komfovent BACnet Connection C6 Controller Installation Guide

BACNET CONNECTION AND SETTINGS

BACnetis a standard communication protocol for Building Automation and Control (BAC) networks that can be used to monitor and control Komfovent air handling units with C6 controller. The supported Data Link Layer is BACnet / IP. BACnet protocol works via Ethernet interface, connection is provided to RJ-45 socket (Pic.1) on the C6 controller (CAT5 cable is recommended):

Picture 1. C6 controller board

Below is default network settings of the C6 controller. These can be changed according to the building network software requirements.
To do so, it is needed to connect a laptop to the integrated webserver of C6 controller:

           Picture 2. Connectivity settings

C6 controller IP can also be viewed and changed on the control panel – from Main menu go to Advanced settings- >Connectivity:

Picture 3. Connectivity settings on C6.1 control panel display

BACnet Interoperability Building Blocks Supported
 

Data sharing

DS-RP-B Read Property
DS-RPM-B Read Property Multiple
DS-WP-B Write Property
 

 

Device management

DM-DCC-B Device Communication Control
DM-DDB-B Dynamic Device Binding
DM-DOB-B Dynamic Object Binding
DM-TS-B Time Synchronization
Standard Object Types Supported:
Object type Properties
Device Object_Identifier, Object_Name, Object_Type, System_Status, Vendor_Name, Vendor_Identifier, Model_Name, Firmware_Revision, Application_Software_Version, Protocol_Version, Protocol_Revision, Protocol_Services_Supported, Protocol_Object_Types_Supported, Object_List, Max_APDU_Length_ Accepted, Segmentation_Supported, APDU_Timeout, Number_Of_APDU_Retries, Device_Address_ Binding, Database_Revision, Property_List; Description, Local_Date, Local_Time
Analog value Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_ Service, Units, Property_List; Reliability
Binary value Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_ Service, Property_List; Incative_Text, Active_Text
Date value Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Property_List
Multi-state value Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_ Service, Number_Of_States, Property_List; State_Text
Positive integer value Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Units, Property_List; Reliability
Time value Object_Identifier, Object_Name, Object_Type, Present_Value, Status_Flags, Property_List

Objects:

Analog value
 

Object name

Object instance Present value
Range/values/units Access
AWAY: setpoint 0 5.0 – 40.0 [°C] W
NORMAL: setpoint 1 5.0 – 40.0 [°C] W
INTENSIVE: setpoint 2 5.0 – 40.0 [°C] W
BOOST: setpoint 3 5.0 – 40.0 [°C] W
KITCHEN: setpoint 4 5.0 – 40.0 [°C] W
Analog value
 

Object name

Object instance Present value
Range/values/units Access
FIREPLACE: setpoint 5 5.0 – 40.0 [°C] W
OVERRIDE: setpoint 6 5.0 – 40.0 [°C] W
HOLIDAYS: setpoint 7 5.0 – 40.0 [°C] W
ECO: minimum supply air temperature 8 5.0 – 40.0 [°C] W
ECO: maximum supply air temperature 9 5.0 – 40.0 [°C] W
AIR QUALITY: temperature setpoint 10 5.0 – 40.0 [°C] W
INFO: supply temperature 11 [°C] R
INFO: extract temperature 12 [°C] R
INFO: outdoor temperature 13 [°C] R
INFO: water temperature 14 [°C] R
INFO: panel 1 temperature 15 [°C] R
INFO: panel 2 temperature 16 [°C] R
INFO: current supply fan intensivity 17 [°C] R
INFO: current extract fan intensivity 18 [°C] R
INFO: heat exchanger 19 [°C] R
INFO: electric heater 20 [°C] R
INFO: water heater 21 [°C] R
INFO: water cooler 22 [°C] R
INFO: DX unit 23 [°C] R
EFFICIENCY/STATUS: SPI 24 [W/(m3/h)] R
EFFICIENCY/STATUS: SPI (day) 25 [W/(m3/h)] R
Binary value
 

