Danfoss FA11 In Back Out Top Cooling Kit Installation Guide

FA11 In Back Out Top Cooling Kit

Specifications

  • Product Name: In-back/Out-top Cooling Kit for FA11-FA12 iC7
    Series Frequency Converters
  • Compatibility: Fits FA11 and FA12 frequency converters mounted
    in Rittal TS8 and VX25 cabinets with widths of 600 mm (24 in) or
    800 mm (32 in)
  • Kit Numbers:
    • 176F4061 – In-back/out-top cooling kit for FA11 frequency
      converters
    • 176F4062 – In-back/out-top cooling kit for FA12 frequency
      converters

Installation Guide

1. Overview

The in-back/out-top cooling kit is designed for FA11 and FA12
frequency converters mounted in specific cabinet models. It
facilitates airflow by drawing air into the back duct and expelling
it through the top duct.

2. Kit Numbers

Refer to the following kits for installation:

  • 176F4061: In-back/out-top cooling kit for FA11
    frequency converters
  • 176F4062: In-back/out-top cooling kit for FA12
    frequency converters

3. Items Supplied

  • Bottom cover
  • Bottom gasket
  • Telescopic top duct assembly
  • Ribbed EPDM rubber seal
  • Back duct
  • 6-hole back gasket
  • 8-hole back gasket
  • Clip-on nut
  • M6x12 screw
  • M5x18 screw
  • M5x14 screw
  • M5 hex nut

Product Usage Instructions

2. Installation

2.1 Safety Information

NOTICE QUALIFIED PERSONNEL: Only authorized
personnel should install the parts as per the instructions.
Disassembly and reassembly must comply with the service guide. Use
standard torque values unless specified.

WARNING DISCHARGE TIME (40 MINUTES):

  1. Stop the motor.
  2. Disconnect all power sources.
  3. Wait 40 minutes for capacitors to discharge fully.
  4. Verify full discharge using a voltage measuring device before
    servicing.

WARNING ELECTRIC SHOCK HAZARD:

  1. Use qualified electricians for installation.
  2. Disconnect from power before service.
  3. Follow safety regulations and guidelines.

NOTICE ELECTROSTATIC DISCHARGE:

Follow ESD procedures to prevent component damage. Ensure
discharge before touching internal components.

Frequently Asked Questions (FAQ)

Q: Can the cooling kit be used with other frequency
converters?

A: The cooling kit is specifically designed for use with FA11
and FA12 frequency converters and may not be compatible with other
models.

Q: How often should the cooling kit be inspected?

A: Regular inspections are recommended to ensure proper
functioning of the cooling system. We suggest inspecting the kit
annually or as per your maintenance schedule.

“`

Installation Guide
In-back/Out-top Cooling Kit for FA11-FA12
iC7 Series Frequency Converters
1 Overview
1.1 Description
The in-back/out-top cooling kit fits FA11 and FA12 frequency converters mounted in Rittal TS8 and VX25 cabinets with widths of 600 mm (24 in) or 800 mm (32 in). When the kit is installed, air flows into the back duct and out through the top duct. See Figure 1.
1

e30be856.10

3

4 2

Figure 1: Direction of Airflow with Kit Installed

1

Top duct (exhaust)

3

Airflow direction

2

Cooling back channel

4

Bottom duct (intake)

1.2 Kit Numbers
Use these instructions with the following kits. Table 1: In-back/Out-top Cooling Kits

Number 176F4061 176F4062

Kit description In-back/out-top cooling kit for FA11 frequency converters In-back/out-top cooling kit for FA12 frequency converters

Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251 | 1

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12

Installation

1.3 Items Supplied
Table 2: Items Supplied in In-back/Out-top Cooling Kits
Item Bottom cover Bottom gasket Telescopic top duct assembly Ribbed EPDM rubber seal Back duct 6-hole back gasket 8-hole back gasket Clip-on nut M6x12 screw M5x18 screw M5x14 screw M5 hex nut
2 Installation
2.1 Safety Information

Quantity 1 1 1 1 1 2 2 8 6 8 8­10 6

NOTICE QUALIFIED PERSONNEL
Only qualified, Danfoss authorized personnel are allowed to install the parts described in these installation instructions. Disassembly and reassembly of the frequency converter must be done in accordance with the service guide. Use the standard fastener torque values from the service guide, unless the torque value is specified in these instructions.

WARNING DISCHARGE TIME (40 MINUTES)
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning indicator lights are off. Failure to wait 40 minutes after power has been removed before performing service or repair work can result in death or serious injury.
Stop the motor.
Disconnect AC mains and remote DC-link power supplies, including battery backups, UPS, and DC-link connections to other drives.
Disconnect or lock the permanent magnet motor.
Wait for the capacitors to discharge fully. The minimum waiting time is 40 minutes.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.

