Integra NOVA 750 Interactive UPS User Manual

Integra NOVA 750 Interactive UPS User Manual

  • Technical information on this manual is property of XMART by INTEGRA . This manual Information cannot be copied or distributed totally or partially without written approval of XMART.
  • XMART can introduce modifications in their products or manuals without further notice.
  • XMART is not responsible of mistakes or missing information in this manual.
  • XMART is not responsible for wrong use a third part can do of this information.
  • Trademarks and logos in this manual are property of their owners.

SAFETY INSTRUCTIONS

SYMBOLS

 WARNING
    ELECTRICAL SHOCK RISK

WARNING: It is required to read and understand this manual. Follow all instructions given in this manual for starting up and operating this product. Only qualified technician must start-up, operate and maintain this product. Keep manuals as a guide for future consults.
WARNING: This product operates with dangerous voltages. It must be installed, operated, and maintained ONLY by qualified technicians trained for this kind of products. Service personnel MUST know and understand very well all electric risks related to this product. UPS manufacturer or distributor will never be responsible for any accident produced by lack of knowledge or negligent practices at the moment of install, starting up, or  aintain this product. UPS manufacturer or distributor is not liable for any damage that might rise from misusing this unit or defective installation.
WARNING: If you are not qualified technician do not try to repair this product.
WARNING: Internal area of this product is locked by screws. Do not try to access inside the UPS unless you are a qualified technician. UPS must be checked, repaired, and maintained by qualified personnel only.
ELECTRICAL SHOCK RISK
CAUTION: There are dangerous voltages in the UPS power outlets although the equipment is not plugged into power line.
CAUTION: Inside this equipment, due to internal batteries, there are ALWAYS dangerous voltages, even UPS is OFF and unplugged of power line.
WARNING: EQUIPMENT DISPOSAL
OUT OF SERVICE UNITS: It is strongly recommended to dispose this piece of equipment according to valid directives in your country. At the moment of disposing all pieces need to be managed appropriately to avoid possible environmental damage or for some materials to be recycled.
BATTERIES: Do not throw it to fire (risk of explosion). Do not open the batteries, there are dangerous liquids inside.

SAFETY & QUALITY STANDARDS

SAFETY – LOW VOLTAGE DIRECTIVE (2014/35/EU)
UPS Part 1-1: General & Safety UPS in accessible areas IEC/EN 62040-1
ELECTROMAGNETIC COMPATIBILITY – EMC DIRECTIVE (2014/30/EU)
UPS, Part 2, Electromagnetic Compatibility: IEC/EN 62040-2
Low Freq. Conducted Disturbances & Signals: IEC/EN 61000-2-2
 Electrostatic discharge immunity Test: IEC/EN 61000-4-2(Air: Level 3, Contact: Level 2)
Radiated radio Frequency immunity: IEC/EN 61000-4-3 (Level 3)
Electrical Fast Transient / burst immunity: IEC/EN 61000-4-4 (Level 3)
 Surge immunity: IEC/EN 61000-4-5(L-L: Level 2, L-G: Level 3)
UPS Part 3: Methods of operation, specifications, and test requirement IEC/EN 62040-3
IT Equipments. SAFETY. Part 1: General Requirements IEC/EN 60950-1
IP PROTECTION IP20 (static)
QUALITY MANAGEMENT: ISO 9001 : 2000 Manufactured under: ISO 9001
ENVIRONMENTAL MANAGEMENT: ISO 14001 : 2004 Manufactured under: ISO 14001

Any modification made by user or operator may affect compliance of the safety and performance certifications listed above.
UPS manufacturer is not responsible of any modification made on the product or its accessories after it is manufactured.
This product is designed to operate in domestic and commercial environment. CE standards apply for 230V models.
This is a C2 category product. In residential environment, this product may cause radio interference, in this case the user may require taking additional measures.

 BATTERY MAINTENANCE

  • Batteries capacity, in general (of all kinds), decreases with time and use.
  • Our products contain high quality batteries only.
  • Batteries useful life in our UPS is between 3 and 5 years, considering environment temperature under 25ºC and optimal operatio nal conditions. This time can be dramatically reduced by high temperature and other adverse operation condition.
  • Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as well as number and kind of equipment connected to UPS.
  • Batteries should be periodically tested to check capacity and assure and appropriate back up.

