Version:TCR7 1.3(12/2023)
IPS Colorful LCD Screen Smart Thermostat
✔ Quick configuration of Wi-Fi connection via BLE Technology super convenient
✔ Programmable device, multiple periods allowed to set per day.
✔ 2.8 inches large colorful LCD screen, delicate visual effect.
✔ The device can be controlled by voice via Amazon Alexa and Google Assistant
Parameter
Supply voltage | AC100~240V; 50/60Hz |
Power consumption | Wi-Fi 3W Max |
Temp. setting range | 5~95℃ (41~203℉) |
Floor limited range | 20~90℃ (68~194℉) |
On/off deviation | 0.5~10℃ (1~10℉), Factory setting 1℃ |
Ambient temperature | -5~50℃ (68~122℉) |
Protection level | IP20 |
Shell material | Anti-Flammable PC |
Product Overview
This series of thermostat has Floor Heating, Fan Coil, and Integrated version, meeting the requirements under different scenarios.
Version |
System mode | Model |
Application |
Floor heating | Floor heating |
EP |
Built-in & floor sensor, floor limit sensor + Weekly programming |
WP |
A NC/NO dual-output + Weekly programming | ||
WPB |
A NC/NO dual-output + Weekly programming + Potential-free output | ||
Fan Coil | Heating /Cooling / Ventilation |
AC2 |
Timer task + 2-pipe system |
AC2-485 |
Timer task + 2-pipe system + Timer task + Potential-free output + 485 Modbus (optional) + Room card (optional) | ||
AC4 |
Timer task + 4-pipe system + Timer task + Potential-free output + 485 Modbus (optional) + Room card (optional) | ||
Integrated | Fan-Coil with Floor-Heating air condition system |
AWY |
Floor heating & fan coil, weekly programming + Potential-free output + Timer task + 485 Modbus (optional) + Room card (optional) |
Display Symbols
- Child-lock Mode
- Frost Protection
- Wi-Fi
- Room humidity
- Set Temp.
- Room Temp.
- Working mode
Fan
Auto Mode
Manual Mode
Temporary Mode
- Fan Speed (back)
- Knob (Power on/off)
- (next) Mode
- Floor Heating valve
- Fan Coil valve
- Outdoor humidity
- Outdoor Temp.
- Date Week
- Time Display
Temperature Control Mode(Floor Heating/Integrated)
Auto Mode
Weekly-circled programme, up to 6 heating events can be set per day.
Heating events, workdays and temperature can be separately customized based on personal routines.
Manual Mode
Thermostat works based on manually-set temperature, disconnecting from auto mode.
Temporary Mode
Thermostat works based on manually-set temperature temporarily and then shifts back to auto mode till next event.
User Operation
Power on/off : Press “” for 3 seconds to turn on/off the thermostat.
Temp setting: Rotate handwheel “” to change setting temperature by 0.5°C.
System mode: Press “” shortly to switch manual/auto mode. (Floor heating)
Press “” shortly to switch cooling/heating/ventilation. (Fan Coil)
Press “” shortly to switch cooling/heating/ventilation/floor heating/ floor heating + heating. (Integrated)
Enter menu: Press “” for 3 seconds to enter the menu interface.
Temp control mode: Press “” shortly to switch manual/auto mode. (Integrated, floor heating)
Child-lock: Press “” + “
” for 3 seconds to activate child-lock.
Wi-Fi setting
Press “” for 3 seconds to enter the menu page. Turn the knob “
“, choose ‘Wi-Fi setting”, and then choose ” Bluetooth Mode “, press “
” and confirm. The device enters the distribution network state.
Bluetooth Mode Access Point Mode
Timer Task Setting (Fan Coil/Integrated)
Under power-on status, long press menu button “” to enter the menu page, choose Auto Mode, then choose Schedule and set the parameters, press menu button “
” to return to the previous page. Finally, press wind speed button “
” to activate the timer switch function.
Advanced Setting (Usually for Professional Technicians)
Under power-on status, long press menu button “” to enter the menu page, choose Engineer Mode, enter the advanced setting page. After setting the parameters, press menu button “
” to save and exit.
