname(ifDCHP)

STOP! It is recommended that you complete step 15 or 16, & step 17 for all IQ5
controllersintheTrendnetworkbeforeproceeding.

18

CheckLANOKIndicator(notNCModeorconnectedtocurrentloop)
Normal operation indication
LANbuiltOKwithatleastoneotherdevice.
AttemptingtobuildaLANwithother devices.Thismaytakeseveralminutes. Controller set to standalone mode and will notbuildaLANwithotherdevices.

Fault indication
If this continues to show for more than a few minutes this indicates that the controller has notfoundanyotherdevicesonthesame LAN.UseIPTooltocheckdevicesettings.

19

ConnecttotheTrendNetworkusingIQSET
Using the Engineering PC/Laptop (see step 7) run IQSET and make a connection to the Trend Network(orSite).Forexample:

IQSETManual(TE200147)

Open a new site (e.g. File > Open/New Project > Live ClickOKtwice.

Site).

In the SystemViewpanel,double-clickthesitenamein

IntheIQSETSystemViewpanelright-clickonSites and

the Sitestree:

select New Site.

SelectTrendasthenetworktypeandclickOK.

Enter a Site name and click Edit site details. The

ConnectionWizardwillappear.

SelectLaunchingTUAEditorandclickNext.TheTUA

editorwillappear.SelecttheCNCtab:

IQ5 Mode
IftheIQ5(towhichyouareconnecting)alreadyhasaSystem Accountsetup,thenyouwillnowbeaskedtologinusingthe appropriatecredentials-gotostep22onpage12.

Otherwise, you will be prompted to press the controller’s

service button to validate the connection and create system

accounts-gotostep20.

SelectTCP/IP, enter the IP Address(orhostname)ofan

IQ5andaddatleastonevalidvCNCportintheRemote Compatibility Mode

IP port list.

Youwillbepromptedtopressthecontroller’sservicebuttonto

validatetheconnectionandcreateaCNCuser-gotostep21.

Note: If using a hostname and DNS or LLMNR is not

supported on the network, add `.local’ to the hostname

and ensure that IQSET is connected to the same segment.

10

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

InstallationInstructions-Configuring

IQ5, IQ5-IO

2 CONFIGURATION (continued)

20

ValidatetheConnectiontoIQ5andCreateSystemAccounts(IQ5ModeOnly)
If you attempt connection to an IQ5 that has no systemaccountssetup,thenIQSETwilldisplay:

Press the service button specifiedtimelimit:

on the controller within the
TheLANOK indicatorwillbe flashingfastonthe required controller

Thenewsystemaccount(s)willnowbesetuponthecontroller and synchronised with all other IQ5 controllers on the same Trendnetwork,i.e.anyIQ5controllerthathas:
thesameNetworkKeyandUDPPortsetup,and nopre-existingsystemaccounts.
This will take a few seconds to complete, after which time IQSETwilldisplayaloginbox-gotostep22onpage12.
Note: To add further system accounts go to the System View in IQSET, right-click the site, select System Account Manager and follow the instructions in the IQSET Manual.

IQSETwillnowdisplayadialogueboxforyoutoenteran

IQSETManual(TE200147)

Account Name, Password and Email address for the

Adminsystemaccount.

Remember to provide the credentials of the Admin

Note: The email address is required in order to recover system account plus the Network Key to the site owner

from a forgotten password.

toenablethemtomanagethesystemaccounts.If the site

ownerdoesnothaveaccesstoIQSETyoumayneedtoadd

Click tocreatetheaccount.

another Admin system account for each system integrator

You will then be given the option to create a single workingonthesite.

Engineersystemaccount-clickYes or Noasrequired.

21

ValidatetheConnectiontoIQ5andCreateCNCUser(CompatibilityModeOnly)
If you attempt connection to an IQ5 that has no CNCusersetup,thenIQSETwilldisplay:

Press the service button specifiedtimelimit:

on the controller within the
TheLANOK indicatorwillbe flashingfastonthe required controller

IQSET will now display a dialogue box that enables the IQ5’svCNCconnectionstobeconfigured.
EntertheCNCUsermodule’snameintheNamebox. EntertheCNCUsermodule’spasswordinthePassword
box. RetypethepasswordintheRetype Passwordbox. ClickCommit.
The CNC User module will now be set up on the controller This will take a few seconds to complete, after which time IQSETwilldisplayaloginbox-gotostep22onpage12.

