INOR logoUSER INSTRUCTIONS
Programmable Temperature Transmitter
IPAQ R460INOR Programmable Temperature Transmitter IPAQ R460

Programmable Temperature Transmitter IPAQ R460

PROBOAT PRB08043 BlackJack 42 Inch Brushless 8S Catamaran - icon 3 Read these instructions before using the product and retain for future information.

► Before Startup
When operating the signal converter, certain parts of the module can carry dangerous voltage! Ignoring the warnings can lead to serious injury and/or cause damage!
The signal converter should only be installed and put into operation by qualified staff. The staff must have studied the warnings in these operating instructions thoroughly.
The signal converter may not be put into operation if the housing is open.
In applications with high operating voltages sufficient distance and isolation as well as shock protection must be ensured.
Safe and trouble-free operation of this device can only be guaranteed if transport, storage and installation are carried out correctly and operation an maintenance are carried out with care.
INOR Programmable Temperature Transmitter IPAQ R460 - icon Appropriate safety measures against electrostatic discharge (ESD) should be taken during range selection and assembly on the transmitter.
► Short description
The programmable transmitter is designed for operating various industrial sensors. The measured values are converted into a current or voltage signal. The configuration can be done either via DIP switch for preference measuring ranges or extensive ranges via an USBinterface with the PC configuration program INOR-Set.
The 3-way isolation guarantees reliable decoupling of the sensor circuit from the processing circuit and prevents linked measurement circuits from influencing each other. The auxiliary power can either be supplied via the connection terminals or via the In-Rail-Bus connector (see Accessories).

Configuration and startup

Configuring with DIP switch
Use the DIP switches to configure the device, according to table.
Via the DIP switches you can select only a limited number of sensors. A wider range of sensors you can select via software configuration.
Configuring with software INOR-Set
Use the software INOR-Set to configure the device. Changes to the configuration and parameterization data can be performed both during operation with a connected measuring circuit and in a disconnected state. The INOR-Set software is free and can be downloaded from our website.
The device is equipped with a programming socket on the front. Use the INOR-Set USB Converter (Order no.: 70USBIM010) for connecting the device to the PC. To change the configuration and parameterization DIP switch S1- 1, 2, 3 have to be set ON!
Commissioning Function
The Commissioning Function with a stepped keystone signal on output supports a fast and simple testing of cabling and connection of downstream devices or measuring adjustment. Press the function button located behind the front cover for longer than 3 seconds. The Commissioning Function will be indicated with a yellow LED (quick double off).
Output value:

Output 0 % INOR Programmable Temperature Transmitter IPAQ R460 - icon 2 50 % INOR Programmable Temperature Transmitter IPAQ R460 - icon 2 100 % INOR Programmable Temperature Transmitter IPAQ R460 - icon 3 50% INOR Programmable Temperature Transmitter IPAQ R460 - icon 3
Time 5 s 3 s 3 s 3 s 5 s 3 s 3 s 3 s

The stepped keystone signal is output continuously. Exit the Commissioning Function by pressing the button again for 3 seconds or power off.
Teach-In Function for Potentiometer, Resistor and mV- Input
The Teach-In function can be used to teach in the start value and end value. There are two ways of the Teach-In function:

  • Automatic set up mode (Auto Teach-In)
  • Manual Teach-In of the start and end value (Manual-Teach-In)

The taught-in values remain stored under the Teach-In setting. The start value is 0 % and the end value is 100 % by default.

Starting the Teach-In Function

Use the function button located behind the front cover of the device to teach in the device (use screw driver to push).