* To enlarge batteries life expectancy, it is recommendable to fully discharge UPS once every 3 months
* During long UPS storage recharge batteries according to following table:

STORAGE TEMPERATURE FREQUENCY RECHARGING TIME
-25°C a +30°C Every 4 months 4 h
+30°C a +45°C Every 2 months 4 h

UPS DESCRIPTION

Known as UPS (Uninterruptible Power Supply), this unit has 2 main functions: Give electrical protection against most dangerous failures of main AC Line and Providing electrical backup based on internal batteries. Products connected to your UPS will be protected and will receive electrical energy even during failures of main AC Line.
This UPS is designed to satisfy requirements of Personal Computers (PCs). It includes internal voltage regulator to stabilize input AC variations without using batteries. Only during important power failures UPS will use batteries to provide energy to outlet sockets. Thus, batteries life expectancy is longer.

                                                          Parts Identification

  1. Outputs (battery backup)
  2. AC Input
  3. Input breaker
  4. RJ45 surge protected sockets
  5. USB
  6. Outputs (Surge protected)

UPS will provide backup energy in its outlets when main AC input fails. Runtime will depend on some different factors:

  • Battery charging level.
  • Battery capacity according to the use given and lifetime.
  • Load consumption connected to UPS outlets. Higher the output load shorter the runtime.

Under normal condition, when UPS is ON and connected to AC source, UPS will keep batteries fully charged.
NOTE: For Self-protection, NOVA 750 & NOVA 1000 have a Max. backup time of 120 Min, limited by UPS electronic. Max. backup time for NOVA 1200 is of 240 Min

UPS INSTALLATION

  • This UPS must be installed indoor, in controlled environment free of excessive dust, corrosive air, or conductive dust.
  • Do not install it outdoor. Keep UPS working under operational conditions listed in specifications table of this manual. Keep out of direct sun light, water, and heat sources.
  • Do not install UPS close to PC screen to avoid interference. UPS must be at least at 20cm from  creen.
  • Connect TEL or LAN line to RJ45/RJ11 port identified as IN. Connect OUT to your Router (TEL input) or to your PC LAN port.
  • Plug power cord of this UPS to AC source socket. Plug your equipment to UPS outlets.
  • This unit MUST NOT be installed in closed boxes/cabinets that avoid fresh air access. During normal
    operation, this unit needs fresh air to flow through ventilation system (Vents) to cool power circuits.
    Installing this unit in a closed box/cabinet makes inner air to be recycled without refreshing, increasing inside temperature, exceeding operation max. temperature, and causing permanent  amage to the UPS.

IMPORTANT WARNINGS:

  • Make sure UPS is plugged to AC source compatible with UPS electrical specifications. Check UPS specs in UPS label.
  • Make sure your products input voltage is compatible with UPS voltage output.
  • Check total load in Watts to be connected to UPS is not higher to maximum UPS capacity.
  • Do NOT plug neither laser printers nor copiers to this UPS. This equipment are high load products will overload your UPS.

OPERATION

  • Once UPS is installed and connected according to section 4 of this manual, please turn UPS on by
    ON/OFF button in front panel. Front panel green LED must turn ON.
  • Turn your products ON one by one. At this moment, your products will be fully protected by the UPS.

This UPS has COLD-START function that allows to turn UPS on even during a failure in the main AC source.
Front panel LED of NOVA 750 & NOVA 1000 will let you know UPS status: OFF / ON / BATTERY MODE.

LCD

NOVA 100 includes an LCD to show valuable information about Utility and UPS data but also provides alarm codes for easy troubleshooting. User can skip from screen to screen by simple touching LCD.
Note: Below table shows screens for 220V model. In 120V models, input & output values will be close to   0V.
UTILITY & UPS INFORMATION

                                                     NORMAL MODE                           BATTERY MODE

OUTPUT SALIDA

INPUT ENTRADA

LOAD CONSUMO

BATTERY

OVERLOAD SOBRECARGA

Mode Symbol

ALARM & ERROR CODES
   ALARM BEEP                      CODE                                     TROUBLESHOOTING

Continuous Beep continuo Output Shorcircuit: Remove faulty equipment from UPS output
Continuous Beep continuo Overload :Remove non critical equipment’s from UPS output
Continuous Beep continuo Overcharge:                                                Call technical service
Continuous Beep continuo Battery Low: Recharge during 6hours. If not solved call tech. service
Continuous Beep continuo Output Hight under battery mode: Call Tech. Service
Continuous Beep continuo High Temperature: Call Tech. Service

CONTROL SOFTWARE

NOVA 1200 includes an USB port to communicate with your PC, for monitor, configuration, and Event Log purposes. Control software (available for: Windows, Mac OSX, Linux, and Unix) and User Manual can be downloaded from our website  : www.xmart-ups.com.