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

11

IQ5, IQ5-IO

InstallationInstructions-Configuring

2 CONFIGURATION (continued)

22

LogintotheTrendNetwork
IfyouattemptconnectiontoanIQ5thathassystem accounts(IQ5mode)orCNCUsers(compatibility mode)setup,thenIQSETwilldisplay:

EntertheUser Name and Password foravalidAdminor Engineersystemaccount.
ClickOK. In the SystemViewpanelclickthesitenametorefresh
thesitedetails(orright-clickandselectRefresh).

23

CreateStrategyinIQSET
CreateanIQSETprojectandcreateastrategy foreachIQ5controller.

IQSETManual(TE200147) IQ5ConfigurationManual(TE201486)

InIQSETclickFile>Open / New Project.

In the Device Details dialogue enter the controller

SelectCreate New SET ProjectandclickOK.

Address and Name,andclickOK.

EntertherequireddetailsandclickOK. In the ProjectViewpaneladdtherequiredLANsbyright-

Note: The Address should match the node(s) defined

clickingtheprojectnameandselectingInsertLan.

using IPTool in step 15.

EntertherequiredLANNumberand Label,andclickOK.

In the Address Module dialogue enter any required

Note: The LAN number should match the LAN(s) defined

settingsandclickOK.

using IPTool in step 15.

In the Sensor Typedialogueenteranyrequiredsettings

andclickExit.

Add the required IQ5 controllers by right-clicking a

LAN and selecting Insert Device > IQ Controller. The Set up IO Modules (if installed)

Controller Selectiondialogueappears:

Right-clickintheemptystrategypageandselectDevice

> I/O Setup.

In the I/O Setup dialogue add and configure any IO

Modules as required by following the instructions in the

IQSETManual.

ConfigureRemainingStrategy(asrequired) Create the remainder of the strategy by following the
instructions in the IQSET Manual and IQ5 Configuration Manual.

LocalUserModules

IQ5 Mode: ItisnotnecessarytocreatelocalUserModules fortheIQ5whenitisoperatinginIQ5Mode,unlesstheseare required to control end users access to the web inter face or the IQVIEW SCD (single controller display). All engineering access is controlled by the system accounts created in step 19.

IQ5 Compatibility Mode: Local User Modules control all access to the IQ5 and MUSTbecreated.

SelectIQ5andselecttherequirednumberofI/Opoints (I/O Total)andfeatures(Options)andclickOK.

Note: For Compatibility mode select the Compatibility Mode check box, for IQ5 mode leave it un-selected.

12

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

InstallationInstructions-Configuring

IQ5, IQ5-IO

2 CONFIGURATION (continued)

24

SetupIQ5FeatureLicencing
If any licensable features are required (e.g. additional IO points, NC or INT functionality) thesemustnowbeenabled.

See`LicenceIQ5Features’inthe IQSETManual(TE200147)

Ensure that an IQ5 with the same address and LAN Aftertheorderhasbeenprocessedanemailwillbesentto

numberwiththerequiredoptionsexistsintheSETproject thespecifiedemailaddress.Youwillthenneedto…

seestep23.

WithIQSETconnected(seestep19)andloggedin(see DownloadtheLicenceFilefromthePortalandsaveit.

step22),gotoSystemView.

Using the IQ5 Feature Licensor click to import the

Right-clickthesitenameintheSites tree and select IQ5

LicenceFile.

FeatureLicensor.

Selectwhichdevice(s)toupdate.

Select the device(s) required and click to generate a Click toupdatethedevicelicences.

LicenceRequestFileandsaveitonthePC.

LogintotheHBTLicensingPortal:

Note: If you are not connected to the same IQ5 vCNC that was

used when creating the Licence Request File a warning will

https://MyBuildings.honeywell.com

be displayed. If you are connected to the same site you can

SelectQuickCartanduploadtheLicenseRequestFile.

ignore the warning. If you are not connected to the same site connect using a different connection.

Addanyadditionaldetailsincludingtheemailaddressof thepersonrequiringthelicence,thencheckouttheorder.

25

Set up NC Communication Mode (iftheIQ5isrequiredtooperateasnodecontroller)
Note: The IQ5 must be licenced for NC mode.