Object name

Object instance Present value
Range/values/units Access
CONTROL: ON/OFF status 0 0 – off 1 – on W
CONTROL: ECO mode 1 0 – off 1 – on W
CONTROL: AUTO mode 2 0 – off 1 – on W
AWAY: heating 3 0 – off 1 – on W
NORMAL: heating 4 0 – off 1 – on W
INTENSIVE: heating 5 0 – off 1 – on W
BOOST: heating 6 0 – off 1 – on W
KITCHEN: heating 7 0 – off 1 – on W
FIREPLACE: heating 8 0 – off 1 – on W
OVERRIDE: heating 9 0 – off 1 – on W
HOLIDAYS: heating 10 0 – off 1 – on W
ECO: free heating/cooling 11 0 – off 1 – on W
ECO: heating enable denied 12 0 – off 1 – on W
ECO: cooling enable denied 13 0 – off 1 – on W
AIR QUALITY: enabled 14 0 – disabled 1 – enabled W
AIR QUALITY: heating 15 0 – off 1 – on W
ALARMS: low supply air flow 16 0 – no 1 – yes R
ALARMS: low extract air flow 17 0 – no 1 – yes R
ALARMS: return water temperature low 18 0 – no 1 – yes R
ALARMS: low supply air temperature 19 0 – no 1 – yes R
ALARMS: high supply air temperature 20 0 – no 1 – yes R
Binary value
 

Object name

Object instance Present value
Range/values/units Access
ALARMS: electric heater overheat 21 0 – no 1 – yes R
ALARMS: heat exchanger failure 22 0 – no 1 – yes R
ALARMS: heat exchanger icing 23 0 – no 1 – yes R
ALARMS: internal fire alarm 24 0 – no 1 – yes R
ALARMS: external fire alarm 25 0 – no 1 – yes R
ALARMS: temperature sensor failure 26 0 – no 1 – yes R
ALARMS: controller failure 27 0 – no 1 – yes R
ALARMS: service mode 28 0 – no 1 – yes R
ALARMS: clogged air filters 29 0 – no 1 – yes R
ALARMS: heat exchanger low efficiency 30 0 – no 1 – yes R
ALARMS: air flow sensor failure 31 0 – no 1 – yes R
INFO: alarm 32 0 – off 1 – on R
INFO: heating 33 0 – off 1 – on R
INFO: cooling 34 0 – off 1 – on R
CLEAN FILTERS CALIBRATION 35 0 – no 1 – yes W
Date value
 

Object name

Object instance Present value
Range/values/units Access
HOLIDAYS: from 0 2017-01-01 – 2035-12-31 W
HOLIDAYS: till 1 2017-01-01 – 2035-12-31 W
Multi-state value
 

Object name

Object instance Present value
Range/values/units Access
CONTROL: auto mode control 0 1 – scheduling 2 – air quality R
 

 

CONTROL: current mode

 

 

1

1 – standby

2 – away

3 – normal

4 – intensive

5 – boost

6 – kitchen

7 – fireplace

8 – override

9 – holiday

10  – auto

11  – off

 

 

W [2-5]

SCHEDULER: operation program 2 1 – stay at home 2 – working week 3 – office

4 – custom

W
 

SCHEDULER: next mode

 

3

1 – standby

2 – away

3 – normal

4 – intensive

5 – boost

 

R

 

SCHEDULER: next mode weekday

 

4

1 – today

2 – mo

3 – tu

4 – we

5 – th

6 – fr

7 – sa

8 – su

 

R

CONTROL: temperature control 5 1 – supply

2 – extract

3 – room

4 – balance

W
CONTROL: flow control 6 1 – CAV

2 – VAV

3 – DCV W
CONTROL SEQEUENCE: stage 1 7  

1 – none

2 – external coil

 

3 – electric heater

4 – external DX unit

W
CONTROL SEQEUENCE: stage 2 8 W
CONTROL SEQEUENCE: stage 3 9 W
SETTINGS: coil type 10 1 – hot water 2 – cold water W
Multi-state value
 

Object name

Object instance Present value
Range/values/units Access
 

 

 

SETTINGS: language

 

 

 

11

1 – en

2 – lt

3 – ru

4 – pl

5 – sk

6 – de

7 – fr

8 – hu

9 – it

 

10  – ee

11  – nl

12  – lv

13  – pt

14  – se

15  – fi

16  – hr

 

 

 

W

SETTINGS: flow units 12 1 – m3/h 2 – l/s W
OVERRIDE: mode 13 1 – all time 2 – if on 3 – if off W
HOLIDAYS: microventilation 14 1 – 1 t. per day

2 – 2 t. per day

3 – 3 t. per day

4 – 4 t. per day

W
AIR QUALITY: sensor type B8 15 1 – none

2 – CO2

3 – VOC

4 – RH

W
AIR QUALITY: sensor type B9 16 W
 

 

RESET SETTINGS

 

 

17

1 – none

2 – “away”

3 – “normal”

4 – “intensive”

5 – “boost”

6 – “holidays”

7 – “override”

8 – “kitchen”

9 – “fireplace” 10 – air quality 11 – eco

12 – advanced

 

 

