RAYCHEM
RTD-200
RTD Temperature Sensor
for Ambient Sensing
Installation Instructions
RTD-200 Temperature Sensor for Ambient Sensing
APPROVALS
Approvals associated with control device, however not to be used in Div. 1 areas.
DESCRIPTION
The nVent RAYCHEM RTD-200 is a three-wire platinum RTD (resistance-temperature-detector) typically used with electronic control systems that require accurate ambient temperature sensing. The RTD-200 comes with a 1/2” NPT fitting that installs to the appropriate conduit box. This allows mounting of the RTD in a typical ambient location. This also allows for splicing of RTD extension wire back to the controller.
Tools required
- None
Additional materials required
- None
KIT CONTENTS
Item | Qty | Description |
A | 1 | RTD temperature sensor with 1/2-in NPT fitting |
SPECIFICATIONS
Sensor | |
Housing | 316 stainless steel |
Dimensions | 3 in (7.6 mm) length 1/4 in (6 mm) diameter |
Accuracy | ±0.3°F (0.2°C) |
Range | –100°F to 300°F (–73°C to 149°C) |
Resistance | 100 ohms +/– .25 ohm at 0°C X=0.00385 ohms/ohm/°C |
Extension Wires | |
Wire size (each of 3) | 22 AWG Note: The length of RTD extension wires is determined by the wire gauge used. To reduce the likelihood that electrical noise will affect temperature measurement, keep RTD extension wires as short as possible. Use shielded instrument cable such as nVent RAYCHEM MONI-RTD-WIRE (22 AWG, PVC insulation, –30°F to 140°F, –20°C to 60°C) or Belden 83553 (22 AWG, FEP insulation, –95°F to 395°F, –70°C to 200°C). |
Wire dielectric strength | 600 volts |
Length | 6 ft (1.8 m) |
Outer jacket | Fluoropolymer |
Maximum exposure temperature |
300°F (149°C) |
Sensor fitting | 1/2-in NPT with sealing washer and nut |
WARNING:
This component is an electrical device. It must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all the installation instructions. Component approvals and performance are based on the use of specified parts only. Do not use substitute parts or vinyl electrical tape to make connections.
INSTALLATION
The RTD-200 can be terminated directly at the controller using the supplied 1/2 in NPT fitting. In this configuration, no additional extension wire is required.
RTD wired directly to controller
(Distance from sensor bulb to controller must be less than 4 ft)
Note: RTD should be placed in a typical ambient location.RTD wired with splice box
Note: RTD should be placed in a typical ambient location.
RTD-200 WIRING
Electrical Schematic of RTD
Connect the wires as shown.
North America Tel +1.800.545.6258 Fax +1.800.527.5703 thermal.info@nVent.com |
Europe, Middle East, Africa Tel +32.16.213.511 Fax +32.16.213.604 thermal.info@nVent.com |
Asia Pacific Tel +86.21.2412.1688 Fax +86.21.5426.3167 cn.thermal.info@nVent.com |
Latin America Tel +1.713.868.4800 Fax +1.713.868.2333 thermal.info@nVent.com |
©2024 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.
RAYCHEM-IM-H56998-RTD200-EN-2401
nVent.com/RAYCHEM
PN P000000095