Using the Engineering PC/Laptop (see step 7) open a compatiblewebbrowserandaccesstheIQ5webinterface usingitsIPAddressorHostname.
Ifprompted,loginusingvalidsystemaccountcredentials. Select Modules > Networks to display the NC
ConfigurationWizard.

Mode Icon

needs new screenshot
Click required mode icon (see table), and if necessary specifyanyparameters,e.g.LANnumber. Note: If no icons appear, check that the IQ5 is configured and licensed for NC operation (see step 23 & 24).
Click ;thecontrollerwillnowreboot. SetthecommunicationschannelontheMS/TPnetwork
moduletotheporttheMS/TPnetworkisconnectedto.

ParameterSettings

EthernetInternetworktotoMS/TPLAN(default)

Parameter
BACNetMSTP LANnumber
BACnetIP DisableModule

Setting 1,4to9,11to119
No=Enabled Yes=Disabled

CurrentLoopInternetworktoMS/TPLan

Parameter Lannumber BACnetIP

Notes 1,4to9,11to119 Canbedisabled

EthernetInternetworktoCurrentLoopLan

Parameter Lannumber BACnetIP BACnetMSTP

Notes 1,4to9,11to119 Canbedisabled Canbeenabled

Ethernet Internetwork to Current loop Internetwork Note address no longer needs to be>100.

Parameter Lannumber BACnetIP BACnetMSTP

Notes 1,4to9,11to119 Canbedisabled Canbeenabled

Manualconfigurationofallparameters (notrecommended)

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

13

IQ5, IQ5-IO

InstallationInstructions-Configuring

2 CONFIGURATION (continued)
26 ConfigureorDisabletheWebServer(ifrequired)
The IQ5’s web server enables users to access the web interfaceforviewing/changingmoduleparameters(including settingupNCmode-seestep25)orinteractingwithoptional GraphIQpagesviaawebbrowser.
Connection to the IQ5’s web ser ver can be made via HTTP and/orHTTPSprotocolandboththeseportsareenabledby default.
Note: Where HTTPS is used it will be necessary to configure SSL certificates (see the IQ5 Configuration Manual).
Ifaccesstothewebinterfaceisnotrequireditisrecommended thatbothportsaredisabledforsecurity.Forexample:
Using the Engineering PC/Laptop (see step 7) open a compatible web browser and access the IQ5 web interfaceusingitsIPAddressorHostname.
Ifprompted,loginusingvalidsystemaccountcredentials. SelectModules > Networks. Selectn1(EthernetIP). Set the Web Server Port Number and/or Secure Web
Server Port Number parametersto0todisabletheport. Click .

IQ5ConfigurationManual(TE201486) IQSETManual(TE200147)

27 SetupCurrentLoopBaudRate
If the IQ5 is to connect to a Trend current loop network baud rate for the current loop network must be specified. The IQ5 will automatically detect the baud rate being used onthenetworkandsetitselfaccordingly.Onsystemswhere thereisonlyIQ5sandIQ4sonthecurrentloopnetwork,the controllerswilldecideamongstthemselveswhatbaudrateto use;thismaynotbetheonethatisrequired.Inthissituation itisnecessaryforonecontrollertobesettoaspecificbaud rateusingIQSET’sIQToolMonitorApplettoensuretheother controllersselecttherequiredbaudrate.

IQToolMonitorAppletManual(TE201298)

28

DownloadStrategytoIQ5Controller
Use IQSET to download the strategy to the controller(s).

IQSETManual(TE200147)

Forasinglecontroller… Select the appropriate controller/strategy in the Project
View. FromtheStrategy menu select Create Data File. In the SystemViewselecttheappropriatecontroller. Right-clickthecontrollerandselectSend File to Device. In the File Downloaddialogueboxcheckthatthecorrect
fileisselectedtheinTransfer Directoryfield. Click tostartthedownload.
For other methods or for downloading to multiple controllers pleaserefertotheIQSETManual

IMPORTANT: The controller’s date and time MUST be set correctly to ensure that the controller’s security certificates can be correctly validated. Communications issues will occur if the security certificates are not valid. This can be done by selecting the option to set the controller’s time is selected when downloading the strategy.
Note: If the strategy uses an NTP server to set the IQ5’s time and date, synchronisation will only occur if the IQ5’s time and the server’s time are within 49 days of each other.
Note: The controller’s date and time may be set up from a controller configured as timemaster.

