invt Good rive Series VFDs in Parallel Connection

Specifications:
- Power (kW): 560, 630, 710, 800, 1000, 1200, 1500, 2000, 2500, 3000
- Rated Input Current (A): Refer to manual for specific values
- Rated Output Current (A): Refer to manual for specific values
- Standard Weight: Refer to manual for specific values
Product Overview:
Goodrive series VFDs in parallel connection are designed for power expansion. The functions and performance are consistent with corresponding series VFDs.
- Product Model:
Refer to the manual for specific models and quantities based on power and voltage requirements. - Product Ratings:
Refer to the manual for detailed output power, input current, and output current ratings based on the specific model. - Product Dimensions and Weight:
Refer to the manual for detailed outline dimensions, package dimensions, standard weight, and gross weight based on power requirements.
Product Usage Instructions
Dimension Drawings:
Installation Dimension of Single VFD:
Refer to the manual for detailed installation dimensions of single VFDs based on power and voltage requirements.
Installation Dimension of VFDs in Parallel Connection (Recommended):
Note: The recommended parallel installation method facilitates air intake inside the product and dissipates heat better, but requires a relatively large installation space. Refer to the manual for detailed instructions.\
FAQ:
- Q: What is the purpose of connecting Goodrive series VFDs in parallel?
A: Goodrive series VFDs in parallel connection are designed for power expansion and maintaining consistent functions and performance with corresponding series VFDs. - Q: How should I determine the appropriate model and quantity for parallel connection?
A: Refer to the manual for the specific power requirements and corresponding models and quantities for parallel connection based on voltage needs.
Operation Manual
Goodrive Series
VFDs in Parallel Connection
SHENZHEN INVT ELECTRIC: C:O., LTD.
Preface
- Implementing a large-power parallel connection solution on the Goodrive series universal products can extend the product power range to 3000kW, meeting market demand.
- This manual applies to Goodrive series variable-frequency drives (VFDs).
- If the product is ultimately used for military affairs or weapon manufacture, comply with the export control regulations in the Foreign Trade Law of the People’s Republic of China and complete related formalities.
- The manual is subject to change without prior notice.
Product overview
Goodrive series VFDs in parallel connection are only designed for power expansion, and their functions and performance are completely consistent with the corresponding series VFDs.
Product model
| Power (kW) | 380V parallel VFD model | 660V parallel VFD model | ||
| Power (kW) | Qty | Power (kW) | Qty | |
| 560 | 280 | 2 | – | – |
| 630 | 315 | 2 | – | – |
| 710 | 355 | 2 | 355 | 2 |
| 800 | 400 | 2 | 400 | 2 |
| 1000 | 500 | 2 | 500 | 2 |
| 1200 | 400 | 3 | 630 | 2 |
| 1500 | 500 | 3 | 500 | 3 |
| 2000 | 500 | 4 | 500 | 4 |
| 2500 | 500 | 5 | 630 | 4 |
| 3000 | 500 | 6 | 630 | 5 |
Product ratings
Ratings of AC 3PH 380V(-15%)–440V(+10%)
| Rating output power (kW) | Rated input current (A) | Rated output current (A) |
| 560 | 1090 | 1060 |
| 630 | 1220 | 1200 |
| 710 | 1250 | 1300 |
| 800 | 1430 | 1440 |
| 1000 | 1780 | 1720 |
| 1200 | 2145 | 2160 |
| 1500 | 2670 | 2580 |
| 2000 | 3560 | 3440 |
| 2500 | 4450 | 4300 |
| 3000 | 5340 | 5160 |
Ratings of AC 3PH 520V(-15%)–690V(+10%)
| Rating output power (kW) | Rated input current (A) | Rated output current (A) |
| 710 | 720 | 760 |
| 800 | 822 | 860 |
| 1000 | 1036 | 1080 |
| 1200 | 1310 | 1360 |
Goodrive series VFDs in parallel connection
| Rating output power (kW) | Rated input current (A) | Rated output current (A) |
| 1500 | 1554 | 1620 |
| 2000 | 2072 | 2160 |
| 2500 | 2620 | 2720 |
| 3000 | 3275 | 3400 |
Product dimensions and weight
Dimensions and weight of AC 3PH 380V(-15%)–440V(+10%)
| Power (kW) | Outline dimensions W×H×D (mm) | Package dimensions W×H×D (mm) | Standard weight (kg) | Gross weight (kg) |
| 560 | 1447×1419.9×442.5 | 845×605×1625 | 432 | 492 |
| 630 | 462 | 522 | ||
| 710 |
1323×1900×636.3 |
855×795×2130 | 814 | 928 |
| 800 | 814 | 928 | ||
| 1000 | 820 | 934 | ||
| 1200 | 1956×1900×636.3 | 1221 | 1392 | |
| 1500 | 1230 | 1401 | ||
| 2000 | 2589×1900×636.3 | 1640 | 1868 | |
| 2500 | 3222×1900×636.3 | 2050 | 2335 | |
| 3000 | 3855×1900×636.3 | 2460 | 2802` |
Dimensions and weight of AC 3PH 520V(-15%)–690V(+10%)
| Power (kW) | Outline dimensions W×H×D (mm) | Package dimensions W×H×D (mm) | Standard weight (kg) | Gross weight (kg) |
| 710 | 1447×1419.9×442.5 | 845×605×1625 | 450 | 510 |
| 800 | 1323×1900×636.3 | 855×795×2130 | 820 | 934 |
| 1000 | 820 | 934 | ||
| 1200 | 820 | 934 | ||
| 1500 | 1956×1900×636.3 | 1230 | 1401 | |
| 2000 | 2589×1900×636.3 | 1640 | 1868 | |
| 2500 | 1640 | 1868 | ||
| 3000 | 3222×1900×636.3 | 2050 | 2335 |
Dimension drawings
Installation dimension of single VFD