2 | Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12

Installation

WARNING ELECTRIC SHOCK HAZARD
AC drives contain dangerous voltages when connected to mains voltage. Installing or servicing the drive with power connected can cause death, serious injury, or equipment failure.
Only use qualified electricians for the installation. Disconnect the drive from all power sources before installation or service. Treat the drive as live whenever the mains voltage is connected. Follow the guidelines in these instructions and local electrical safety regulations.
NOTICE ELECTROSTATIC DISCHARGE
Electrostatic discharge can damage components. Follow standard ESD procedures. Ensure discharge before touching internal components, for example by touching a grounded, conductive surface or by wearing a grounded armband.
2.2 Installation Overview
NOTICE APPLYING GASKETS
This kit contains self-adhesive gaskets to ensure a proper seal between metal parts. Before affixing a gasket, check that the part matches the gasket and that no holes are covered.

Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251 | 3

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12

e30bg259.10

Installation 6 7

1 2

3 4 5

Figure 2: Overview of In-back/Out-top Cooling Kit

1

Frequency converter

3

Bottom gasket

5

Bottom cover

7

Top duct assembly

9

Back gasket

11 M6x12 screw

4 | Danfoss A/S © 2024.09

8 9 10
11 12

2

Rittal cabinet

4

M5x14 screw

6

M5 hex nut

8

Clip-on nut

10 Back duct

12 M5x18 screw

AN361429223580en-000201 / 136R0251

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12

Installation

2.3 Creating a Vent Opening in the Mounting Plate
To create mounting holes and a back vent opening in the mounting plate, use the following steps. Use the dimensions in Figure 3 for 600 mm (24 in) cabinets, or Figure 4 for 800 mm (32 in) cabinets. Procedure
1. Drill 6 mounting holes in the back of the frequency converter using the dimensions in the template. 2. Insert 6 M10 pem self-clinching nuts (not supplied) in the mounting holes. 3. Cut out the vent opening in the mounting plate using the dimensions in the template.
The opening must match the frequency converter vent opening.
4. Drill 6 screw holes around the vent opening using the dimensions in the template.
The holes must match the holes in the inner flange of the back duct.

Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251 | 5

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12
499 (19.7) 6X S-M10-2Z1

206 (8.1) 0.0
206 (8.1) e30bg255.10

Installation
23 (0.9) 0.0

7 (0.3) 3 (0.1)

2X 1335 (52.6) 1357 (53.4) 1368 (53.9)
1513 (59.6) 1524 (60.0) 2X 1545 (60.8)
1645 (64.7)

246 (9.7) 230 (9.1) 215 (8.5) 201 (7.9) 0.0 201 (7.9) 215 (8.5) 230 (9.1) 246 (9.7)

Figure 3: Vent Dimensions for Mounting Plate in 600 mm (24 in) Cabinet

6 | Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12
699 (27.5)
6X S-M10-2Z1

206 (8.1) E3h 254 (10.0) E4h 0.0 206 (8.1) E3h 254 (10.0) E4h
e30bg256.10

Installation
23 (0.9) 0.0

7 (0.3) 3 (0.1)

2X 1335 (52.6) 1357 (53.4) 1368 (53.9)
1513 (59.6) 1524 (60.0) 2X 1545 (60.8)
1645 (64.7)

246 (9.7)

230 (9.1)

E3h E4h

26231 (51(08..45))

201 (7.9)

0.0

246 (9.7) 230 (9.1) 26231 (51(08..45)) EE43hh 201 (7.9)

Figure 4: Vent Dimensions for Mounting Plate in 800 mm (32 in) Cabinet
2.4 Creating a Vent Opening in the Backplate
To create a vent opening in the cabinet backplate to match the mounting plate and frequency converter vent, use the following steps. Use the dimensions in Figure 5 for 600 mm (24 in) cabinets, or Figure 6 for 800 mm (32 in) cabinets. Procedure
1. Cut out the vent opening in the cabinet backplate using the template dimensions.
The opening must match the frequency converter vent opening.
2. Drill 8 screw holes (6 mm) around the vent opening using the dimensions in the template.

Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251 | 7

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12 The holes must match the holes in the outer flange of the back duct.
592 (23.3)

Installation
18 (0.7) 0.0

e30bg257.10

16X Ø 6 (0.2)

1383 (54.4) 4X 1394 (54.9) 1396 (55.0)
1590 (62.6) 4X 1592 (62.7) 1603 (63.1)

244 (9.6) 2X 232 (9.1)
225 (8.9) 2X 218 (8.6)
2X 82 (3.2) 75 (3.0)
2X 68 (2.7) 0.0
2X 68 (2.7) 75 (3.0)
2X 82 (3.2) 2X 218 (8.6)
225 (8.9) 2X 232 (9.1)
244 (9.6)

Figure 5: Vent Dimensions for Backplate in 600 mm (24 in) Cabinet

8 | Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12
792 (31.2)

Installation
18 (0.7) 0.0

e30bg258.10

16X Ø 6 (0.2)

1383 (54.4) 4X 1394 (54.9) 1396 (55.0)
1590 (62.6) 4X 1592 (62.7) 1603 (63.1)

244 (9.6) 2X 232 (9.1)
225 (8.9) 2X 218 (8.6)
2X 82 (3.2) 75 (3.0)
2X 68 (2.7) 0.0
2X 68 (2.7) 75 (3.0)
2X 82 (3.2) 2X 218 (8.6)
225 (8.9) 2X 232 (9.1)
244 (9.6)

Figure 6: Vent Dimensions for Backplate in 800 mm (32 in) Cabinet
2.5 Creating a Vent Opening in the Top Plate
To create a vent opening in the cabinet top plate, use the following steps. Procedure
1. Cut out the vent opening in the cabinet top plate using the dimensions in Figure 7 for TS9 cabinets, or Figure 8 for Vx25 cabinets.
The opening must match the frequency converter vent opening.
2. Drill 6 screw holes (6 mm) around the vent opening using the dimensions in the template.

Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251 | 9

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12

The holes must match the holes in the upper flange of the top duct.

48 (1.9)

378 (14.9)

160 (6.3)

160 (6.3)

159 (6.2)

Installation
62 (2.4) 131 (5.2)

e30bg114.11

e30bl756.10

3 (0.1)

6X 6 (0.2)

Figure 7: Dimensions of Opening in Top Plate of TS8 Cabinet

195 (7.7)

378 (14.9)

160 (6.3)

160 (6.3)

89 (3.5)

131 (5.2)

14 (0.6) 159 (6.2)

4 (0.15)

14 (0.6) 384 (15.1)

6X 6 (0.2)
Figure 8: Dimensions of Opening in Top Plate of VX25 Cabinet 10 | Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12

Installation

2.6 Assembling the Top Duct
The top duct is a telescopic duct that collapses to simplify installation. To assemble the duct before installation, use the following steps. See Figure 9. Procedure
1. Cut the strip of ribbed EPDM rubber seal into 2 pieces of 1027 mm (40.4 in). 2. Peel the paper off the self-adhesive seals. Place 1 strip on the outside bottom edge of the inner sleeve of the duct, and 1 strip on
the upper inside edge of the outer sleeve of the duct. 3. With the rubber seal in place, carefully slide the inner sleeve of the duct into the outer sleeve.

e30bj178.10

1

2 3

Figure 9: Assembly of Telescopic Duct

1

Inner sleeve of duct

3

Outer sleeve of duct

2

Ribbed EPDM rubber seal

Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251 | 11

e30bg232.10

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12
2.7 Installing the Top Duct Over the Top Vent
To attach the top duct over the top vent of the frequency converter, use the following steps. See Figure 10. Procedure
1. Remove 2 M5x14 screws (T25) at the back of the top vent and retain the screws. 2. Remove 3 M5x12 screws (T25) at the front of the top vent and retain the screws. 3. Position the top duct over the vent in the top of the frequency converter. 4. Line up the holes in the lower flange with the screw holes in the frequency converter. 5. Secure the lower flange to the frequency converter with 5 screws (T25) previously removed.
Torque fasteners to 2.3 Nm (20 in-lb). 6. Collapse the duct until installation of the cabinet top plate.
1
2
3
4 5
6

Installation
7 8

Figure 10: Installation of the Top Duct Over the Top Vent

1

Threaded stud

3

M5x14 screw

5

Top of frequency converter

7

Upper flange of duct

12 | Danfoss A/S © 2024.09

2

Top duct

4

M5x12 screw

6

Cooling back channel

8

Lower flange of duct

AN361429223580en-000201 / 136R0251

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12

Installation

2.8 Installing the Bottom Cover
NOTICE DRAIN OPENING
The bottom cover features a drain opening in the middle of the plate. To drain moisture in wet or humid environments, attach nylon tubing with an interior diameter of 8 mm (0.3 in). To seal the drain in dry environments, fasten a screw in the drain hole.
To install the bottom cover at the lower end of the cooling back channel, use the following steps. See Figure 11. Procedure
1. Remove the paper backing from the bottom gasket. 2. Adhere the gasket to the upper side of the bottom cover. 3. Position the bottom cover and gasket over the opening at the lower end of the cooling channel. 4. Secure the bottom cover using the M5x14 screws (T25).
Torque screws to 2.3 Nm (20 in-lb). FA11 frequency converters require 8 screws, and FA12 frequency converters require 10 screws.