14

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

InstallationInstructions-Configuring

IQ5, IQ5-IO

2 CONFIGURATION (continued)

29

Check RS-485 Network Indicators (ifRS-485devicesareconnected)

RS485 123
IQ500only

Normal operation indication
PortconfiguredOKandcommunicationsaregood.
Port not active. No Network module exists in the controllerstrategyorisnotconfiguredcorrectly.
Fault indication Nocommunicationsornonetworkconnected.Does not apply when por t is assigned to a network XNC serialmodule.
Note: A controller configured for NC operation will show on port 1 until BACnet devices are connected.

30

Check Ethernet Indicators (foranyconnectedports)

Normal operation indication 1000Mbpslinkdetected
100Mbpslinkdetected
10Mbpslinkdetected

IQ500only

IQ500only

Note: The indicator will flash when data is being transmitted or received.

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

15

IQ5, IQ5-IO

InstallationInstructions-Configuring

2 CONFIGURATION (continued)

31

CheckStatusIndicatorofT1LDevices(ifconnected)
IQ5-IO Modules
Normal operation indication T1L device operational and addresssetOK. IfallT1Ldevicesareinthisstate, gotostep`32’onpage18. T1Ldeviceisbootingup-please wait a few minutes and check again.
IQ5-IOHOAmoduleisinOffline mode

IQ5-LAN-ADPT

Every0.5s
Every0.2s Fault indication

Address is being set after Service button has been pressed.
Download or configuration in progress. – configuration addressviasoftware.
FactorydefaultmodeT1Ldevice not addressed properly – go to step`31’onpage17. T1Ldevicenotpowered-check connection from previous module or separate PSU (if applicable) TheT1Ldevicehasencountered aproblem.
AfterT1Ldevicehasbootedup. Communication with controller lost or for IO modules there is an issuewithaninputchannel.

16

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

InstallationInstructions-Configuring

IQ5, IQ5-IO

2 CONFIGURATION (continued)

32

SettheAddressofanI/OModuleorCurrentLoopLANAdapter
The IQ5 controller will automatically attempt to match each physical device (I/O module or Current Loop LAN Adapter)withitscorrespondingstrategyI/Omoduleandsetitsaddressaccordingly.

However,thecontrollerwillbeunabletosettheaddressif:

there is more than one unaddressed physical device of thesametype,
thereismorethanoneunaddressedstrategymoduleof thesametype,or
thereisnocorrespondingstrategymoduleinthestrategy.

Shouldanyoftheabovesituationsariseitwillbenecessary to set the address of any affected device using either of the followingmethods.

Method 1:UsetheIQToolSoftAddresserAppletinIQSET. IQ Tool Soft Addresser Applet Manual (TE201356)
Use the applet to assign the physical device to the appropriatestrategyI/Omodule.

Note: If a T1L device is not visible in either the applet or the
web interface, it may be because it has already be used with another controller. A T1L device becomes bound to the first controller it connects to over the T1L bus. If connecting the module to a different controller it will need to be reset as shown in section 7 on page 24.

Method 2:Usethecontrollerwebinterface.

IQ5UserGuide(TE201490)

Logintothecontroller’swebinterface. Access the I/O Module page and enter addresses as
required.

IdentifyingaModuleusingthe`Wink’Function(ifrequired)

Tohelpidentifyaspecificmoduleitcanbeplacedin`wink’mode,eitherfromthemoduleitselforsetuptool.Whileinwinkmode themodule’sserviceindicator willflashandthestatusindicatorringofthecorrespondingcontrollerwillalsoflashgreen.

Method 1:Usethemodule’sservicebutton..

Pressthemodule’sservicebutton briefly(<1second).

The module’s service indicator

will flash for

approximately1minute,showingthatthedeviceisinwink

mode.

Open either the IQ Tool Soft Addresser Applet or the

controller’swebinterface(seeMethod2and3).

Any module in wink mode will have its Wink parameter

setto`On’.

Method 2:UsetheIQToolSoftAddresserAppletinIQSET.
IQ Tool Soft Addresser Applet Manual (TE201356)

Clickthe

buttonfortheappropriatemodule.

