LOGO AAON

AAON PREHEAT-X Series Module Controller

AAON-PREHEAT-X-Series-Module-Controller-PRODUCT

Spesifikasi Produk

  • Model: PREHEAT-X Module
  • Controllers: VCCX-IP, VCCX2, VCB-X, VCM-X E-BUS
  • Sensors: Air Temperature Sensor, Outside Air Sensor
  • Cable Assembly: E-BUS Cable Assembly
  • Power & Comm Cable Lengths: 1.5 Ft, 3 Ft, 10 Ft, 25 Ft, 50 Ft, 75 Ft, 100 Ft, 150 Ft, 250 Ft, and 1000 Foot Spool

Petunjuk Penggunaan Produk

Informasi Umum
The PREHEAT-X Module is designed to regulate temperature in HVAC systems. It works in conjunction with various controllers and sensors to maintain desired temperatures.

Input dan Output
The module supports analog and binary inputs, analog outputs, and relays for precise control over the HVAC system. Refer to the user manual for detailed configuration options.

Urutan Operasi
The module offers different operation modes to suit various heating requirements. Users can select the appropriate mode based on their needs for efficient temperature control.

Penyelesaian Masalah
In case of issues, refer to the LED diagnostics section in the manual to identify problems. The module also features alarms toalert users of any malfunctions that may occur during operation.

LOG REVISI PREHEAT-X
REVISI DAN TANGGAL MENGUBAH
 

Pendeta E, 16 April 2021

Nomor komponen, alarm dan riwayat alarm, serta label telah diperbarui. Halaman konten Gambar/Tabel telah ditambahkan, dan konversi suhu Fahrenheit/Celsius telah diperbaiki. Kesalahan tampilan telah diperbaiki.
Pendeta F, 2 Februari 2024 layar yang diperbarui, tabel bagian yang diperbarui, berbagai pembaruan kosmetik
REFERENSI BAGIAN PREHEAT-X
DESKRIPSI BAGIAN NOMOR BAGIAN
Modul PREHEAT-X ASM01688
Pengontrol VCCX-IP ASM07424
Pengontrol VCCX2 ASM01698
Pengontrol VCB-X ASM01862
Pengontrol E-BUS VCM-X Bahasa Indonesia: V07151
Sensor Suhu Udara G051240 (6 inci), G051250 (12 inci)
Sensor Udara Luar G042230
Rakitan Kabel E-BUS Daya & Komunikasi E-BUS 1.5 Kaki, 3 Kaki, 10 Kaki, 25 Kaki, 50 Kaki, 75 Kaki, 100 Kaki, 150 Kaki, 250 Kaki, dan Gulungan 1000 Kaki G029440 (1.5 kaki), G012870 (3 kaki), G029460 (10 kaki), G045270 (25 kaki), G029510 (50 kaki), G029530 (75 kaki), G029450 (100 kaki), G029470 (150 kaki), V36590 (250 kaki), G018870 (GULUNGAN)

Semua manual juga tersedia untuk diunduh www.aaon.com/manualkontrol.

  • AAON
  • 2425 South Yukon Ave. Tulsa, OK 74107-2728
  • www.aaon.com
  • Telepon Dukungan Teknis Pabrik: Telepon: 918-382-6450
  • Dukungan Kontrol AAON: Telepon: 866-918-1100
  • Tujuan AAON adalah memberikan informasi produk yang akurat dan terkini. Namun, demi kepentingan penyempurnaan produk, AAON berhak mengubah harga, spesifikasi, dan/atau desain produknya tanpa pemberitahuan, kewajiban, atau tanggung jawab.
  • AAON P/N: G086640, Rev. F
  • © February 2024 AAON Inc. All rights reserved throughout the world.
  • AAON® is a registered trademark of AAON, Inc., Tulsa, OK. AAON assumes no responsibility for errors or omissions in this document.
  • Dokumen ini dapat berubah tanpa pemberitahuan.

LEBIHVIEW

  • PREHEAT-X dirancang untuk mengontrol s tetaptagPemanasan Awal dan modulasi Pemanasan Awal opsional untuk mempertahankan Titik Setel Suhu Udara Keluar Pemanasan Awal yang diinginkan. Lihat Gambar 1, halaman ini untuk dimensi. Lihat Gambar 2 dan 3, halaman 7 dan 8 untuk detail kabel.