1 2

e30bg243.10

7

3

8

4

5

6

Figure 11: Installation of the Bottom Cover

1

Frequency converter

3

Bottom gasket

5

M5x14 screws

7

Mounting plate

2

Cooling back channel

4

Bottom cover

6

Drain hole

8

Cabinet rails

Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251 | 13

e30bl642.10

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12

Installation

2.9 Mounting the Frequency Converter
To install the mounting plate and frequency converter in the cabinet, use the following steps. Procedure
1. Remove the paper backing from both 6-hole gaskets, exposing the adhesive. 2. Adhere 1 gasket around the vent opening on each side of the mounting plate. 3. Install the Rittal mounting plate brackets in the furthest back position on the rails at the base of the cabinet.
For VX25 cabinets, see step 1 in Figure 12. For TS8 cabinets, see step 1 in Figure 13.
4. Insert the plastic brackets on the mounting plate into the brackets installed on the cabinet rails in the previous step.
For VX25 cabinets, see step 2 in Figure 12. For TS8 cabinets, see step 2 in Figure 13.

1

2

Figure 12: Rittal VX25 Cabinet – Installation of Mounting Brackets and Mounting Plate

14 | Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12
1
2

Installation

e30bl643.10

Figure 13: Rittal TS8 Cabinet – Installation of Mounting Brackets and Mounting Plate 5. Align the highest mounting plate hole with the 5th hole from the top of the cabinet rails.
Check that the pem nuts face the back of the cabinet. 6. Fasten the mounting plate to the cabinet rails with 14 M5x10 thread-forming screws. 7. Loosely fasten 3 M10 screws (not supplied) into the pem nuts at the lower end of the mounting plate.
Check that the screws are secure. The base of the frequency converter rests on the screws. 8. Slightly lean the top of the frequency converter forward and set the cutouts in the base onto the 3 screws. 9. Slowly push the top of the frequency converter back against the mounting plate until the top 3 pem nuts line up with the holes
in the frequency converter. 10. Secure the top of the frequency converter using 3 M10 screws.
Torque the 6 M10 screws to 19 Nm (170 in-lb).

Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251 | 15

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12

Installation

2.10 Attaching the Top Duct to the Top Plate
After the frequency converter is installed on the mounting plate, attach the top duct to the cabinet top plate using the following steps. Procedure
1. Extend the top duct upward until the upper flange of the duct is positioned against the underside of the cabinet top plate. 2. Secure the duct to the top plate with 6 M5 hex nuts (T25).
Torque fasteners to 2.3 Nm (20 in-lb).
2.11 Installing the Backplate and Back Duct
To attach the cabinet backplate and the back duct, use the following steps. See Figure 14. Procedure
1. Position the backplate on the back rails of the cabinet behind the mounting plate. 2. Secure the backplate to the rails using the existing fasteners. 3. Slide 8 M5 clip-on nuts over the screw holes around the duct opening in the backplate. 4. Remove the paper backing from both 8-hole gaskets, exposing the adhesive. 5. Adhere 1 gasket to the back and 1 gasket to the front of the back duct outer flange. 6. Position the back duct in the hole created for it in the mounting plate and backplate. 7. Fasten the inner flange of the back duct with 6 M6x12 screws (T30).
Torque to 3.9 Nm (35 in-lb).
8. Fasten the outer flange of the duct with 8 M5x18 screws (T25).
Torque fasteners to 2.3 Nm (20 in-lb).

16 | Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12

Installation
1 2 3 4
5 6

e30bg264.10

7

8 9
10

Figure 14: Installation of the Backplate and Back Duct

1

Backplate

3

M5 clip-on nut

5

M5x18 screw

7

8-hole gaskets

9

Rittal cabinet

2

Mounting plate

4

Back duct

6

M6x12 screw

8

6-hole gaskets

10 Frequency converter

Danfoss A/S © 2024.09

AN361429223580en-000201 / 136R0251 | 17

Installation Guide | In-back/Out-top Cooling Kit for FA11-FA12

Danfoss A/S DK-6300 Graasten Ulsnaes 1 drives.danfoss.com

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalog descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogs, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

Danfoss A/S © 2024.09

M00280
*136R0251*

AN361429223580en-000201 / 136R0251