Thebuttonbackgroundwillflashgreenandthemodule’s

serviceindicator willflash,showingthatthedevice

isinwinkmode.

Clickthebuttonagaintoturnoffwinkmode.

Method 3:Usethecontrollerwebinterface.

IQ5UserGuide(TE201490)

Logintothecontroller’swebinterface. AccesstheI/O Modulepage. In the Wink column set the parameter to `On’ for the
appropriatemodule. The module’s service indicator will flash, showing
thatthedeviceisinwinkmode.Itwillcontinuetoflashuntil thecorrespondingWinkparameterissetbackto`Off’.

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

17

IQ5, IQ5-IO

InstallationInstructions-Configuring

2 CONFIGURATION (continued)

33

CheckTxandRXIndicators(IQ5-LAN-ADPTonly)

IQ5-LAN-ADPT

Normal operation indication CurrentloopisintactontheTxside.
Tx

CurrentloopisintactontheRxside. Rx

Fault indication

SignalnotreachingRXon

Tx

downstreamdeviceonnetwork

NoTXsignalfromupstream

Rx

deviceonnetwork.

CheckconnectionbetweenIQ5-LAN-ADPTandIQ5 Checkbaudsettingsofalldevicesoncurrentloop Checkalldeviceconnections.

34

SwitchOffController(includingadditionalPSUs)

35 Reconnect Inputs
IQ5 IQ5-IO IQ5-IO IQ5-IO IQ5-IO

IQ5-IO IQ5-IO

!

CAUTION:CheckthateachinputconnectionisappropriatefortheIOmoduleinputtype.Forexample,ensurethata mainsvoltageisnotappliedtoalowvoltageinput.

18

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

InstallationInstructions-Configuring

2 CONFIGURATION (continued)

36

Switch On Controller & Input Supplies (includingadditionalPSUs)

O
PSU
I

O
PSU
I

O
PSU
I

IQ5, IQ5-IO
PSU

I O

IQ5 IQ5-IO IQ5-IO IQ5-IO IQ5-IO

IQ5-IO IQ5-IO

O
PSU
I
37 Check Input Operation Analogue

Digital

IQ4/IO Modules
IQ4/IO/..InstallationInstructions-Configuring(TG201161) Section 4 Only
XCITE/IOModules
XCITE/IO/..InstallationInstructions-Configuring(TG200627) Section 4 Only

38

SwitchOffController&InputSupplies(includingadditionalPSUs)

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

19

IQ5, IQ5-IO 2 CONFIGURATION (continued)
39 Reconnect Outputs

InstallationInstructions-Configuring

IQ5 IQ5-IO IQ5-IO IQ5-IO IQ5-IO

IQ5-IO IQ5-IO

!

CAUTION:CheckthateachoutputconnectionisappropriatefortheIOmoduleoutputtype.Forexample,ensurethata mainsvoltageisnotappliedtoalowvoltageoutput.

40 Switch On Controller, Input & Output Supplies (includingadditionalPSUs)

41 Check Output Operation Analogue Channel Indicator

Digital

Channel Indicator

LOAD

LOAD

LOAD

LOAD

IQ4/IO Modules
IQ4/IO/..InstallationInstructions -Configuring(TG201161) Section 4 Only

XCITE/IOModules
XCITE/IO/..InstallationInstructions -Configuring(TG200627) Section 4 Only

42 BackupStrategy

Itisgoodpracticetouploadthestrategyfromeachcontroller intoIQSETtocreateabackup.
Ifrequired,youcanalsocomparethisuploadedstrategywith thatheldinyourprojectandcheckforanydifferences.

IQSETManual(TE200147)

20

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

InstallationInstructions-Configuring

IQ5, IQ5-IO

2 CONFIGURATION (continued)

43

Install Supervisors or Displays (ifrequired)
If a supervisor or local display is required, install these now following the appropriate installationinstructionsandtheguidancenotesbelow.Otherwisegotostep43onpage22.

Connection Method
DirectviaEthernetPort ViaEthernetNetwork DirectviaUSBEngineeringPort

Suitable for IPTool IQSET

ü

ü*

ü

ü*

û

ü

Supervisor (e.g.IQVISION)
ü*
ü*
û

*connectionrequiresavCNCtobeconfiguredonthetargetcontroller.

