32 Red 2-Port Push-In Wire Connectors
Instruction Manual
Installation Instructions – Push-In Wire Connectors
Models 32, 33, 34, 87, 88 & 90
- Do not exceed the rating of these connectors.
- Turn OFF power before removing or installing connectors.
- Wiring must comply with all applicable electrical regulations.
- COPPER TO COPPER ONLY. Do not use on aluminium wire.
- Incorrect use of these connectors can cause electrical fires, personal injury or death.
- These connectors are suitable for solid and semi-rigid (<7 strands) conductors. They are not suitable or rated for use with flexible cable with >7 strands.
- Strip wires back 13mm.
- Grip wire firmly and push conductor into open port.
- Use only one conductor per port.
- Connectors are reusable on solid wires of the same wire gauge or larger. If reusing connectors, cut and re-strip conductors.
- In order to remove a wire, pull and twist the wire back and forth.
- DO NOT RE-USE connector on stranded wire.
Specifications
|
![]() 2-Port |
![]() 3-Port |
![]() 4-Port |
![]() 5-Port |
![]() 6-Port |
![]() 8-Port |
|
Rating | 32 Amp / 450V / 105°C maximum | 24 Amp / 450V / 105°C maximum | |||||
Depth | 19.81 mm | 18.52 mm | 18.52 mm | 18.21 mm | |||
Width | 13.21 mm I | 17.53 mm | I 20.83 mm | 23.03 mm | 15.32 mm | 35.03 mm | |
Height | 9.65 mm | 9.02 mm | 15.42 mm | 9.02 mm | |||
Wire Combination Range |
Solid wire | 0.75mm2 to 4.0mm2 | 0.75mm2 to 4.0mm2 | ||||
Stranded wire* | 1.5mm2 to 2.5mm2 | 1.5mm2 to 2.5mm2 |
* Stranded wire is limited to ≤ 7 strand
Documents / Resources
![]() |
IDEAL 32 Red 2-Port Push-In Wire Connectors [pdf] Instruction Manual 32, 33, 34, 87, 88, 90, Push-In Wire Connectors, 32 Push-In Wire Connectors, Wire Connectors, Connectors, 32 Red 2-Port Push-In Wire Connectors, 32 Red 2-Port |