Figure 2-1 Single-unit installation dimension for 380V 280–315kW and 660V 355 kW models 

Figure 2-2 Single-unit installation dimension for 380V 355–500kW and 660V 400–630kW models
|
Power (kW) |
380V single VFD (unit: mm) | ||||||||
| W1 | W2 | W3 | H1 | H2 | D1 | D2 | D3 | Hole diameter | |
| 280–315 | 749 | 685 | 719 | 1419.9 | 1356 | 442.5 | 429.5 | 350 | Ø 12 |
| 355–500 | 690 | 620 | 655 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| Power (kW) | 660V single VFD (unit: mm) | ||||||||
| W1 | W2 | W3 | H1 | H2 | D1 | D2 | D3 | Hole diameter | |
| 355 | 749 | 685 | 719 | 1419.9 | 1356 | 442.5 | 429.5 | 350 | Ø 12 |
| 400–630 | 690 | 620 | 655 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
Installation dimension of VFDs in parallel connection (recommended)
Note: The recommended parallel installation method facilitates air intake inside the product and dissipates heat better, but requires a relatively large installation space.

Figure 2-3 Parallel installation dimension for 380V 560–630kW and 660V 710kW models


Figure 2-4 Parallel installation dimension for 380V 710–3000kW and 660V 800–3000kW models
| Power (kW) | 380V VFDs in parallel (recommended) (unit: mm) | ||||||||||
| W1 | W2 | W3 | W4 | W5 | H1 | H2 | D1 | D2 | D3 | Installation hole | |
| 560–630 | 749 | 685 | 719 | 1503 | 35 | 1419.9 | 1356 | 442.5 | 429.5 | 350 | Ø 12 |
| 710–1000 | 690 | 620 | 655 | 1385 | 40 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 1200–1500 | 690 | 620 | 655 | 2080 | 40 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 2000 | 690 | 620 | 655 | 2775 | 40 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 2500 | 690 | 620 | 655 | 3470 | 40 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 3000 | 690 | 620 | 655 | 4165 | 40 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| Power (kW) | 660V VFDs in parallel (recommended) (unit: mm) | ||||||||||
| W1 | W2 | W3 | W4 | W5 | H1 | H2 | D1 | D2 | D3 | Installation hole | |
| 710 | 749 | 685 | 719 | 1503 | 35 | 1419.9 | 1356 | 442.5 | 429.5 | 350 | Ø 12 |
| 800–1200 | 690 | 620 | 655 | 1385 | 40 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 1500 | 690 | 620 | 655 | 2080 | 40 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 2000–2500 | 690 | 620 | 655 | 2775 | 40 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 3000 | 690 | 620 | 655 | 3470 | 40 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
Installation dimension of VFDs in parallel connection (installed closely)
Note: The closely installed method of VFD parallel connection has a smaller installation dimension, which may affect the product’s internal air intake but meet the product’s heat dissipation.