WebInterface (e.g.IQVIEWSCDforIQ5)
ü
ü
û

Direct Connection via Ethernet Port

Connection via Ethernet Network

IQVIEW SCD

IQVIEW SCD

PC

IQ500only

IQ500only
RJ45 StandardEthernetcable (Cat5etwistedpair) max100m(109yds)

PC

RJ45 IQ500only

IQ500only
StandardEthernetcable (Cat5etwistedpair) max100m(109yds)

TomakeaconnectionwithIQSETorsupervisorensure that a vCNC is available in a Trend device on the same Ethernet Trend network and connect to the vCNC as describedinthesupplieddocumentation.
Note: If connecting with IP Tool, the PC should be on the same Ethernet segment as the IQ5.
To make a connection with a web browser run the web browser on the PC and access the IQ5’s IP address or hostname.
To make a connection with an IQVIEW SCD, install the IQVIEWSCDapplicationonthecontroller,thenconfigure thedisplaydevicewiththeURLoftheIQ5controller.For fulldetailsseeIQVIEWSingleControllerDisplayforIQ5 Manual(TE201504).

Router

Hub/Switch

DirectConnectionviaUSBEngineeringPort
PC (with IQSET)

Thismethodisonlysuitableforatemporaryconnectionwith IQSETduringsystemcommissioningorfaultfinding.

USBtypeC connector
(behindflap)

USBcable

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

21

IQ5, IQ5-IO

2 CONFIGURATION (continued)

44

Close Panel / Enclosure
Theconfigurationprocedureisnowcomplete!

InstallationInstructions-Configuring

22

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

InstallationInstructions-Configuring

3 RESETIQ5CONTROLLERTOFACTORYDEFAULTS
Afactoryresetwillerasethestrategyandrebootthecontrollerintoitsdefaultconfiguration.

1

Isolate Power and Disconnect All I/O

Followsteps1,2,4,8and9(onpages1to4)to:

Isolate Power, Open Panel, DisconnectAllI/O, UnplugallEthernetcables.AnyRS-485networksmaybeleftconnected, SwitchonpowertoIQ5only, Waitforcontrollertosettle.

IQ5, IQ5-IO

2

Perform the Reset

Press and hold down the service button (located behind thedropdownflap)untiltheringindicatorflashesyellow,then releasethebutton.Toinitiatetheresetpressthebuttonagain whiletheindicatorisstillflashing.

The reset process may take up to several minutes depending on the controller type. Do not remove power to the controller until the process has completed.
Whilethecontrolleriserasingthestrategy,theringindicator will remain yellow and appear to `rotate’. When the reset is completethecontrollerwillrebootasshowninstep9onpage 4.

Thestrategy,usermodules(passwords,etc),alarmlogs,and plots records are cleared down, and all other parameters will
be returned to their default settings as shown in step 15 on page8.

Note: Time and date are left at their current values, and the license is not affected by the reset.

10s

5 s

60s

LongPress 10s

Release

ShortPress <5s

10s
IQ5 will reboot, seestep9.

3

Re-configuretheController

Gotostep15

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

23

IQ5, IQ5-IO

InstallationInstructions-Configuring

4 RESETAT1LDEVICETOFACTORYDEFAULTS
Afactoryresetwilleraseallsettingsandrebootthedeviceintoitsdefaultconfiguration.

1

Isolate Power and Disconnect all I/O from the Device

Followsteps1,2,4,8and9(onpages1to4)to:

Isolateanypowersuppliesusedbythedeviceinputsoroutputs, Open panel, DisconnectallI/Ofromthedevice, Isolatethedevicepowersupply.

2

Perform the Reset

Withthedevicepoweredup,usetheservicebuttontoinitiate theresetprocessasfollows:

Theresetprocesswillonlytakeafewsecondsdepending on the module type. Do not remove power to the module
until the process has completed.

When the reset is complete the module will reboot and the controller will attempt to re-address the module as shown in

10s

<5s

<5s

LongPress 10-15s

Release ShortPress <1s

Module will
thenrebootinto default state

3

Reconnect Inputs & Outputs and Check Operation

Followtheguidancefromstep30onpage16,throughtostep`43’onpage22.

