FP4151TN-V2 QUICK START GUIDE
Product Code: FP4151TN-V2: 15", 1024 x 768, XGA Color TFT with 4-wire analog resistive touch screen with 2 communication ports, one USB Device port, one USB Host port & 1 Ethernet Port.
GETTING STARTED
User should follow the given sequence to configure and use any FlexiPanels series unit:
- Install FlexiSoft Software.
- Create a PZM application using FlexiSoft software.
- Connect programming cable.
- Download Firmware i.e. driver for the HMI.
- Download application.
- Now FP unit is ready to use in the system.
For more information, visit www.renuelectronics.com
SPECIFICATIONS
Parameter | Details |
Power (Base) | 24VDC (+20%), 600mA, 14.4W |
Display | 15", 1024 x 768pixels, XGA color TFT with 4-wire analog resistive touch screen |
LEDs | 1 |
RAM Memory | 512MB |
User Application | Up to 1GB that includes user application, data log, alarms, retentive memory and logic memory |
eMMC | 4GB |
RTC | Built-in, date and time function |
Weight | Approx. 3Kg |
Product Dimensions | 402.3(W) x 287.0(H) x 67.5(D)mm |
Panel Cut-out | 388.0(W) x 287.0(H)mm |
LCD | Backlight life: Module Typical 70,000 h LED life time: Minimum 50,000h Luminance: Minimum 320 cd/m2 (Typical 400 cd/m2) |
Communication | |
COM1 and COM2 | RS232/RS485 |
USB Ports | 1 USB Type C Port and 1 USB Host Port |
Ethernet | 1 Ethernet Port Default IP Address & Subnet Mask: Auto |
SD Card | Micro SD [High Capacity (4GB to 32GB)] Speed Class: @@@@ [While inserting and removing SD card, please make sure to TURNOFF the power to the unit.] |
Environment & Approvals | |
Operating Temperature | 0° to 60°C* |
Storage Temperature | -30° to 85°C |
Humidity | 10 to 90% (Non-Condensing) |
Shock | IEC 60068-2-27 25g, 11ms, 6 shocks per axis, total 18 shocks (X, Y, Z) |
Vibration | IEC 60068-2-6 5 to 150Hz, 3g peak (X, Y, Z) |
EMC | EN 55011: 2009/A1: 2010 EN 61131-2:2007 EN 61000-6-2: 2005/AC: 2005 EN 61000-6-4: 2007/A1: 2011 |
Protection | Front panel-IP66, Rear panel-IP20 |
APPROVALS | CE, UL(Class1 Div2), UKCA, REACH & ROHS [*Note: For UL, operating temperature range is 0° to 50°C.] |
PRODUCT DIMENSIONS
A diagram showing the front, right side, top, and bottom views of the FP4151TN-V2 unit with dimensions labeled.
Front View: 402.3(W) x 287.0(H) x 67.5(D)mm
Right Side View: 67.5mm depth
Top View: 402.3(W) x 301.3(H)mm
Bottom View: 402.3(W) x 301.3(H)mm
WARNINGS
- This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-hazardous locations only.
- WARNING - EXPLOSION HAZARD - Do not disconnect equipment unless power has been removed or the area is known to be non-hazardous.
- WARNING - EXPLOSION HAZARD - Substitution of components may impair suitability for Class I, Division 2.
- WARNING CAUTION, Battery May Explode If Mistreated. Do Not Recharge, Disassemble or Dispose of in Fire.
- The list of materials used in the construction of these devices with name of sealed device - generic name of the material and the supplier's name and type designation.
- It is recommended that the user periodically inspect the sealed devices used, for any degradation of properties and Replace the device if any degradation is found.
COMMUNICATION INTERFACES
This section provides information regarding communication interfaces supported by this product.
COM1 & COM2: RS485/RS232
A diagram showing the pinout for RS232 and RS485 connections.
RS232 Pinout:
Pin number | Signal |
2 | TXD(RS232) |
3 | RXD(RS232) |
5 | GND |
RS485 Pinout:
Pin number | Signal |
2 | TX+(RS422/RS485) |
3 | RX+(RS422/RS485) |
7 | NC |
8 | TX-(RS422/RS485) |
9 | RX-(RS422/RS485) |
Ethernet Port
- Fully compliant with IEEE 802.3 / 802.3u standards.