Figure 2-5 Parallel installation dimension for 380V 560–630kW and 660V 710kW models

Figure 2-6 Parallel installation dimension for 380V 710–3000kW and 660V 800–3000kW models
| Power (kW) | 380V VFDs in parallel (installed closely) (unit: mm) | |||||||||
| W1 | W2 | W3 | W4 | H1 | H2 | D1 | D2 | D3 | Installation hole | |
| 560–630 | 1447 | 1383 | 1417 | 13 | 1419.9 | 1356 | 442.5 | 429.5 | 350 | Ø 12 |
| 710–1000 | 1323 | 1253 | 1288 | 13 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 1200–1500 | 1956 | 1886 | 1921 | 13 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 2000 | 2589 | 2519 | 2554 | 13 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 2500 | 3222 | 3152 | 3187 | 13 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 3000 | 3855 | 3785 | 3820 | 13 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| Power (kW) | 660V VFDs in parallel (installed closely) (unit: mm) | |||||||||
| W1 | W2 | W3 | W4 | H1 | H2 | D1 | D2 | D3 | Installation hole | |
| 710 | 1447 | 1383 | 1417 | 13 | 1419.9 | 1356 | 442.5 | 429.5 | 350 | Ø 12 |
| 800–1200 | 1323 | 1253 | 1288 | 13 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 1500 | 1956 | 1886 | 1921 | 13 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 2000–2500 | 2589 | 2519 | 2554 | 13 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
| 3000 | 3222 | 3152 | 3187 | 13 | 1900 | – | 636.3 | 625.5 | 570 | Ø 12 |
Wiring diagram
Wiring diagram of the main circuit

|
|
|
|
|
|
| (+) bus length | ≈1700mm | ≈1700mm | ≈1700mm | ≈1700mm | ≈1700mm |
| (-) bus length | ≈1700mm | ≈1700mm | ≈1700mm | ≈1700mm | ≈1700mm |
Note:
- The number of VFDs in parallel connection depends on the actual power. A maximum of 6 VFDs are supported in parallel connection.
- Both the input and output terminals of the master and slaves need to be connected with parallel cables of equal length.
Wiring between the master and a slave (560kW–630kW)

Wiring between the master and a slave (710kW–3000kW)


Wiring diagram of control circuit
| Master | Master– Slave 1 | Master– Slave 2 | Master– Slave 3 | Master– Slave 4 | Master– Slave 5 | |
| 15-core serial port cable length | ≈960mm | ≈1910mm | ≈3220mm | ≈3220mm | ≈4740mm | ≈4740mm |
| Fiber optic length | ≈1010mm | ≈2100mm | ≈3420mm | ≈3420mm | ≈4940mm | ≈4940mm |

Daily inspection

Appendix A Optional peripheral accessories
Cable
Power cable
The sizes of the input power cables and motor cables must comply with local regulations.
- The input power cables and motor cables must be able to carry the corresponding load currents.
- The maximum temperature margin of the motor cables in continuous operation cannot be lower than 70°C.
The conductivity of the PE grounding conductor is the same as that of the phase conductor, that is, the cross-sectional areas are the same. To meet the EMC requirements stipulated in the CE standards, you must use symmetrical shielded cables as motor cables (as shown in the following figure).
Four-core cables can be used as input cables, but symmetrical shielded cables are recommended.
Compared with four-core cables, symmetrical shielded cables can reduce electromagnetic radiation as well as the current and loss of the motor cables.

Note: If the electrical conductivity of the motor cable shield layer does not meet the requirements, a separate PE conductor must be used.
To protect the conductors, the cross-sectional area of the shielded cables must be the same as that of the phase conductors if the cable and conductor are made of materials of the same type. This reduces grounding resistance, and thus improves impedance continuity.
To effectively restrict the emission and conduction of radio frequency (RF) interference, the conductivity of the shielded cable must at least be 1/10 of the conductivity of the phase conductor. This requirement can be well met by a copper or aluminum shield layer. The following figure shows the minimum requirement on motor cables of a VFD. The cable must consist of a layer of spiral-shaped copper strips. The denser the shield layer is, the more effectively the electromagnetic interference is restricted.

