IDEAL 30-1032 In Sure Box Enclosure
Specifications:
- Max Aggregate Current (max Iag): 32
- Max Current / Voltage ~ Rating: 16A 250V
- Wire Connector Description: Maintenance Free Accessory
Product Usage Instructions:
INSTALLATION INSTRUCTIONS
(BS EN 60670-22 & BS 5733-MF)
Compatible Wire Connectors:
The wire connectors provided are compatible with various cable types and wire combination ranges as listed below:
Connector Model No. | Description | Wire Combination Range | Strip Length |
---|---|---|---|
32 | Flat Twin & Earth | 13mm | N/A |
33 | 3 Core Flat & Earth | 13mm | N/A |
34 | General Purpose Flexible Cable | 13mm (Rigid stranded wire is 7 strands) | N/A |
L2 | 2 Port Gen II Lever | 9-10mm | 13mm |
L3 | 3 Port Gen II Lever | 9-10mm | 13mm |
L5 | 5 Port Gen II Lever | 9-10mm | 13mm |
42 | 2 Core Flat Flexible Cable | 9-10mm | N/A |
Step-by-Step Guide for Installation:
- Decide on either single end entry or in-line wiring configuration.
- Strip back the outer protective sheathing of the cable.
- Connect the cables together to make the circuit.
- The outer sheathing of cable must be secured by the inner and outer grips.
- If installing 2 cables of the same type through 1 cable entry point, ensure the cables are the same type.
When the In-Sure® Box is installed in an inaccessible location, the additional instructions below apply. This ensures the completed installation complies with BS 5733 for a maintenance free accessory.
Step 1: Apply BS 5733 rating requirements. Only use the connectors referred to in table 3. Connectors have been de-rated to be suitable as a BS 5733 maintenance free accessory. The Max Aggregate Current (Iag) is the sum of all the possible currents through the In-Sure® Box in normal use. This limit must not be exceeded.
- Usually the max Iag equals the number of phase connectors in the In-Sure® Box multiplied by the rating of the OPD (Over Current Protective Device) for the circuit.
Step 2: Follow the In-Sure® Box BS EN 60670-22 installation instructions. Additionally secure the lid on the In-Sure® Box with a cable tie passed through the loop. If you have any doubts consult a professional electrician or other qualified installer.
Table 3.
Connector |
Wire Connector |
Max Current / | Max Cable mm² | Max Aggregate |
32 | 2 Port In-Sure® Push-In | 16A
250V |
2.5mm² | 48A |
33 | 3 Port In-Sure® Push-In |
16A 250V |
2.5mm² |
24A |
34 | 4 Port In-Sure® Push-In | |||
L2 | 2 Port Gen II Lever | 16A
250V |
2.5mm² | 48A |
L3 | 3 Port Gen II Lever |
16A 250V |
2.5mm² |
24A |
L5 | 5 Port Gen II Lever | |||
42 | SpliceLine® in-line | 16A
250V |
2.5mm² | 24A |
Model |
Description |
Quantity |
Cat. No. |
32 | 2 Port In-Sure® Push-In | Box of 100 | 30-1032 |
33 | 3 Port In-Sure® Push-In | Box of 100 | 30-1033 |
34 | 4 Port In-Sure® Push-In | Box of 100 | 30-1034 |
L2 | 2 Port Gen II Lever | Box of 40 | 30-0092 |
L3 | 3 Port Gen II Lever | Box of 40 | 30-0093 |
L5 | 5 Port Gen II Lever | Box of 30 | 30-0095 |
L2 L3 L5 | 2 Port, 3 port
and 5 port Gen II Lever |
Combo pack: 10 x 2-port
10 x 3-port 10 x 5-port |
30-0099 |
42 | SpliceLine® in-line | Pack of 10 | 30-1342S |
42 | SpliceLine® in-line | Box of 100 | 30-1042 |
– | In-Sure® Box | Each | 30-4000 |
FOR ADDITIONAL INFORMATION ON OUR WIRE CONNECTOR
- RANGE PLEASE VISIT: idealind.com
- IDEAL INDUSTRIES EMEA Unit 3, Europa Court, Europa Boulevard, Westbrook, Warrington, WA5 7TN, UK
- Tel: +44 (0)1925 444 446 | Fax: +44 (0)1925 445 501 eur.sales@idealindustries.com
- Products and specifications subject to change. E&OE
- ©2024 IDEAL INDUSTRIES, INC.
