Troubleshooting

THANK YOU Congratulations on your purchase and welcome to the KEPLERX logo Family. Your new KEPLERX logo Air Conditioner combines high-efficiency operation with portable convenience. By following the operating and care instructions in this manual, your air conditioner will provide you with many years of reliable service. Please visit our website www.keplerx.net For any questions or Technical Support, please contact us by mail info@keplerx.net or by phone 1-866-466-3451.

TROUBLESHOOTING

Parameter point check table

1. Top discharge outdoor unit
For 18S-EHV*24WD2V, 18S-EHV*36WD2V

KEPLERX 18SEER Condensing and Air Handler - discharge outdoor unit

Function description for the corresponding position:

No. Content No. Content
1 Compressor wiring terminal 12 High/Low pressure switch ports
2 DC fan motor wiring terminal 13 AC fan motor wiring terminal
3 Transformer 14 Four-way valve control port
4 Outdoor display board wiring terminal 15 Crankcase Heating zone control terminal
5 Reserved 16 Chassis Electric Heater control terminal
6 24V wire controller interface 17 Solenoid valve2 control terminal
7 EXV drive port 18 Power supply connecting terminal
8 Exhaust temperature sensor port(T5) 19 Power supply connecting terminal
9 Outdoor ambient temperature sensor port(T4) 20/21 Relay
10 Condenser temperature sensor port(T3) 22 Inductor wiring terminal 1
11 Pressure sensors ports 23 Inductor wiring terminal 2

For 18S-EHV*48WD2V, 18S-EHV*60WD2V

KEPLERX 18SEER Condensing and Air Handler - TROUBLESHOOTING

Function description for the corresponding position:

No. Content No. Content
1 Compressor wiring terminal 12 AC fan motor wiring terminal
2 DC fan motor wiring terminal 13 Four-way valve control port
3 Transformer 14 Crankcase Heating zone control terminal
4 Outdoor display board wiring terminal 15 Chassis Electric Heater control terminal
5 24V wire controller interface 16 Solenoid valve control terminal
6 EXV drive port 17 Power supply connecting terminal
7 Exhaust temperature sensor port(T5) 18 Power supply connecting terminal
8 Outdoor ambient temperature sensor port(T4) 19 Relay
9 Condenser temperature sensor port(T3) 20 Relay
10 Pressure sensors ports 21 Inductor wiring terminal 1
11 High/Low pressure switch ports 22 Inductor wiring terminal 2

2. Air handing unit
For 18S-EHV*24WD2H, 18S-EHV*36WD2H 18S-EHV*48WD2H 18S-EHV*60WD2H

KEPLERX 18SEER Condensing and Air Handler - Air handing unit

Function description for the corresponding position:

No. Content No. Content
1 DC fan motor wiring terminal 8 Output port of transformer(11V)
2 Reserved 9 Dip switch to adjust fan speed
3 Chassis Electric Heater control terminal 10 Power supply connecting terminal(L1)
4 Reserved 11 Fan power cord input port(L1)
5 24V wire controller interface 12 Input power cord transformer port
6 Output port of transformer(24V) 13 Power supply connecting terminal(L2)
7 Fuse 14 Fan power cord input port(L2)

Error code
(1) The error codes for outdoor unit as follows:

