Danfoss AK-CC55 Multi Coil Case Controllers

Danfoss AK-CC55 Multi Coil Case Controllers

Danfoss AK-CC55 Multi Coil Case controllers

Danfoss AK-CC55 Multi Coil Case controllers

Danfoss AK-CC55 Multi Coil Case controllers

Copyright, Limitation of Liability and Revision Rights

This publication contains information proprietary to Danfoss. By accepting and using this interface description the user agrees that the information contained herein will be used solely for operating equipment from Danfoss or equipment from other vendors provided that such equipment is intended for communication with Danfoss AK-CC55 Multi Coil Controllers over the RS 485 Modbus serial communication link.

This publication is protected under the Copyright laws of Denmark and most other countries.

Danfoss does not guarantee that a software program produced according to the guidelines provided in this manual will function properly in every physical, hardware or software environment.

Although Danfoss has tested and reviewed the documentation within this interface description, Danfoss makes no warranty or representation, either express or implied, with respect to this documentation, including its quality, performance, or fitness for a particular purpose.

In no event shall Danfoss be liable for direct, indirect, special, incidental, or consequential damages arising out of the use, or the inability to use information contained in this interface description, even if advised of the possibility of such damages.

In particular, Danfoss is not responsible for any costs including but not limited to those incurred as a result of lost profits or revenue, loss or damage of equipment, loss of computer programs, loss of data, the costs to substitute these, or any claims by third parties.

Danfoss reserves the right to revise this publication at any time and to make changes in its contents without prior notice or any obligation to notify previous users of such revisions or changes.

Modbus Communication

Danfoss AK-CC55 controllers are using Modbus RTU.
Communication speed is default “auto detection” Default communication settings are “8 bit, Even parity, 1 stop bit”.

Network address can be set via AK-UI55 setting display and Network address as well as Network communication settings can be changed via the AK-UI55 Bluetooth display and the AK-CC55 Connect service app. For further information see AK-CC55 Documentation.

Danfoss AK-CC55 controllers are Modbus compliant and MODBUS Application Protocol Specification can be found via http://modbus.org/specs.php

AK-CC55 Documentation:
AK-CC55 User Guides and Installation Guides can be found via www.danfoss.com:

https://www.danfoss.com/en/products/electronic-controls/dcs/evaporator-and-room-control/#taboverview

Parameter list for Multi Coil (084B4084)