24

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

InstallationInstructions-Configuring

IQ5, IQ5-IO

5 MANUALCHANNELCONFIGURATION 5.1 SetChannelTypeandValue
WhenIQ5-IOHOAmodulesareinofflinemodethechannelsmustbeconfiguredtomatchtheconnectedI/Oandtherequiredvalue set.

1

Select Channel

1

2

3

4

ON

ON

OFF

OFF

5

6

7

8

ON

ON

OFF

OFF

Auto

1

2

3

4

ON

ON

OFF

OFF

5

6

7

8

ON

ON

OFF

OFF

N/A

Auto

2

SelectChannelConfiguration

N/A N/A
DO
AO 0-11V
AO 0-20mA

Auto
Note: If N/A is selected the channel can’t be used.

3

SetOutputValue

AO 3

VOLTAGE 0-11V
0%
Output in Manual

Auto

AO 3

VOLTAGE 0-11v

Auto

AO 3

VOLTAGE 0-11V
0%

AO 3

VOLTAGE 0-11V
25%
Output in Manual

Auto

AO 3
VOLTAGE 0-11V
SET 25%
Output in Manual

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

25

IQ5, IQ5-IO

5.2 Reset Channel Type

1

Select Channel

DO 1 ON OFF
DO 5 ON OFF

DO 2 ON OFF
DO 6 ON OFF

AO 3
25% DO 7
ON OFF

DO 4 ON OFF
DO 8 ON OFF

Auto

2

Reset Channel

AO 3 VOLTAGE 0-11V
SET 25%
Output in Manual
Auto
3s

InstallationInstructions-Configuring

DO 1 ON OFF
DO 5 ON OFF

DO 2 ON OFF
DO 6 ON OFF

AO 3
25% DO 7
ON OFF

DO 4 ON OFF
DO 8 ON OFF

Auto

AO 3
VOLTAGE 0-11V
SET 25%
Output in Manual

N/A

6 SETANIQ5-IOMODULETOONLINEMODE

1

Set an IQ5-IO Module Back to Online Mode

DO 1 ON OFF
DO 5 ON OFF

DO 2 ON OFF
DO 6 ON OFF

AO 3
25% DO 7
ON OFF

DO 4 ON OFF
DO 8 ON OFF

Auto
3s

When in offline mode the IO module will attempt to communicate with the controller after 3 minutes of inactivity. Ifitisabletocommunicatewiththecontrolleritwillexitoffline mode and wait for the configuration from the controller. Any channelsthathavebeenoverriddenwhileinofflinemodewill retaintheiroverriddenstatus.
Ifitisunabletocommunicatewiththecontrolleritwillcontinue tolistenforthecontroller.
If required it can be forced to exit off-line mode during the 3 minutewaitbypressingtheAutobuttonfor3s.
Note: Resetting the IO module will start the module set up process enabling online or offline mode to be selected as required.

26

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

InstallationInstructions-Configuring

IQ5, IQ5-IO

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025

27

IQ5, IQ5-IO

InstallationInstructions-Configuring

Please send any comments about this or any other Trend technical publicationtotechpubs@trendcontrols.com
© 2025 HoneywellProductsandSolutionsSARL,ConnectedBuildingDivision.Allrightsreserved.ManufacturedforandonbehalfoftheConnected BuildingDivisionofHoneywellProductsandSolutionsSARL,Z.A.LaPièce,16,1180Rolle,SwitzerlandbyitsAuthorizedRepresentative,TrendControl SystemsLimited.
TrendControlSystemsLimitedreservestherighttorevisethispublicationfromtimetotimeandmakechangestothecontenthereofwithoutobligation tonotifyanypersonofsuchrevisionsorchanges.
TrendControlSystemsLimited
St.Mark’sCourt,NorthStreet,Horsham,WestSussex,RH121BW,UK.Tel:+44(0)1403211888,www.trendcontrols.com

28

IQ5,IQ5-IOController&I/OModulesInstallationInstructions-ConfiguringTG201483Issue5,12-May-2025.

Documents / Resources

TREND IQ5-IO Controller and I-O Modules [pdf] Installation Guide
IQ5, IQ5-IO, IQ5-IO Controller and I-O Modules, Controller and I-O Modules, I-O Modules, Modules

References

Leave a comment

Your email address will not be published. Required fields are marked *