COMPATIBLE WIRE CONNECTORS
The IDEAL In-Sure® Box enclosure can only be used with In-Sure® Push-In, Gen II Lever and SpliceLine® connectors as indicated below.
Connector |
Description |
Wire Combination Range |
Strip length |
32 |
2 Port In-Sure® Push-In | Solid Wires 0.75mm²- 2.5mm²
Rigid Stranded Wires 1.5mm²- 2.5mm² (Rigid stranded wire is ≤ 7 strands) |
13mm |
33 |
3 Port In-Sure® Push-In |
13mm |
|
34 |
4 Port In-Sure® Push-In |
13mm |
|
L2 | 2 Port Gen II Lever | Solid, Rigid Stranded: 0.2mm²- 4.0mm² Flexible: 0.14mm²- 4.0mm² | 9-10mm |
L3 | 3 Port Gen II Lever | 9-10mm | |
L5 | 5 Port Gen II Lever | 9-10mm | |
42 |
SpliceLine® in-line |
Solid: 0.5mm²
– 4.0mm² Stranded*: 1.0mm² – 2.5mm² |
13mm |
- Stranded wire is limited to ≤ 7
COMPATIBLE CABLE TYPES
- The In-Sure® Box is designed to accept most common flat and round cables with an overall diameter of between 3 to 8mm – see below for the range of cables supported by the In-Sure® Box and the maximum cables per size.
Cable Type/Size |
Flat Twin & Earth |
3 Core Flat & Earth |
General Purpose Flexible Cable | 2 Core Flat Flexible Cable |
2.5mm² | 2 | N/A | N/A | N/A |
1.5mm² | 6 | 4 | 2 | N/A |
1.0mm² | 8 | 6 | 4 | N/A |
0.75mm² | N/A | N/A | 4 | 8 |
0.5mm² | N/A | N/A | 6 | 8 |
- The In-Sure® Box can accept up to 6 individual connectors and has 4 cable entry points.
STEP BY STEP GUIDE
The In-Sure® Box enclosure has no loose parts and is simple and easy to use. Simply follow the steps below to provide a secure installation in an accessible location as per BS EN 60670-22:
Step 1: Decide on either single end entry or in-line wiring configuration.
Step 2: Strip back the outer protective sheathing of the cable.
Step 3: Connect the cables together to make the circuit.
- Step 4: Place the termination into the In-Sure® Box firmly pressing the cables into the cable grips.
- Step 5: The outer sheathing of cable must be secured by the inner and outer grips.
- Step 6: If installing 2 cables of the same type through 1 cable entry point, the cables should be the same type.
- Step 7: Squeeze the In-Sure® Box together and snap shut the lid.
- Step 8: The In-Sure® Box has the ability to be mounted to any suitable surface using counter sunk no. 6 screw (3.5mm thread) either by using 2 external mounting points or if preferred, the 2 internal mounting points.
- Step 9: DO NOT cover the In-Sure® Box with insulating material.
FAQS
Q: Where can I find more information on the wire connector range?
A: For additional information on our wire connector range, please visit idealind.com or contact Ideal Industries EMEA at the provided address and contact details.
Q: What is the contact information for Ideal Industries EMEA?
A: Ideal Industries EMEA can be reached at Unit 3, Europa Court, Europa Boulevard, Westbrook, Warrington, WA5 7TN, UK. Tel: +44 (0)1925 444 446 | Fax: +44 (0)1925 445 501, or via email at eur.sales@idealindustries.com.
Q: Is the wire connector maintenance-free?
A: Yes, the wire connector is a maintenance-free accessory designed for safe and fast installation.
Q: What is the maximum current and voltage rating of the wire connectors?
A: The wire connectors have a maximum current/voltage rating of 16A at 250V.
Documents / Resources
![]() |
IDEAL 30-1032 In Sure Box Enclosure [pdf] Instruction Manual 30-1032, 30-1033, 30-1034, 30-0092, 30-0093, 30-0095, 30-0099, 30-1342S, 30-1042, 30-1032 In Sure Box Enclosure, 30-1032, In Sure Box Enclosure, Sure Box Enclosure, Box Enclosure |