W

ECO: heat recovery control 18 1 – Auto

2 – Constant

3 – Non stop W
Positive integer value
 

Object name

Object instance Present value
Range/values/units Access
CONTROL: maximum supply flow 0 [m3/h, l/s] R
CONTROL: maximum extract flow 1 [m3/h, l/s] R
CONTROL: maximum supply pressure 2 0 – 1000 [Pa] W
CONTROL: maximum extract pressure 3 0 – 1000 [Pa] W
CONNECTIVITY: IP address 4 0 – 4294967295 W
CONNECTIVITY: mask 5 0 – 4294967295 W
AWAY: supply flow 6 0.2 max – max [m3/h, l/s, Pa] W
AWAY: extract flow 7 0.2 max – max [m3/h, l/s, Pa] W
NORMAL: supply flow 8 0.2 max – max [m3/h, l/s, Pa] W
NORMAL: extract flow 9 0.2 max – max [m3/h, l/s, Pa] W
INTENSIVE: supply flow 10 0.2 max – max [m3/h, l/s, Pa] W
INTENSIVE: extract flow 11 0.2 max – max [m3/h, l/s, Pa] W
BOOST: supply flow 12 0.2 max – max [m3/h, l/s, Pa] W
BOOST: extract flow 13 0.2 max – max [m3/h, l/s, Pa] W
KITCHEN: supply flow 14 0.2 max – max [m3/h, l/s] W
KITCHEN: extract flow 15 0.2 max – max [m3/h, l/s] W
FIREPLACE: supply flow 16 0.2 max – max [m3/h, l/s] W
FIREPLACE: extract flow 17 0.2 max – max [m3/h, l/s] W
OVERRIDE: supply flow 18 0.2 max – max [m3/h, l/s] W
OVERRIDE: extract flow 19 0.2 max – max [m3/h, l/s] W
KITCHEN: timer 20 0 – 300 [min] W
FIREPLACE: timer 21 0 – 300 [min] W
OVERRIDE: timer 22 0 – 300 [min] W
Positive integer value
 

Object name

Object instance Present value
Range/values/units Access
AIR QUALITY: air quality setpoint 23 0 – 2000 [ppm]

0 – 100 [%]

W
AIR QUALITY: humidity setpoint 24 0 – 100 [%] W
AIR QUALITY: minimum intensivity 25 0, 20 – 100 [%] W
AIR QUALITY: maximum intensivity 26 0, 20 – 100 [%] W
AIR QUALITY: check period 27 1 – 24 [h] W
 

ALARMS: active alarms count

 

28

 

0 – 10

W [39366

resets alarms]

ALARMS: alarm history count 29 0 – 50 R
INFO: current supply flow 30 [m3/h, l/s] R
INFO: current extract flow 31 [m3/h, l/s] R
INFO: filters impurity 32 [%] R
INFO: air dampers 33 [%] R
INFO: supply pressure 34 [Pa] R
INFO: extract pressure 35 [Pa] R
INFO: air quality/humidity sensor 1 36 [ppm, %] R
INFO: air quality/humidity sensor 2 37 [ppm, %] R
INFO: panel 1 humidity 38 [%] R
INFO: panel 2 humidity 39 [%] R
INFO: panel 1 air quality 40 [ppm] R
INFO: panel 2 air quality 41 [ppm] R
EFFICIENCY/STATUS: power consumption 42 [W] R
EFFICIENCY/STATUS: heater power 43 [W] R
EFFICIENCY/STATUS: heat exchanger recovery 44 [W] R
EFFICIENCY/STATUS: heat exchanger efficiency 45 [%] R
EFFICIENCY/STATUS: energy saving 46 [%] R
EFFICIENCY/STATUS: recovered energy (day) 47 [Wh] R
EFFICIENCY/STATUS: recovered energy (month) 48 [Wh] R
EFFICIENCY/STATUS: recovered energy (total) 49 [Wh] R
CONSUMPTION: AHU (day) 50 [Wh] R
CONSUMPTION: AHU (month) 51 [Wh] R
CONSUMPTION: AHU (total) 52 [Wh] R
CONSUMPTION: add. air heater (day) 53 [Wh] R
CONSUMPTION: add. air heater (month) 54 [Wh] R
CONSUMPTION: add. air heater (total) 55 [Wh] R
Time value
 

Object name

Object instance Present value
Range/values/units Access
SCHEDULER: next mode start time 0 00:00 – 24:00 R

UAB KOMFOVENT

SERVICE AND SUPPORT
Phone: +370 5 200 8000
service@komfovent.com

 

Read More About This Manual & Download PDF:

Documents / Resources

komfovent BACnet Connection C6 Controller [pdf] Installation Guide
BACnet Connection C6 Controller, BACnet, Connection C6 Controller, Connection, C6 Controller