Fitur
PREHEAT-X memiliki fitur-fitur berikut:

  • Dapat dioperasikan sebagai modul mandiri atau berkomunikasi dengan VCCX2 atau pengontrol unit AAON lainnya.
  • Memantau Suhu Udara Keluar Preheater dan Sinyal Reset Udara Keluar dan mengontrol untuk mempertahankan titik setel
  • Berisi layar karakter LCD 2 x 8 dan empat tombol yang memungkinkan tampilan status dan perubahan setpoint

CATATAN: PREHEAT-X tidak memiliki komponen yang dapat diservis oleh pengguna. Hubungi teknisi yang berkualifikasi jika PREHEAT-X Anda tidak berfungsi dengan benar.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (1)

PEMASANGAN KABEL

Pertimbangan Pengkabelan Penting

Modul harus dihubungkan ke sumber daya 18-30 VAC dengan ukuran yang sesuai untuk kebutuhan beban VA yang dihitung. Semua ukuran transformator harus didasarkan pada peringkat VA yang tercantum pada Tabel 1 di halaman ini.

 

Kontrol Perangkat

 

 

Jil.tage

Beban VA  

 

Suhu Operasional

Humidity (Non- Condensing)
 

 

 

PREHEAT-X

18-30 VAC 18 -22°F hingga 158°F*

-30ºC to 70ºC*

Kelembaban 0-95%
 

 

Masukan

Resistive Inputs require 10KΩ

Type III Thermistor

24 VAC Inputs provide 4.7KΩ

Memuat

Keluaran Output Relai: 1 amp maksimum per keluaran.

Table 1: PREHEAT-X Electrical and Environmental Requirements

CATATAN: Jika suhu di PREHEAT-X di bawah -22ºF (-30ºC), kecepatan penyegaran tampilan mungkin kurang responsif.

PERINGATAN: Saat menggunakan satu transformator untuk memberi daya pada lebih dari satu pengontrol atau modul ekspansi, polaritas yang benar harus selalu dijaga di antara papan. Kegagalan untuk mematuhi polaritas yang benar akan mengakibatkan kerusakan pada pengontrol unit AAON, PREHEAT-X, dan modul terkait lainnya.

Harap baca dengan saksama dan terapkan informasi berikut saat memasang kabel pengontrol unit AAON, PREHEAT-X, dan modul terkait.

  1. Semua pemasangan kabel harus sesuai dengan kode dan spesifikasi kelistrikan lokal dan nasional.
  2. Semua kabel 24 VAC harus dihubungkan sedemikian rupa sehingga semua kabel ground tetap terhubung. Kegagalan mengikuti prosedur ini dapat mengakibatkan kerusakan pada pengontrol dan perangkat yang terhubung.
  3. Ukuran kabel minimum untuk kabel 24 VAC harus berukuran 18.
  4. Ukuran kabel minimum untuk semua sensor harus 24-gauge. Beberapa sensor memerlukan kabel dua konduktor, sementara yang lain memerlukan kabel tiga atau empat konduktor.
  5. Ukuran kabel minimum untuk kabel termostat 24 VAC harus berukuran 22-gauge.
  6. Pastikan semua sambungan kabel terpasang dan kencang dengan benar pada blok terminal. Jangan biarkan untaian kabel mencuat dan menyentuh terminal di sebelahnya karena dapat menyebabkan korsleting.
  7. Jika kabel komunikasi akan digunakan untuk menghubungkan pengontrol unit AAON atau untuk menghubungkan ke perangkat komunikasi lain, semua kabel harus berperingkat plenum, minimal 18-gauge, dua konduktor, pasangan terpilin dengan pelindung. AAON dapat menyediakan kabel komunikasi yang memenuhi spesifikasi ini dan diberi kode warna untuk jaringan atau loop lokal. Silakan hubungi distributor AAON Anda untuk informasi lebih lanjut. Jika diinginkan, kabel Belden #82760 atau kabel yang setara juga dapat digunakan.
  8. Sebelum memberikan daya ke pengontrol unit AAON, PREHEAT-X, dan modul terkait, pastikan untuk memeriksa ulang semua sambungan dan terminasi kabel secara menyeluruh.

Memperkuat
Saat pengontrol dan modul pertama kali dinyalakan, LED DAYA akan menyala terus-menerus. Jika tidak menyala, pastikan Anda telah menghubungkan pengontrol ke sumber daya 24 VAC, sambungan kabelnya kencang, dan polaritasnya benar. Daya 24 VAC harus dihubungkan agar semua kabel ground tetap terhubung. Jika setelah semua pemeriksaan ini, LED DAYA tidak menyala, silakan hubungi Dukungan AAON Controls untuk mendapatkan bantuan.