Parameter PNU Value Min. Max. Type RW Scale A
Readouts
— Sum alarm 2541 0 0 1 Boolean R 1
u00 Ctrl. State 2007 0 0 48 Integer R 1
U74 Ctrl. State B 2734 0 0 48 Integer R 1 X
U83 Ctrl. State C 2743 0 0 48 Integer R 1 X
u17 Ther. air 2532 0 -2000 2000 Float R 0.1
U77 Ther. air B 2737 0 -2000 2000 Float R 0.1 X
U86 Ther. air C 2746 0 -2000 2000 Float R 0.1 X
u26 Evap Temp Te 2544 0 -2000 2000 Float R 0.1
u20 S2 temp 2537 0 -2000 2000 Float R 0.1
U79 S2 temp. B 2739 0 -2000 2000 Float R 0.1 X
U88 S2 temp. C 2748 0 -2000 2000 Float R 0.1 X
u16 S4 air temp. 2531 0 -2000 2000 Float R 0.1
U76 S4 temp B 2736 0 -2000 2000 Float R 0.1 X
U85 S4 temp C 2745 0 -2000 2000 Float R 0.1 X
u09 S5 temp 1011 0 -2000 2000 Float R 0.1 X
u75 S5 temp. B 2595 0 -2000 2000 Float R 0.1 X
U72 Food temp 2702 0 -200 2000 Float R 0.1 X
u23 EEV OD % 2528 0 0 100 Float R 0.1 X
U82 EEV OD % B 2742 0 0 100 Float R 0.1 X
U91 EEV OD % C 2751 0 0 100 Float R 0.1
U73 Def. Stop Temp 2703 0 -2000 2000 Integer R 1 X
U93 Def. Stop Tem B 2763 0 -2000 2000 Integer R 1 X
U94 Def. Stop Tem C 2764 0 -2000 2000 Integer R 1 X
u57 Alarm air 2578 0 -2000 2000 Float R 0.1
u86 Ther. band 2607 1 1 2 Integer R 0.1
U34 Alarm air B 2671 0 -2000 2000 Float R 0.1 X
U92 Alarm air C 2762 0 -2000 2000 Float R 0.1 X
u13 Night cond 2533 0 0 1 Boolean R 1
u90 Cutin temp. 2612 0 -2000 2000 Float R 0.1
u91 Cutout temp. 2513 0 -2000 2000 Float R 0.1
u21 Superheat 2536 0 -2000 2000 Float R 0.1
u22 Superheat Ref 2535 0 -2000 2000 Float R 0.1
U80 Superheat B 2740 0 -2000 2000 Float R 0.1 X
U81 SH Ref B 2741 0 -2000 2000 Float R 0.1 X
U89 Superheat C 2749 0 -2000 2000 Float R 0.1 X
U90 SH Ref C 2750 0 -2000 2000 Float R 0.1 X
Settings
r12 Main switch 117 0 -1 1 Integer RW 1
r00 Cutout 100 20 -500 500 Float RW 0.1
r01 Differential 101 20 1 200 Float RW 0.1
— Def. Start 1013 0 0 1 Boolean RW 1
d02 Def . Stop temp 1001 60 0 500 Float RW 0.1
A03 Alarm delay 10002 30 0 240 Integer RW 1
A13 High Lim Air 10019 80 -500 500 Float RW 0.1
A14 Low Lim Air 10020 -300 -500 500 Float RW 0.1
r21 Cutout 2 131 2.0 -60.0 50.0 Float RW 1
r93 Diff Th2 210 2.0 0.1 20.0 Float RW 1
d02 Def. Stop Temp 1001 6.0 0.0 50.0 Float RW 1
d04 Max Def. time 1003 45 d24 360 Integer RW 0
d28 DefStopTemp2 1046 6.0 0.0 50.0 Float RW 1
d29 MaxDefTime2 1047 45 d24 360 Integer RW 0
Alarms
— Contr. error 20000 0 0 1 Boolean R 1
— RTC error 20001 0 0 1 Boolean R 1
— Pe error 20002 0 0 1 Boolean R 1
— S2 error 20003 0 0 1 Boolean R 1
— S4 error 20004 0 0 1 Boolean R 1
— S5 error 20005 0 0 1 Boolean R 1
— S5 error B 20006 0 0 1 Boolean R 1
— RH input err 20007 0 0 1 Boolean R 1
— S4 error B 20008 0 0 1 Boolean R 1
— S4 error C 20009 0 0 1 Boolean R 1
— S2 error B 200010 0 0 1 Boolean R 1
— S2 error C 200011 0 0 1 Boolean R 1
— Hight. alarm 200012 0 0 1 Boolean R 1
— Low t. alarm 200013 0 0 1 Boolean R 1
— Door alarm 200014 0 0 1 Boolean R 1
— Max Hold Time 200015 0 0 1 Boolean R 1
— No Rfg. sel. 200016 0 0 1 Boolean R 1
— DI1 alarm 200017 0 0 1 Boolean R 1
— DI2 alarm 200018 0 0 1 Boolean R 1
— Standby mode 200019 0 0 1 Boolean R 1
— Case clean 200020 0 0 1 Boolean R 1
— High Temp. B 200021 0 0 1 Boolean R 1
— Low Temp. B 200022 0 0 1 Boolean R 1
— CO2 Alarm 200023 0 0 1 Boolean R 1
— Refg. Leak 200024 0 0 1 Boolean R 1
— High Humidity 200025 0 0 1 Boolean R 1
— Low Humidity 200026 0 0 1 Boolean R 1
— High Temp. C 200027 0 0 1 Boolean R 1
— Low Temp. C 200028 0 0 1 Boolean R 1
— Max Def. Time 200029 0 0 1 Boolean R 1
— Max Def Time B 200030 0 0 1 Boolean R 1
— Max Def Time C 200031 0 0 1 Boolean R 1

Note: Parameters marked with “X” in the “A” (App mode column) is not present in all App modes (for further info see AK-CC55 User Guide).

Customer Support

Danfoss A/S
Climate Solutions danfoss.com +45 7488 2222
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.
©Danfoss | Climate Solutions | 2022.02
Logo

Documents / Resources

Danfoss AK-CC55 Multi Coil Case Controllers [pdf] User Guide
AK-CC55, AK-CC55 Multi Coil Case Controllers, Multi Coil Case Controllers, Coil Case Controllers, Case Controllers, Controllers

References

Leave a comment

Your email address will not be published. Required fields are marked *