  1. Configure the device using the DIP switches on the side of the device.
  2. Press the function button for longer than 3 seconds.
    INOR Programmable Temperature Transmitter IPAQ R460 - icon 1 The yellow LED will flash quickly
  3. Auto Teach-In: Set input signal to both min and max range limits as often as desired. Start value and end value will be automatically determined and recorded.
    or

Manual Teach-In: Set input signal to first range limit and press the function button for around 0.5 seconds. Set second limit and press the function button for around 0.5 seconds. This can be repeated as often as required. The value of the last two keystrokes will be stored for start value and end value.
Ending the Teach-In, Saving the Start Value and End Value
Press the function button for longer than 3 seconds. Release the button when the yellow LED lights up constant. The values are stored. The green LED indicates the successfully storage.
Ending the Teach-In without Saving the Start Value and End Value
Press the function button for longer than 6 seconds. Release the button when the yellow LED starts to flash again after lit up constant.
The values are ignored and not stored.
Or switch off the device. The values are not stored.
Teach-In Fault
If the span between the start value and the end value is too small, the red LED will flash slowly after saving the values (configuration error). In case of a fault, the Teach-In function must be performed again in its entirety.

Technical Data

Input

Sensor Span min. Error
Pt100, Pt200, Pt500, Pt1000 10 K < 0.1 K + 0,05 % meas. val.
Ni100, Ni200, Ni500, Ni1000 10 K < 0.2 K + 0,05 % meas. val.
KTY (29 types) 25 K < 0.3 K + 0.05 % meas. val.
Resistor 0…5000Q 100 Q < 0.1 52 + 0.02 % meas. val.
Sensor current/ connection 0.2 mA / 4-wire, 3-wire, 2-wire
Cable resistance < 100 S2 per wire, manual compensation for 2-wire connection programmable
TC Sensor E, J, K, L, N, R, S, T, U / B, C, D 50 K / 100 K < 0.3 K + 0.08 % meas. val.
Cold junction compensation intern, extern Pt100, uncompensated, manual setting
(Error of cold junction compensation internal < 1.5 K)
±100 mV, ±1000 mV 5 mV, 50 mV < 50 pV + 0.02 % meas. val.
Poti 100 c2 to 50 kS2 10% < 0.05 %
Output Current Voltage
Output signal 0…20 mA 0…10 mA
4…20 mA 2…10 mA
0…10 V 0…5 V
2…10V 1…5 V
Load 12 V (600 .0 at 20 mA) 5 mA (2 kf.) at 10 V)
Residual ripple < 10 mVrms
Transfer range 0 to 102.5 % (3.8 to 20.5 mA at output 4 to 20 mA) Transfer characteristic rising / falling
Error signal Sensor- / wire break, error signal programmable

General data

Transmission error < 0.1 % full scale
Temperature coefficient2) < 100 ppm/K
Measurement rate 4 / s
Response time T99 250 ms
Test voltage 3 kV, 50 Hz, 1 min.
Input against output against power supply
Working voltage³) (basic insulation) 600 V AC/DC for overvoltage category II and contamination class 2 acc. to EN 61010-1
Protection against dangerous body currents³ Protective Separation by reinforced insulation acc. to EN 61010-1 up to 300 V AC/DC for overvoltage category II and contamination class 2 between input and output and power supply.
Ambient temperature Operation -25 °C to +70 °C (-13 to +158 °F)
Transport and storage -40 °C to +85 °C (-40 to +185 °F)
Power supply 24 V DC 16.8 V … 31.2 V, approx. 0.8 W
EMV4) EN 61326-1
Construction 6.2 mm (0.244″) housing, protection type: IP 20 mounting on 35 mm DIN rail acc. to EN 60715
Connection (captive plus-minus clamp screws) Solid: 0.5 mm2 – 4 mm2 / AWG 20-12
Fine-stranded: 0.5 mm2 – 2.5 mm2 / AWG 20-14
Stripped length: 8 mm / 0.3 in
Screw terminal: torque 0.6 Nm / 5 lbf in
Weight Approx. 70 g
  1. Factory setting:
    Input: Pt100, 0…100°C, 4-wire-sensor connection
    Output: 0…20 mA, Characteristic rising, error signal 22 mA
  2. Average TC in specified operating temperature range
  3. As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipment’s. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
  4. Minor deviations possible during interference