Control cable
All analog control cables and cables used for frequency input must be shielded cables. Analog signal cables need to be double-shielded twisted-pair cables (as shown in figure a). Use one separate shielded twisted pair for each signal. Do not use the same ground wire for different analog signals. 
Power cable routing
- For low-voltage digital signals, double-shielded cables are recommended, but shielded or unshielded twisted pairs (as shown in figure b) also can be used. For frequency signals, however, only shielded cables can be used.
- Relay cables need to be those with metal braided shield layers.
- Keypads need to be connected by using network cables. In complicated electromagnetic environments, shielded network cables are recommended.
- Note: Analog signals and digital signals cannot use the same cables, and their cables must be arranged separately.
- Dielectric withstand tests have been performed between the main circuit and housing of each VFD before delivery. In addition, the VFD has the internal voltage limiting circuit, which can automatically cut off the test voltage.
- Do not perform any voltage withstand or insulation resistance tests, such as high-voltage insulation tests or using a megameter to measure the insulation resistance, on the VFD or its components.
- Note: Before connecting the input power cable of the VFD, check the insulation conditions of the cable according to local regulations
A.1.3.1 AC 3PH 380V(-15%) – 440V(+10%)
| Power (kW) | 380V parallel VFD model | Recommended cable size of single VFD (mm²) | |||
| Power (kW) | Qty | RST UVW | PE | (+)(-) | |
| 560 | 280 | 2 | 2×150 | 150 | 2×150 |
| 630 | 315 | 2 | 2×150 | 150 | 2×150 |
| 710 | 355 | 2 | 2×185 | 185 | 2×185 |
| 800 | 400 | 2 | 3×150 | 2×120 | 3×150 |
| 1000 | 500 | 2 | 3×185 | 2×150 | 3×185 |
| 1200 | 400 | 3 | 3×150 | 2×120 | 3×150 |
| 1500 | 500 | 3 | 3×185 | 2×150 | 3×185 |
| 2000 | 500 | 4 | 3×185 | 2×150 | 3×185 |
| 2500 | 500 | 5 | 3×185 | 2×150 | 3×185 |
| 3000 | 500 | 6 | 3×185 | 2×150 | 3×185 |
AC 3PH 520V(-15%)–690V(+10%)
| Power (kW) | 660V parallel VFD model | Recommended cable size of single VFD (mm²) | |||
| Power (kW) | Qty | RST UVW | PE | (+)(-) | |
| 710 | 355 | 2 | 185 | 95 | 185 |
| 800 | 400 | 2 | 2×70 | 70 | 2×70 |
| 1000 | 500 | 2 | 2×120 | 120 | 2×120 |
| 1200 | 630 | 2 | 2×150 | 150 | 2×150 |
| 1500 | 500 | 3 | 2×120 | 120 | 2×120 |
| 2000 | 500 | 4 | 2×120 | 120 | 2×120 |
| 2500 | 630 | 4 | 2×150 | 150 | 2×150 |
| 3000 | 630 | 5 | 2×150 | 150 | 2×150 |
Note:
- The cables recommended for the main circuit need to be used in scenarios where the ambient temperature is lower than 40°C, the wiring distance is shorter than 100m, and the current is the rated current.
- The terminals P1, (+), PB, and (-) are used to connect to DC reactors and braking accessories.
Cable configuration
| Master | Slave 1 | Slave 2 | Slave 3 | Slave 4 | Slave 5 | |
| RST input cables | Prepared by the user | Prepared by the user | Prepared by the user | Prepared by the user | Prepared by the user | Prepared by the user |
| UVW output cables | Prepared by the user | Prepared by the user | Prepared by the user | Prepared by the user | Prepared by the user | Prepared by the user |
| Master | Master– Slave 1 |
|
|
|
|
|
| (+), (-) bus cable for parallelconnection | – | Standard | Standard | Standard | Standard | Standard |
| Master | Master– Slave 1 | Master– Slave 2 | Master– Slave 3 | Master– Slave 4 | Master– Slave 5 | |