AFTER SALES SUPPORT & WARRANTY

Support: If a failure or problem is detected please check troubleshooting section in user manual. If problem cannot be solved, please contact authorized service center or authorized dealer.
Batteries: Rechargeable batteries can be charged and discharged hundreds of times. However, they will eventually wear out.
This is not a defect or failure so that batteries wear out is not covered by this warranty.
Battery lifetime will depend on operative conditions like working temperature, type and frequency of discharging cycles. Higher the temperature shorter will be the lifetime. Frequent and deep discharging cycles also will short lifetime.  or critical applications batteries should be revised and replaced periodically. Long storage (longer than 6 months) without required recharging will wear out batteries. This situation is not covered by this limited warranty since this is not considered as a defect. Check recharging instructions on user manual.

Conditions Limited Warranty “PLUS” 

  1. Subject to the conditions of this limited warranty, this product is warranted to be free from defects in materials and workmanship at the time of XMART supplies the product.
    •  In Europe, warranty time is 2 years on electronic parts and 2 years on internal batteries from XMART invoice date.
    • In America, standard warranty times could vary depending on country/region or can be extended by purchasing warranty options. Please check warranty plans and extensions with your local distributor.
  2. If during the warranty period, this product fails to operate under normal use and service, due to defects in materials or workmanship, authorized distributor or service center will, at their option, either repair or replace the product in accordance with terms and conditions stipulated herein. Transportation expenses are not covered by this limited warranty.
  3. Warranty is valid only if the original invoice issued by XMART, specifying date of purchase, serial number, and name of the dealer, is presented with the product to be revised. XMART and authorized partners reserve the right to refuse warranty service if any of this information has been removed, changed, or missing in original invoice document.
  4. If product is repaired or replaced, repaired, or replaced product will be warranted for the remaining time of the original warranty or for 90 days on repaired part from date of repair, whichever is longer.
  5. XMART or their distribution/service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty.
  6. If product is out of warranty a reparation proposal will be sent to the user for his approval. If proposal is not accepted, service center will keep product available for the user during 60 continuous days. After this period product would be disposed and user will not be able to rise any claim.
  7. Rechargeable batteries, like included in this product, will definitively wear out even under normal operation. This is not a defect or failure, so it is not covered by this warranty.
  8. This warranty does not cover batteries wear out caused by improper or long storage (over 6 months without required recharging indicated in product manual). Even performing recharging procedure this product cannot be storage longer than 18 months. Problems on batteries caused by this kind of long storage are not covered by this warranty.
  9. This warranty does not cover product failures caused by installations, modifications or repair performed by non-authorized person. If product is open by not authorized technician warranty will be considered void. This warranty does not cover failure caused by inadequate installation or maintenance, misuse, accidents, fire or floods.
  10. This product can include protection devices like input fuse or input breaker. Activation of this kind of devices is not a failure it is caused by an improper product installation. Input fuse or breaker reset, or replacement is not covered by this warranty.
  11. This warranty does not cover damages produced during transportation from user to technical service caused by improper packing of the product by user.
  12. Warranty terms and conditions cannot be modified or extended by third parties without written approval of XMART.
    Limited Warranty “PLUS”
    • XMART does not warrant that the operation of this product will be uninterrupted or error-free during its lifetime. If product fails to work, the maximum liability of XMART under this limited warranty is expressly limited to the lesser of the price you have paid for the product or the cost of repairing or replacement of any hardware components that malfunction in conditions of normal use.
    • In no event will XMART be liable for any damages caused by the product or the failure of the product to perform, including any lost profits or savings or special, incidental, or consequential damages. XMART is not liable for any claim made by a third party to XMART or to final user.
    • XMART is not responsible for damage that occurs because of your failure to follow the instructions intended for this hardware product.

TECHNICAL SPECIFICATIONS

INTERACTIVE UPS 750 1000  

 

