KRD Cake Showcase

Functional characteristics
Small integrated fuselage temperature control/refrigeration/lighting/fan/defrosting/high and low temperature alarm/locking/self-diagnosis Second, the technical parameters
- Power supply: ~ 220VAC50/60hz
- Temperature sensor: NTC1 strips (regardless of positive or negative) are 2m long.
- Temperature display range:-35℃ ~ 45℃ with accuracy of 0 1℃
- Temperature control range:-35℃ ~ 45℃ The factory value is 02℃
Appearance dimensions: 150mm (length) ×94mm (width) ×67mm (depth)
Opening size: 86mm (length) ×143mm (width) - Working environment temperature:-10 ~ 60℃; Relative humidity: 20% ~ 90% (no condensation)
- Contact capacity of relay: compressor: 20A/250VAC (the maximum can be connected with a 1P compressor, and external AC contactor is required if it exceeds 1P) Lighting: 10A/250VAC Fan: 10A/250VAC.
Demisting: 10A/250VAC
Third, the panel operation
- Control temperature setting: press
key to display the shutdown temperature, press
key to change the control temperature, without pressing any key, return to display the warehouse temperature and save the parameters. (First power on, press the key to skip the press delay) - Parameter setting: press the
key for six seconds before entering the setting program, that is, E1 will be displayed.
Press the key
to select the menu for setting E1-P1 and other parameters. Press
to enter the corresponding parameters. If no key is pressed within six seconds, the normal operation mode will be returned. - Parameter locking: lONg
press to show “OFF” for locking and “on” for unlocking. Indicates that it is currently locked. If you need to adjust the parameters, unlock them first and then adjust them. - Modify the factory setting value: press
to enter the temperature setting interface, adjust the control temperature, and after exiting the display state, press
for a long time to enter the parameter setting interface and adjust the parameters, and then press
to display any characters of E1 ~ P1, and press
for six seconds to display “COP”, and store the modified control temperature and parameter setting value as the current factory setting value. - On/off function: press and hold the
key for 6 seconds to realize the off function, and the display screen will display “-“and turn off other output states except lighting; - Restore the factory settings: In the power-off state, press and hold the
key for 6 seconds, and “888” will be displayed, indicating that the factory settings are successfully restored. Note: If it is unlocked, unlock it first. - Refrigeration indicator light: During refrigeration, the refrigeration indicator light is on; The constant temperature refrigeration indicator goes out; During the delay, the indicator light flashes.
Lighting indicator: During the lighting work, the lighting indicator lights up and turns off when it is turned off.
Fan indicator light: During the operation of the fan, the fan indicator light is on, and it goes out when it is turned off. - Lighting indicator: Press the
key to start or stop lighting. - Defrosting indicator: You can enter or exit the defrosting state by pressing the
defrosting button for six seconds.
| code | function | Set range | Factory setting | code | function | Set range | Factory setting | |
| E1 | Minimum control temperature | -45℃ ~ control temperature | 00℃ |
F3 |
Temperature display during defrosting |
0= Library temperature is
displayed normally. |
one |
|
|
E2 |
Maximum control temperature | Control the
temperature to 80℃ |
30℃ |
1= Temperature at the beginning of defrosting. | ||||
|
E3 |
Temperature return difference |
1~15℃ |
6℃ |
C1 |
High
temperature alarm value |
C2 parameter ~ 80℃ |
45℃ |
|
|
E4 |
Delayed start time |
0 ~ 10 minutes |
3 minutes |
C2 |
Low
temperature alarm value |
-45℃ ~ C1 parameter |
﹣40℃ |
|
|
E5 |
Calibration of
library temperature probe |
– 15~15℃ |
0 |
C3 |
Alarm delay time |
0 ~ 90 minutes |
3 minutes |
|
F1 |
Defrosting time |
1 ~ 90 minutes |
15 minutes |
H1 |
Fan control | H1 = 01 Synchronize with the compressor and start when
defrosting. |
2 | |
|
F2 |
Defrosting interval |
0 ~ 24 hours
00= no defrosting |
4 hours |
H1=02 keeps running, and opens when defrosting. | ||||
| P1 | Demisting control | 00 ~ 180 minutes 00 is long. | 00 |
Program list
Function Description
- Temperature control: refrigeration: when the current temperature is more than or equal to the set temperature+ temperature back difference and delayed, the load relay will pull in. Refrigeration stop: when the current temperature is less than or equal to the set temperature, the load relay is disconnected.
- Defrosting function:
When the set time reaches the shutdown defrosting interval (F2), enter the shutdown defrosting function to stop the current compressor; When the defrosting time (F1) is met, the shutdown defrosting mode is exited, and the compressor is started in a delayed mode, and the refrigeration operation mode is entered.
Lock the display of warehouse temperature during defrosting: when F3=01 is locked, lock the temperature in the warehouse during defrosting and display the temperature at the beginning of defrosting. After defrosting, unlock and resume displaying the normal probe temperature. - Fan control: the fan runs according to the set value of parameter (H1). When the fan is synchronized with the compressor, it will take 3 seconds to start the fan after the compressor starts.
- Fault running time: When the temperature sensor fails, the compressor stops for 15 minutes
and runs for 15 minutes.
| Fault code | Fault description | Mode of operation |
| E-1 | Short circuit of library temperature probe | The compressor is stopped for 15 minutes and turned on for 15
minutes. Cyclic work |
| E-2 | Open circuit of library temperature probe | |
| HHH | The high temperature of the library temperature probe exceeds C1 set value. | Check whether C1/C2 is misaligned. |
| LLL | Low temperature of reservoir
temperature probe is lower than C2 set value. |
- Alarm mode:
High temperature alarm: When the probe temperature is ≥C1, the display of “HHH” flashes alternately with the current temperature, and pressing any key can eliminate the alarm sound. Low temperature alarm: When the prob e temperature is ≤C2, the display “LLL” flashes alternately with the current temperature, and pressing any key c an eliminate the alarm sound. The probe shows E-1 for short circuit, and “E-2” for open circuit or overrun.
Six, wiring diagram

Note:
- The thermostat can’t be installed where there is dripping water.
- The probe should be installed with the head up and the line down.
- In order to prevent high-frequency dry burning, the probe wire should not be tied in parallel with the power cord, but should be wired separately
KRD CATERING EQUIPMENTS LTD
www.krdcatering.co.uk
FAQ
How can I restore factory settings?
Press the key to display the shutdown temperature, then use the up or down key to change the control temperature.