- 10/100 Mbps support.
- Connector used: Standard shielded RJ-45 female jack with in-built speed and link activity indication LEDs.
USB Device Port
- USB Device port, compliant with USB2.0 specification, self-powered device.
- Connector used: Micro USB Type C Female connector.
USB Host Port
- USB Host, compliant with USB 2.0 specification.
- USB Host can be used to transfer logged data and historical alarm to USB memory stick.
- USB Host can handle only USB memory stick devices and can source current up to 150mA only.
- Connector used: Standard USB Type a Female connector.
Cable Diagrams
Diagrams illustrating PC to unit programming cable (RS232) and 2-wire and 4-wire RS485 connections.
Earthing
The optimum method for Earthing electronic equipment is to earth it separately from other high-power systems, to earth more than one unit of electronic equipment with a single-point earth. The Earthing marked terminal (see below) is provided on the unit.
A diagram shows DC+, DC-, and Earth terminals for 24Vdc power input.
[Note: Do not use an earth that has an unstable impedance, such as painted screws or earth subject to vibration.]
UL APPROVAL
Information regarding UL approval for hazardous and non-hazardous locations, including Class I Division 2 Groups A B C and D. Details on associated apparatus, capacitance, and inductance values are provided.
REVISION HISTORY
Rev. | Description | Date |
1.2 | Specification updated | 09/06/2025 |
1.1 | Control cable details removed, RENU logo updated | 06/06/2022 |
1.0 | First Draft | 21/10/2021 |
RENU Electronics Pvt. Ltd. reserves the right to change or discontinue specifications and features without prior notice. To view the latest and updated datasheets/manuals please visit www.renuelectronics.com.
File Info : application/pdf, 2 Pages, 1.03MB
DocumentDocumentReferences
Microsoft Word 2010 Microsoft Word 2010Related Documents
![]() |
RENU FlexiPanels FP4 Advanced HMI Series Datasheet Datasheet for RENU FlexiPanels FP4 Advanced HMI series, detailing features, specifications, application examples, supported protocols, ordering information, and dimensions for models FP4043CN, FP4070CN, and FP4101CN. |
![]() |
FlexiPanels FP2 V2 Basic HMI Series: Technical Specifications and Features Explore the FlexiPanels FP2 V2 Basic HMI series, featuring a 4.3" color TFT display, robust connectivity options including RS232, RS485, USB, and Ethernet, and compliance with CE, UL Class I Div 2, RoHS, and IP66 standards. This document details model specifications, supported protocols, and application examples. |
![]() |
FlexiPanels FP2 V2 Basic HMI Series Datasheet Datasheet for the RENU FlexiPanels FP2 V2 Basic HMI series, featuring a 4.3" color TFT display, RS232/RS485 communication, and industrial approvals. |
![]() |
FlexiPanels FP2 V2 Basic HMI Series Datasheet Datasheet for the RENU FlexiPanels FP2 V2 Basic HMI series, featuring a 7" Color TFT display, analog resistive touch screen, and various communication options. |
![]() |
Renu FlexiPanels FP2 V2 Basic HMI Series Datasheet Datasheet for the Renu FlexiPanels FP2 V2 Basic HMI series, featuring a 7" TFT display, analog resistive touch screen, and various communication and environmental specifications. |
![]() |
RENU FP4101 Series: Industrial Touch Panel Quick Start Guide This guide introduces the RENU FP4101 Series industrial touch panels, detailing models like FP4101T and FP4101TN. It covers key specifications, connectivity options (USB Type C, Ethernet, RS232/RS485), getting started steps, and industrial certifications such as UL Class I Division 2. |
![]() |
FP2070TN-LE2016RP-A0402U FlexiPanels FP2 HMI Datasheet Detailed specifications and features of the RENU FlexiPanels FP2 FP2070TN-LE2016RP-A0402U, a 7-inch color TFT HMI with local and pluggable I/Os, offering advanced controller functions and robust connectivity. |
![]() |
WP6101TN Plus Quick Start Guide A quick start guide for the WP6101TN Plus Thin Client, detailing its specifications, product dimensions, panel cutout dimensions, communication interfaces, getting started steps, main settings, UL approval, and revision history. |