function list |
Handwheel “![]() |
Default Value | Integrated | Fan Coil | Floor Heating | ||||
AWY | AC2-485 | AC4 | AC2 | EP | WP |
WPB |
|||
ModBus Address | Adjustment range 0~250 |
0 |
✔ | ✔ | ✔ | ✖ | ✔ | ✔ |
✔ |
Sensor Calibration | -9.9~9.9℃(-9.9~9.9℉) |
0℃ |
✔ | ✔ | ✔ | ✔ | ✔ | ✔ |
✔ |
Temp. Dif. | 0.5~10℃ (1~10℉) |
1℃ |
✔ | ✔ | ✔ | ✔ | ✔ | ✔ |
✔ |
Max Setting Value | 5~95℃ (41~203℉) |
50℃ |
✔ | ✔ | ✔ | ✔ | ✔ | ✔ |
✔ |
Min Setting Value | 5~47℃ (41~117℉) |
5℃ |
✔ | ✔ | ✔ | ✔ | ✔ | ✔ |
✔ |
Anti-Freeze Protection | ON/OFF |
OFF |
✔ | ✔ | ✔ | ✔ | ✔ | ✔ |
✔ |
Temperature Unit | ℃/℉ |
℃ |
✔ | ✔ | ✔ | ✔ | ✔ | ✔ |
✔ |
Sensor Mode | Built-in sensor Floor sensor Built-in Control & Floor Limitation |
IN |
✔ | ✖ | ✖ | ✖ | ✔ | ✔ |
✔ |
Floor limited Value | 20~90℃ (68~194℉) |
35℃ |
✔ | ✖ | ✖ | ✖ | ✔ | ✔ |
✔ |
Weekday Mode | Monday to Friday Monday to Saturday Monday to Sunday |
2-day |
✔ | ✖ | ✖ | ✖ | ✔ | ✔ |
✔ |
Fan control settings | 00: Fan speed controllable 01: Fan speed uncontrollable |
00 |
✔ | ✔ | ✔ | ✔ | ✖ | ✖ |
✖ |
Linkage Time Delay | 0~5min |
0min |
✔ | ✖ | ✖ | ✖ | ✔ | ✔ |
✔ |
Child-lock Type | None Lock All All but power |
None |
✔ | ✔ | ✔ | ✔ | ✔ | ✔ |
✔ |
Boot Type | Function Off Function On Function Saved |
Last |
✔ | ✔ | ✔ | ✔ | ✔ | ✔ |
✔ |
Air-Condition Mode | All/Cold Only |
All |
✔ | ✔ | ✔ | ✔ | ✖ | ✖ |
✖ |
Temp Control | Manual/Auto |
Manual |
✔ | ✖ | ✖ | ✖ | ✖ | ✖ |
✖ |
Reset All Settings | Yes/No |
/ |
✔ | ✔ | ✔ | ✔ | ✔ | ✔ |
✔ |
Installation instructions
Auto-mode Setting (Floor Heating/Integrated)
Under power-on status, long press menu button “” to enter the menu page, choose Auto Mode, then choose Weekly Programming and set the period parameters, press menu button “
” to save and exit.
Events |
Time | Temperature | |||
Default value | Modify | Default value |
Modify |
||
Workdays |
Sunrise | 06:00 | ![]() |
20℃ | ![]() |
Morning | 08:00 |
15℃ |
|||
Nooning |
11:30 | 15℃ | |||
Afternoon | 12:30 |
15℃ |
|||
Evening |
17:00 | 22℃ | |||
Night | 22:00 |
15℃ |
|||
Weekends |
Sunrise | 08:00 | 20℃ | ||
Night | 22:00 |
15℃ |
Dimensions (Unit: mm)
Floor Heating #EP #WP #WPB Fan Coil #AC2 ![]() ![]() |
Fan Coil #AC2-485 #AC4 Integrated #AWY ![]() ![]() |
Mounting Steps
The thermostat adopt pre-guide and limited snap-fit design. It is easy to mount.
1) Release front cover by inserting a head screw-driver into bottom crack.
2) Insert the wires and then fix these wires with screws. Suggested wire-stripping length is 7-9mm.
3) Mount backing plate into wall-cassette, put screws and then fix thermostat.
Make sure that the thermostat is fixed without deformation. Suggested torque is 0.2~0.4N.m (2.0~4. 1kgf.cm).
4) Re-mount the front cover via snap-fit connection.
Sensor failure
Please select work mode of sensors correctly. When it shows Er0/Er1 error, thermostat will stay power-off till the error is eliminated. Er0: built-in sensor is short-circuited or disconnected. Er1: floor sensor is short-circuited or disconnected.
Connecting Diagram
The thermostat operates in full capacity in areas with the altitude of less than 2500 above sea level. Power rating of external load should be less than or equal to 80% rated power of the thermostat in areas with altitude of 2500m to 4200m.
Floor Heating
#TCR7-WIF-EP #TCR7-WIFI-WP (1) a) Normally-closed electric actuator (2) a) Normally-open electric actuator (3) a) Three-wire electrical ball valve |
Fan Coil
#TCR7-WIFI-AC2 a) Air conditioner valve #TCR7-WIFI-AC2-485 a) Air conditioner valve #TCR7-WIFI-AC4 a) Heat valve |
Integrated
#TCR7-WIFI-AWY a) Floor system valve |
Documents / Resources
![]() |
BEOK CONTROLS TCR7 IPS Colorful LCD Screen Smart Thermostat [pdf] Owner's Manual TCR7, TCR7 IPS Colorful LCD Screen Smart Thermostat, IPS Colorful LCD Screen Smart Thermostat, Colorful LCD Screen Smart Thermostat, LCD Screen Smart Thermostat, Screen Smart Thermostat, Smart Thermostat, Thermostat |