| Optical fiber for parallel
connection |
Standard | Standard | Standard | Standard | Standard | Standard |
| 15-core serial port cable for parallel connection | Standard | Standard | Standard | Standard | Standard | Standard |
Breaker and electromagnetic contactor
The circuit breaker is mainly used to prevent electric shock accidents and short circuits to the ground that may cause leakage current fire. The electromagnetic contactor is mainly used to control the main circuit power on and off, which can effectively cut off the input power of the VFD in case of system failure to ensure safety.
According to the working principle and structure of breakers, if the manufacturer’s regulation is not followed, hot ionized gases may escape from the breaker enclosure when a short-circuit occurs. To ensure safe use, exercise caution when installing and placing the breaker, and follow the manufacturer’s instructions for operation.]
AC 3PH 380V(-15%)–440V(+10%)
The following table is the fuse and breaker model selection for a single VFD. The capacity of the fuse/breaker for a parallel product is twice the rated current of the parallel product. (For details about the rated current of each parallel product, see 1.2 Product ratings.)
| Power (kW) | Fuse (A) | Circuit breaker (A) | Contactor rated current (A) |
| 280 | 1000 | 800 | 630 |
| 315 | 1000 | 1000 | 800 |
| 355 | 1000 | 1000 | 800 |
| 400 | 1200 | 1000 | 1000 |
| 500 | 1400 | 1250 | 1000 |
Note: The accessory specifications described in the preceding table are ideal values. You can select accessories based on the actual market conditions, but try not to use those with lower values.
AC 3PH 520V(-15%)–690V(+10%)
The following table is the fuse and breaker model selection for a single VFD. The capacity of the fuse/breaker for a parallel product is twice the rated current of the parallel product. (For details about the rated current of each parallel product, see 1.2 Product ratings.)
| Power (kW) | Fuse (A) | Circuit breaker (A) | Contactor rated current (A) |
| 280 | 1000 | 800 | 630 |
| 315 | 1000 | 1000 | 800 |
| 355 | 1000 | 1000 | 800 |
| 400 | 1200 | 1000 | 1000 |
| 500 | 1400 | 1250 | 1000 |
Note: The accessory specifications described in the preceding table are ideal values. You can select accessories based on the actual market conditions, but try not to use those with lower values.
Reactor
When the voltage of the grid is high, the large current that flows into the input power circuit may damage rectifier components. You need to configure an AC reactor on the input side, which can also improve the current adjustment coefficient on the input side.
When the distance between the VFD and motor is longer than 50m, leakage current is excessive due to parasitic capacitive effect of the long cable to ground, and overcurrent protection of the VFD may be frequently triggered. To prevent this from happening and avoid damage to the motor insulator, compensation must be made by adding an output reactor.
DC reactors can be directly connected to the VFDs of 380V, 660V models in large-power parallel connection. DC reactors can improve the power factor, avoid damage to bridge rectifiers caused due to large input current of the VFD when large-capacity transformers are connected, and also avoid damage to the rectification circuit caused due to harmonics generated by grid voltage transients or phase-control loads. 