Definitions of malfunction Error code
T4 Outdoor ambient temperature sensor error E4
T5 Discharge temperature sensor error E5
T3 Condenser temperature sensor error E6
AC under voltage protection E9
EEPROM error E10
IPM modular sensor error E12
HLP Pressure sensor error E13
T3 or T5 sensor disconnect error E14
High pressure switch error E15
Communication error of main chip and IPM chip H0
T3 sensor high temperature error(In cooling mode, 20 times P5 error within 180mins) H1
High pressure switch error(20 times P1 error within 150 mins) H2
High pressure abnormal in heating mode (20 times P13 error within 180 mins) H3
IPM modular high temp error (20 times P8 within 120 mins) H4
Low pressure error (20 times P2 within 100 mins) H5
Discharge temperature abnormal error(20 times P4 within 100 mins) H6
Wet operation error (20 times P12 within 200 mins) H7
T3 condenser sensor disconnect error (20 times E14 within 100 mins) H8
Discharge temp sensor disconnect error(20 times E14 within 180 mins) H12
High pressure protection P1
Low pressure protection P2
DC over current protection P3
T5 Discharge temperature abnormal error P4
T3 Condenser sensor high temp protection(In cooling mode) P5
IPM module protection P6
IPM high temperature protection (Ft)M high temperature protection (Ft) P8
DC fan motor error P9
Wet operation error P12
High pressure abnormal error(In heating mode) P13
High compression ratio protection P14
Low compression ratio protection P15
DC cable bus low voltage protection L1
DC cable bus high voltage protection L2
MCE fault / sync / closed loop L4
Zero speed protection L5
Compressor phase loss protection ratio protection L7
Compressor stalls L8
Frequency limitation or decline by high pressure L9
Frequency limitation by voltage LA
Frequency limitation by condenser temp. LC
Frequency limitation by discharge temp LD
Frequency limitation by IPM modular high temp LE
Frequency limitation by current LF
Oil return d0
Defrost dF
Force cooling dH

(2) Troubleshooting by error code

E4/E5/E6 (T4/T5/T3 temperature sensors error)
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - error code
E10 (EEPROM failure)
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - EEPROM failure
E9 ( AC under voltage protection )
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - AC under voltage protection
E12 (IPM modular sensor error)
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - modular sensor error
E13 (HLP Pressure sensor error)
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - Pressure sensor error
E14/H8/H12 (T3 or T5 sensor disconnect error )
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - sensor disconnect error
E15 ( High pressure switch error )
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - High pressure switch error
H0 (Communication error of main chip and IPM chip )
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - Communication error of main
P1/H2 ( High pressure switch protection )
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - pressure switch protection
P2/H5 (Low pressure switch protection)
Diagnosis Handing
KEPLERX 18SEER Condensing and Air Handler - pressure switch protection 2
P5/H1( T3 condenser sensor high temp protection )
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - T3 condenser sensor
P6 (IPM module protection)
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - IPM module protection
P8/H4 (IPM high temperature protection)
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - IPM high temperature protection
P9 ( DC fan motor error )
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - DC fan motor error
P5/H1 (T3 condenser sensor high temp protection)
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - temp protection
P13/H3(High pressure abnormal error(In heating mode) )
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - pressure abnormal error
P14 (High compression ratio protection)
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - High compression ratio
P15 (Low compression ratio protection)
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - compression ratio protection
L1/L2 (DC cable bus low/high voltage protection)
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - DC cable bus
L4-L8 (IPM module subdivision protection)
Diagnosis Handling
KEPLERX 18SEER Condensing and Air Handler - IPM module subdivisionL9-LE (Frequency limitation protection, not error)