Dimensions

INOR Programmable Temperature Transmitter IPAQ R460 - Dimensions► Mounting, Electrical Connection
The transmitter is mounted on standard 35 mm DIN railINOR Programmable Temperature Transmitter IPAQ R460 - Mounting

► Order Information

Temperature Transmitter Order No.
IPAQ R460 70R4600010

LIMITED WARRANTY

INOR Process AB hereby warrants that the Product will be free from defects in materials or workmanship for a period of five (5) years from the date of delivery (”Limited Warranty”). This Limited Warranty is limited to repair or replacement at INOR’s option and is effective only for the first end-user of the Product.
This Limited Warranty applies only if the Product:

  1. is installed according to the instructions furnished by INOR;
  2. is connected to a proper power supply;
  3. is not misused or abused; and
  4. there is no evidence of tampering, mishandling, neglect, accidental damage, modification or repair without the approval of INOR or damage done to the Product by anyone other than INOR.

Delivery conditions are based upon the „GENERAL CONDITIONS FOR THE SUPPLY OF PRODUCTS AND SERVICES OF THE ELECTRICAL AND ELECTRONICS INDUSTRY“
Subject to change!
Set the input and output ranges with DIP switches (● = ON) as indicated in the following table:
Input
DIP S1 ● = on

1 2 3 4 5
Pt100
Pt1000
Ni100
Resistor
2-wire
3- wire
4- wire
Potentiometer
Type J
Type K
CJC internal
CJC external (Pt100)
CJC off
± 100mV
mV x 10
PC (USB) Setting

Output
DIP S2

7 8 9 10
0 … 20 mA
4 … 20 mA
0 … 10 V
0 … 5 V
Characteristic
rising
falling
Error Message
signalize
not signalize

● = ON
Factory settings: all switches in position OFF
Start Value
DIP S1

6 7 8 9 10 °C °F Pot mV
-200 -328 0 0% -100
-175 -283 50 1% -90
-150 -238 100 2% -80
-125 -193 150 3% -70
-100 -148 200 4% -60
-75 -103 250 5% -50
-50 -58 300 6% -45
-25 -13 350 7% -40
0 32 400 8% -35
25 77 450 9% -30
50 122 500 10% -25
75 167 550 11% -20
100 212 600 12% -15
125 257 650 13% -10
150 302 700 14% -5
175 347 750 15% 0
200 392 800 20% 5
225 437 850 25% 10
250 482 900 30% 15
275 527 950 35% 20
300 572 1000 40% 25
350 662 1500 45% 30
400 752 2000 50% 35
450 842 2500 55% 40
500 932 3000 60% 45
550 1022 3500 65% 50
600 1112 4000 70% 60
650 1202 4500 75% 70
700 1292 -/- 80% 80
800 1472 -/- 85% 90
900 1652 -/- 90% -/-
1000 1832 Teach In

End Value
DIP S2

1 2 3 4 5 6 °C °F Poti mV
-150 -238 100 10% -/-
-125 -193 150 15% -/-
-100 -148 200 20% -/-
-75 -103 250 25% -/-
-50 -58 300 30% -/-
-25 -13 350 35% -/-
0 32 400 40% -/-
25 77 450 45% -/-
50 122 500 46% -/-
75 167 550 47% -/-
100 212 600 48% 100
125 257 650 49% 95
150 302 700 50% 90
175 347 750 51% 85
200 392 800 52% 80
225 437 850 53% 75
250 482 900 54% 70
275 527 950 55% 65
300 572 1000 56% 60
325 617 1050 57% 55
350 662 1100 58% 50
375 707 1150 59% 45
400 752 1200 60% 40
425 797 1250 61% 35
450 842 1300 62% 30
475 887 1400 63% 25
500 932 1500 64% 20
525 977 1600 65% 15
550 1022 1700 66% 10
575 1067 1800 67% 5
600 1112 1900 68% 0
625 1157 2000 69% -5