Reactors for AC 3PH 380V(-15%)–440V(+10%)
The following table is the reactor selection table for a single VFD.
| Power (kW) | Fuse (A) | Circuit breaker (A) | Contactor rated current (A) |
| 355 | 600 | 500 | 500 |
| 400 | 700 | 630 | 500 |
| 500 | 900 | 800 | 630 |
| 630 | 1000 | 1000 | 800 |
Note:
- The rated input voltage drop of input reactor is designed to 2%.
- The current adjustment coefficient on the input side of the VFD is higher than 90% after a DC reactor is configured.
- The rated output voltage drop of output reactor is designed to 1%.
- The DC reactor is an external accessory. You need to specify whether external or built-in accessories are needed in your purchase order.
Reactors for AC 3PH 520V(-15%)–690V(+10%)
The following table is the reactor selection table for a single VFD.
| Power (kW) | Input reactor | DC reactor | Output reactor |
| 280 | ACL2-280-4 (optional) | DCL2-280-4 (optional) | OCL2-280-4 (optional) |
| 315 | ACL2-315-4 (optional) | DCL2-315-4 (optional) | OCL2-315-4 (optional) |
| 355 | ACL2-350-4 (optional) | DCL2-400-4 (optional) | OCL2-350-4 (optional) |
| 400 | ACL2-400-4 (optional) | DCL2-400-4 (optional) | OCL2-400-4 (optional) |
| 500 | ACL2-500-4 (optional) | DCL2-500-4 (optional) | OCL2-500-4 (optional) |
Note:
- The rated input voltage drop of input reactor is designed to 2%.
- The current adjustment coefficient on the input side of the VFD is higher than 90% after a DC reactor is configured.
- The rated output voltage drop of output reactor is designed to 1%.
- The DC reactor is an external accessory. You need to specify whether external or built-in accessories are needed in your purchase order.
Filter
J10 is not connected in factory for the 380V 110kW and lower VFD models. Connect the J10 packaged with the manual if the requirements of level C3 need to be met. J10 is connected in factory for the 380V 132kW and higher VFD models, all of which meet the requirements of level C3.
Note:
- Do not connect C3 filters in IT power systems.
- Disconnect J10 in the following situations:
- The EMC filter is applicable to the neutral-grounded grid system. If it is used for the IT grid system (that is, non-neutral grounded grid system), disconnect J10.
- If leakage protection occurs during configuration of a residual-current circuit breaker, disconnect J10.
Interference filters on the input side can reduce the VFD interference on the surrounding devices.
Noise filters on the output side can decrease the radio noise caused by the cables between VFDs and motors and the leakage current of conducting wires.
We provide some of the filters for you to choose.
Filter model description