Exploded views and part list

Air Handler Indoor unit

KEPLERX 18SEER Condensing and Air Handler - Air Handler Indoor unit

No. Part     Name Quantity No. Part     Name Quantity
1 Filter Cover plate 1 3.8 Evaporator Bafle 1
2 Water pan components 1 3.9 Evaporator Water Bafle #1 2
2.1 Water pan# 1 1 3.10 Evaporator Water Bafle #2 1
2.2 Water pan# 2 1 3.11 Evaporator Water Bafle #3 1
2.3 Water pan fixed block 1 3.12 Evaporator Fixing Plate #1 1
2.4 Water pan brace 2 3.13 Evaporator Fixing Plate #2 1
3.1 Air header Assembly 1 3.14 Evaporator Junction Plate 2
3.2 Diverter Assembly 1 3.15 Evaporator Bafl eweld assembly 1
3.3 TXV 1 4 Chasiss assembly 1
3.4 Evaporator A 1 5 Supporter 2
3.5 Evaporator B 1 6.1 Right Volute Wind Wheel 1
3.6 Evaporator C 1 6.2 Indoor Motor 1
3.7 Evaporator D 1 7 Fan Motor Fixing plate assembly 1
No. Part     Name Quantity No. Part     Name Quantity
7.1 Fan Motor Fixing plate 1 9.1 ELectronic Control Mounting Plate 1
7.2 Wind Wheel Fixed Block 2 9.2 Main Board 1
7.3 Fixed plate on air duct 1 9.3 Transformer 1
7.4 Stator 2 10 Water pan supporter assembly 4
7.5 air duct left stationary plate 1 11 Upper side plate assembly 1
7.6 air duct right stationary plate 1 12 Pipe Cover plate assembly 1
8 Electric control cover foam assembly 1 13 Lower side plate assembly 1
9 ELectronic Control Components 2

Top discharge outdoor unit

KEPLERX 18SEER Condensing and Air Handler - Top discharge outdoor unit

No. Part     Name Quantity No. Part Name Quantity
1 Cover net 1 6 Rear side panel 1
2 Outdoor motor 1 7 Left side panel 1
3 Axial-flow fan 1 8 Piping support plate 2
4 Top cover assembly 1 9 Cooling pipe components of refri 1
5 Support board 3 10 Return pipe welding assembly 1
No. Part Name Quantity No. Part Name Quantity
11 Gas liquid separator 1 16.3.2.3 Pressure sensor 1
12 Top panel 1 16.3.3 Four-way valve connecting pipe #2 1
13 Compressor 1 16.3.4 Four-way valve connecting pipe #3 1
14 Chassis assembly 1 16.3.5 Coil of four-way valve 1
15 Left side panel 1 17 Radiator cover 1
16.1 High pressure valve welding assembly 1 18 Electronic components 1
16.1.1 High pressure valve connecting pipe 1 18.1 Outdoor communication display board 1
16.1.2 Square valve 1 18.2 Reactor 1
16.2 Electronic expansion valve assembly 1 18.3 Fan motor capacitance 1
16.2.1 Check valve 1 18.4 Electronically controlled mounting plate assy 1
16.2.2 Two-way filter 2 18.5 Reactor mount 1
16.2.3 Electronic expansion valve 1 18.6 Main control board mounting base 1
16.2.4 L-shaped tube 1 18.7 Communication board mounting base 1
16.2.5 Coil of electronic expansion valve 1 18.8 Terminal block mounting plate 1
16.3 Four way valve assembly 1 18.9 Terminal block 1
16.3.1 Four way valve 1 18.10 Reactor mounting cover welded parts 1
16.3.2 Four-way valve connecting pipe #1 assy 1 18.11 Outdoor inverter integrated board 1
16.3.2.1 Pressure Switch 1 20 Condenser parts 1
16.3.2.2 Four-way valve connecting pipe #1 1 20.2 Condenser assembly 1
16.3.2 Four-way valve connecting pipe #4 assy 1 20.1 Condenser input pipe assembly 1
16.3.2.1 Square valve 1 21 Right side panel 1
16.3.2.2 Four-way valve connecting pipe #4 1

KEPLERX 18SEER Condensing and Air Handler - logoKeplerX Co.Ltd
120 US Route 46,
Parsippany, NJ 07054
Toll Free 1-866-466-3451

Documents / Resources

KEPLERX 18SEER Condensing and Air Handler [pdf] Instruction Manual
18S-EHVC WD2V, 18S-EHVC WD2H, 18S-EHVH WD2V, 18S-EHVH WD2H, 18SEER Condensing and Air Handler, 18SEER, Condensing and Air Handler, Air Handler, Handler

References

Leave a comment

Your email address will not be published. Required fields are marked *