DIP S2

1 2 3 4 5 6 °C °F Poti mV
650 1202 2100 70% -10
675 1247 2200 71% -15
700 1292 2300 72% -20
725 1337 2400 73% -25
750 1382 2500 74% -30
775 1427 2600 75% -35
800 1472 2700 76% -40
825 1517 2800 77% -45
850 1562 2900 78% -50
875 1607 3000 79% -55
900 1652 3100 80% -60
925 1697 3200 81% -65
950 1742 3300 82% -70
975 1787 3400 83% -75
1000 1832 3500 84% -80
1025 1877 3600 85% -85
1050 1922 3700 86% -90
1075 1967 3800 87% -/-
1100 2012 3900 88% -/-
1125 2057 4000 89% -/-
1150 2102 4100 90% -/-
1175 2147 4200 91% -/-
1200 2192 4300 92% -/-
1225 2237 4400 93% -/-
1250 2282 4500 94% -/-
1275 2327 4600 95% -/-
1300 2372 4700 96% -/-
1325 2417 4800 97% -/-
1350 2462 4900 98% -/-
1375 2507 5000 99% -/-
1400 2552 -/- 100% -/-
1425 2597 Teach In

LED indication

The transmitter has a green and a red/yellow LED on front panel.

LED Announcement
green continuous Power LED, normal operation
green flashing Over/under range on input
yellow quick flashing Teach-In mode active
yellow slow double flashing Commissioning Function active
red flashing Sensor break or configuration error
red continuous Device error, replacement is necessary

Error diagnostic function on output
(other output ranges react analogous to the table)

Characteristic Error Output Under range Over range Sensor break / invalid setting
rising

S2-9 OFF

signalize S2-10 = OFF 0 … 20 mA
4 … 20 mA
0 … 5 V
0 … 10 V
0 mA
3.8 mA 0 V 0 V
20.5 mA
20.5 mA
5.125 V
10.25 V
22 mA
22 mA
5.5 V 11 V
not signalize S2-10 = ON 0 … 20 mA
4 … 20 mA
0 … 5 V
0 … 10 V
0 mA
4 mA
0 V
0 V
20 mA
20 mA
5 V
10 V
0 mA
4 mA
0 V
0 V
falling S2-9 ON signalize S2-10 = OFF 20 … 0 mA
20 … 4 mA
5 … 0 V
10 … 0 V
20.5 mA
20.5 mA
5.125 V
10.25 V
0 mA
3.8 mA 0 V 0 V
22 mA
22 mA
5.5 V 11 V
not signalize S2-10 = ON 20 … 0 mA
20 … 4 mA
5 … 0 V
10 … 0 V
20 mA
20 mA
5 V
10 V
0 mA
4 mA
0 V
0 V
0 mA
4 mA
0 V
0V

INOR Process AB, PO Box 9125, SE-200 39 Malmö, Sweden, Phone: +46 40 312 560, Fax: +46 40 312 570,
E-mail: support@inor.se
INOR Transmitter OY, Tuupakantie 3 01740 Vantaa, Finland, Phone:+358 10 421 7900, Fax: +358 10 421 7901,
E-mail: myynti@inor.fi
INOR Transmitter GmbH, Am See 24, D-47279 Duisburg, Germany, Phone: +49-203 7382 762 0, Fax: +49-203 7382 762 2,
E-mail: info@inor-gmbh.de
KROHNE Temperature Division INOR, 55 Cherry Hill Drive, Beverly, MA 01915, United States, Phone: +1 978 826 6900,
Fax: +1 978 535 1720,
E-mail: inor-info@krohne.com

© INOR 11/2022 – 4009623201 – MA IPAQ R460 R01
All information subject to change without notice.