| Field | Description |
| A | FLT: VFD filter series |
| B |
|
| C |
|
| D | 3-digit code indicating the rated current. For example, 015 indicates 15 A. |
| E |
|
| F |
|
Filter model selection for AC 3PH 380V(-15%)–440V(+10%)
The following table is the filter selection table for a single VFD.
| Power (kW) | Input filter | Output filter |
| 280 | FLT-P04600L-B | FLT-L04600L-B |
| 315 | FLT-P04800L-B | FLT-L04800L-B |
| 355 | ||
| 400 | ||
| 500 | FLT-P041000L-B | FLT-L041000L-B |
Filter model selection for AC 3PH 520V(-15%)–690V(+10%)
The following table is the filter selection table for a single VFD.
| Power (kW) | Input filter | Output filter |
| 355 | FLT-P06400H-B | FLT-L06400H-B |
| 400 | FLT-P061000H-B | FLT-P061000H-B |
| 500 | ||
| 630 |
Note:
- The input EMI meets the C2 requirements after an input filter is configured.
- The preceding table describes external accessories. You need to specify the ones you choose when purchasing accessories.
- For the filter model selection for parallel products, please refer to the above filter selection table for a single VFD.
Braking system
Braking component selection
When the VFD driving a high-inertia load decelerates or needs to decelerate abruptly, the motor runs in the power generation state and transmits the load-carrying energy to the DC circuit of the VFD, causing the bus voltage of the VFD to rise. If the bus voltage exceeds a specific value, the VFD reports an overvoltage fault. To prevent this from happening, you need to configure braking components.
![]() |
|
![]() |
Connect the braking components to the VFD according to the wiring diagram. If the wiring is not properly performed, damage to the VFD or other devices may be caused. |
Braking units for AC 3PH 380V(-15%)–440V(+10%)
An external braking unit is required for the Goodrive series 380V large-power parallel VFD. Select braking resistors according to the specific requirements (such as the braking torque and braking usage) on site.
The following table is the braking unit selection table for a single VFD.
| Power (kW) | Braking unit model | Resistance applicable for 100% braking torque (Ω) | Braking resistor dissipation power (kW) (10% braking usage) | Braking resistor dissipation power (kW) (50% braking usage) | Braking resistor dissipation power (kW) (80% braking usage) | Min. allowed braking resistance (Ω) |
| 280 | Quantity: Two DBU100H-320-4 | 3.6*2 | 21*2 | 105*2 | 168*2 | 2.2 *2 |
| 315 | 3.2*2 | 24*2 | 118*2 | 189*2 | ||
| 355 | 2.8*2 | 27*2 | 132*2 | 210*2 | ||
| 400 | 2.4*2 | 30*2 | 150*2 | 240*2 | ||
| 500 | Quantity: Two DBU100H-400-4 | 2*2 | 38*2 | 186*2 | 300*2 | 1.8*2 |
Note:
- Select braking resistors according to the resistance and power data provided by INVT.
- The braking resistor may increase the braking torque of the VFD. The preceding table describes the resistance and power for 100% braking torque, 10% braking usage, 50% braking usage, and 80% braking usage. You can select the braking system based on the actual operation conditions.
- When using an external braking unit, set the brake voltage class of the braking unit properly by referring to the manual of the dynamic braking unit. If the voltage class is set incorrectly, the VFD may not run properly.
![]() |
Do not use braking resistors whose resistance is lower than the specified minimum resistance. The VFD does not provide protection against overcurrent caused by resistors with low resistance. |
![]() |
In scenarios where braking is frequently implemented, that is, the braking usage is greater than 10%, you need to select a braking resistor with higher power as required by the operation conditions according to the preceding table. |
Braking units for AC 3PH 520V(-15%)–690V(+10%)
An external braking unit is required for the Goodrive series 660V large-power parallel connection solution. Select braking resistors according to the specific requirements (such as the braking torque and braking usage) on site.
The following table is the braking unit selection table for a single V
| Power (kW) | Braking unit model | Resistance applicable for 100% braking torque (Ω) | Braking resistor dissipation power (kW) (10% braking usage) | Braking resistor dissipation power (kW) (50% braking usage) | Braking resistor dissipation power (kW) (80% braking usage) | Min. allowed braking resistance (Ω) |
| 355 | DBU100H-320-6 | 3.5 | 53 | 263 | 420 | 3.4 |
| 400 | DBU100H-400-6 | 3.0 | 60 | 300 | 480 | 2.8 |
| 500 | Two sets of DBU100H-320-6 | 4.8*2 | 38*2 | 188*2 | 300*2 | 3.4*2 |
| 630 | 3.8*2 | 47*2 | 236*2 | 378*2 |
Note:
- Select braking resistors according to the resistance and power data provided by INVT.
- The braking resistor may increase the braking torque of the VFD. The preceding table describes the resistance and power for 100% braking torque, 10% braking usage, 50% braking usage, and 80% braking usage. You can select the braking system based on the actual operation conditions.
- When using an external braking unit, set the brake voltage class of the braking unit properly by referring to the manual of the dynamic braking unit. If the voltage class is set incorrectly, the VFD may not run properly.
![]() |
Do not use braking resistors whose resistance is lower than the specified minimum resistance. The VFD does not provide protection against overcurrent caused by resistors with low resistance. |
![]() |
In scenarios where braking is frequently implemented, that is, the braking usage is greater than 10%, you need to select a braking resistor with higher power as required by the operation conditions according to the preceding table. |
Braking resistor cable selection
Braking resistor cables should be shielded cables.
Braking resistor installation
All resistors must be installed in places with good cooling conditions.
![]() |
The materials near the braking resistor or braking unit must be flame resistant. Since the surface temperature of the resistor is high and air flowing from the resistor is of hundreds of degrees Celsius, it is necessary to prevent any materials from coming into contact with the resistor. |
Braking unit installation
![]() |
|
The following figure shows the connection of one VFD to a dynamic braking unit. 
E-mail: overseas@invt.com.cn
Website: www.invt.com
- The products are owned by Shenzhen INVT Electric Co.,Ltd.
- Two companies are commissioned to manufacture: (For product code. refer to the 2nd/3rd place of S/N on the name plate.)
- Sheese VY Ganging Te had origin code, Songbai Road, Matian, Guangming District, Shenzhen, China
- INVT Power Electronics (Suzhou) Co., Ltd. (origin code: 06) Address: 1# Kunlun Mountain Road, Science& Technology Town, Gaoxin District, Suzhou, Jiangsu, China
- Industrial Automation:
- HMI
- PLC
- Elevator Intelligent Control System
- Energy & Power:
- UPS
- DCIM _
- New Energy Vehicle Powertrain System
- New Energy Vehicle Motor
- VFD
- Servo System
- Rail Transit Traction System
- Solar Inverter
- SVG
- New Energy Vehicle Charging System