IDEAL L2 Lever Push In Wire Connector
Installation Instructions
Models L2, L3 & L5
- Do not exceed the rating of these connectors.
- Turn OFF power before removing or installing connectors.
- Wiring must comply with all applicable electrical regulations.
- COPPER TO COPPER ONLY. Do not use on aluminium wire.
- Incorrect use of these connectors can cause electrical fires, personal injury or death.
- Use only one conductor per port.
- Strip wires back 11-12mm.
- For solid and rigid stranded wire, grip wire firmly and insert conductor into open port (lever does not need to be open).
- For flexible stranded wire (>7 strands) lift lever and insert conductor into open port. Close lever.
- Verify conductors are fully inserted to the back of the connector.
- To remove a wire, lift lever and pull out wire.
- Strip Length
- Insertion
- Removal
Specifications
Specifications | Model L2 2-Port | Model L3 3-Port | Model L5 5-Port | |
Rating |
32 Amp / 450V / 85° |
|||
Depth |
18.6 mm |
|||
Width | 13.3 mm | 18.9 mm | 30.4 mm | |
Height |
8.8 mm |
|||
Wire Combination Range | Solid and Rigid Stranded |
0.2mm2 – 4.0mm2 |
||
Flexible Wires |
0.14mm2 – 4.0mm2 |