1200

Capacity / Capacidad 750VA / 375W 1000VA / 500W 1200VA/600W
Input / Entrada
Voltage 120V Model: (89-145 Vac) – 220VModel: (162-290V) – 230V Model: (170-299Vac)
Frequency 60Hz / 50 Hz: Auto Sensing / Autodetección
Power cord                        4 feet (1.22m) NEMA5-15P
Generator Compatible / Yes
Output
Voltage +/- 10% (1 Phase / 1 Fase)
Frequency 60Hz (+/- 1Hz) – 50Hz (+/- 1Hz)
Transfer Time 2 – 6 ms typical / típico
Waveform / Forma de Onda (Normal Mode) Sinewave / Sinusoidal
Waveform / Forma de Onda (Battery Mode)
Batteries
Type Sealed Lead Acid – Maintenance Free (VRLA AGM) / Acido Plomo Sellada Sin Mtto. (VRLA AGM)
Capacity 7AH 9AH 7AH
Quantity 1 1 2
17-20 min. 22-25 min. 40 min. max.
Back-up Time Typical / Autonomía Típica (N1*) 17-20 min. 22-25 min. 40 min. max.
Recharge Time Sealed Lead Acid – Maintenance Free (VRLA AGM) / Acido Plomo Sellada Sin Mtto. (VRLA AGM
Protections Deep discharge and overcharge
Alarms-Indications / Alarmas-Indicaciones LED Indicators – Indicadores LED LCD Screen / Pantalla LCD
Models 750 & 1000: LED Batt. Mode / Low Batt. / Overload / Batt. Replacement / UPS Fault Touch LCD / Pantalla LCD táctil In & Out Volts, UPS mode, Batt. %, Load %, Alarms
AC Mode / Modo Normal Green Lighting / Verde Fijo
Battery Mode / Modo Batería Green Flashing / Verde Intermitente
Battery Mode / Low Battery / Overload / Battery Replacement / UPS Fault
Protections / Protecciones
Input Circuit Breaker / “Breaker” de Entrada With Manual Reset / Rearmable
Surge/Spikes Protection (Line H-N) Protección contra Picos / Rayos (Línea L-N) Power Outlet Sockets with surge & spikes protection: L-N Tomas de Salida Protegidas contra Picos/Rayos: L-N
Surge Protection (Network) / Protección contra Picos (Red) Tel/Internet/Ethernet: RJ11 / RJ45
 

Total Suge Suppression / Supresión Total

120V Model: (> 758J) – 220V & 230 Models: (>175J)
Features / Funcionalidades
Power Outlets per model / Tomas por modelo
Models: NEMA 120V & NEMA 220V 6 x NEMA5-15R 6 x NEMA5-15R 8 x NEMA5-15R (6 with Backup + 2 Surge Protected)
Models: SCHUKO 230V 2 x Schuko 2 x Schuko Schuko x 4 (all battery backup & protected)
Communication Por / Puerto de Comunicaciones No  

 

No

USB
Software / Software Support: Windows, Mac OS; Linux ;Unix
Dimensions / Dimensiones 280 x 102 x 142 mm 280 x 102 x 142 mm 325 x 135 x 185 m
Net Weight / Peso Neto Unitario 4.3 Kg 4.9 Kg 8.5 Kg
Operating / Condiciones de Operación: < 95% RH / 0-40ºC / ≤ 40 dB @ 1 mt
Packing / Empaque
Carton Information / Información Cartón (mm) 4 units per carton / 4 unidades por carton (350x600x260) 1 Un x carton (399 x 198 x 280)

 

 

Half Pallet Information / Información Medio Pallet 96pcs/432Kg 120 x 100 x 113cm           96pcs/489Kg 120 x 100 x 113cm 60pcs/555Kg 120 x 100 x 127cm
Full Pallet Information / Información Medio Pallet 192pcs/864Kg 120 x 100 x 213cm 192pcs/979Kg 120 x 100 x 213cm 105pcs/960Kg 120 x 100 x 225cm
Safety & Standards
For 220V & 230V CE (Low Voltage Directive 2006/95/EC & EMC Directive 2004/108/EC)
Conduction & Radiation (Models 220V/230V) IEC / EN 62040-2 (Class 2 EMC), IEC 61000-4-2, 4-3, 4-4, 4-5, & 2-2
Quality & Enviroment RoHS / ISO9001 & ISO14001
Technical specifications may change without further notice. Las especificaciones pueden cambiar sin aviso previo. N1*: Times for 1PC + TFT load / Tiempos para 1PC + Pantalla TFT

  USA Headquarters:
Miami, FL33196
Florida, USA
xmartmiami@xmart-ups.com
EUROPE Headquarters:
Sabadell, 08202
Barcelona, SPAIN
sales@xmart-ups.com
Latin America Headquarters:
Santiago de Chile, 8330662
Chile, CHILE
sales@xmart-ups.com
www.xmart-ups.com VER. 2403.14-AP_ENG

Documents / Resources

PDF thumbnailNOVA 750 Interactive UPS
User Manual · 750, 1000, 1200VA, NOVA 750 Interactive UPS, NOVA 750, Interactive UPS, UPS

References

Ask a Question

Use this section to ask about setup, compatibility, troubleshooting, or anything missing from this manual.

Ask a Question

Ask about setup, compatibility, troubleshooting, or anything missing from this manual. Name and email are optional.