Kabel Input

Masukan 
The PREHEAT-X works as a stand-alone module or comm-unicating with the VCCX2 or other AAON unit controllers. For connection to the PREHEAT-X use an E-BUS Cable connecting to the appropriate E-BUS ports. The Reset Input and Heat Enable are only used in Stand-Alone Mode. See Figure 2, this page for the Inputs Wiring Diagram.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (2)

Pengkabelan Output

Keluaran 
PREHEAT-X berfungsi sebagai modul mandiri atau berkomunikasi dengan VCCX2 atau pengontrol unit AAON lainnya. Untuk koneksi ke PREHEAT-X, gunakan Kabel E-BUS yang terhubung ke port E-BUS yang sesuai. Lihat Gambar 3 di halaman ini untuk Pengkabelan Output.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (3)

INPUT DAN OUTPUT

Input Analog dan Biner, Output Analog dan Relai

Input Analog
1 Suhu Udara Keluar 1 (LAT1)
2 Suhu Udara Keluar 2 (LAT2)
3 Sensor Suhu Udara Masuk
4 Reset Masuk (0-10 VDC)
Masukan Biner
1 Aktifkan panas
2 Pemadaman Darurat
3 Penggunaan di Masa Depan
Keluaran Analog
1 Mod SCR 0-10 VDC
2 PWM SSR
Relai
1 Alarm
2 Panas 1
3 Panas 2
4 Panas 3
5 Panas 4
6 Panas 5
7 Panas 6

Tabel 2: Input dan Output PREHEAT-X

Peta I/O

Lihat Tabel 2, halaman ini untuk merujuk input dan output yang tersedia pada PREHEAT-X.

Input Analog

  • Suhu Udara Keluar 1 (LAT1)
    Saat diaktifkan, PREHEAT-X akan mengontrol titik setel Suhu Udara Keluar (LAT). PREHEAT-X dapat dikonfigurasi untuk hanya menggunakan LAT1 untuk tujuan ini. Biasanya, rata-rata LAT1 dan LAT2 yang digunakan.
  • Suhu Udara Keluar 2 (LAT2)
    Saat diaktifkan, PREHEAT-X akan mengontrol Titik Setel Suhu Udara Keluar. Fitur ini dapat dikonfigurasi untuk hanya menggunakan LAT2 untuk tujuan ini. Biasanya, rata-rata LAT1 dan LAT2 yang digunakan.
  • Memasuki Suhu Udara
    Bila Suhu Udara Masuk turun di bawah Titik Tetap Suhu Udara Masuk, pemanasan awal akan diaktifkan.

CATATAN: Untuk AI1 hingga AI3, semua sensor suhu harus berupa Sensor Suhu Thermistor Tipe III, yang menyediakan 77.0ºF @ resistansi 10K ohm.

Atur Ulang Masukan (0-10 VDC)
Ketika PREHEAT-X digunakan sebagai modul mandiri, Titik Setel Suhu Udara Keluar dapat diatur ulang dengan memasok sinyal 0-10 VDC ke RST IN vol rendahtagBlok terminal e. Sinyal reset ini bersifat opsional dan hanya perlu digunakan jika Anda perlu mengatur ulang Suhu Udara Pembuangan.

Masukan Biner

  • Kontak Pengaktif Panas (HEAT EN)
    Input ini hanya diperlukan ketika PREHEAT-X digunakan sebagai modul mandiri; tidak diperlukan ketika berkomunikasi dengan pengontrol unit AAON. Input Heat Enable diaktifkan oleh sinyal 24 VAC yang dipasok dari sistem otomasi gedung untuk mengaktifkan PREHEAT-X. Modul tidak akan beroperasi tanpa tegangan 24 VAC yang diterapkan ke terminal input ini ketika digunakan sebagai modul mandiri. Ketika sinyal Heat Enable hilang atau dimatikan, semuatages nonaktifkan segera.
  • Masukan Shutdown Darurat
    Input kontak basah (24 VAC) ini digunakan untuk memulai penghentian unit HVAC ketika Detektor Asap NC (oleh pihak lain), Firestat (oleh pihak lain), atau kondisi penghentian lainnya (oleh pihak lain) terjadi dan kontak dibuka. PREHEAT-X tetap aktif dan dapat memulai relai alarm.

Keluaran Analog

  • SCR Modulasi 0-10 VDC
    Bergantung pada jenis Panas yang digunakan, keluaran ini akan memasok sinyal keluaran 0-10 VDC untuk kontrol Panas SCR yang termodulasi.
  • Modulasi Lebar Pulsa SSR
    Bergantung pada jenis Panas yang digunakan, keluaran ini akan memasok Sinyal Keluaran PWM 12 V untuk kontrol Panas SSR yang termodulasi.

Output Relai

  • Relai #1 – Alarm
    Relai ini mengirimkan sinyal saat alarm diaktifkan.
  • Relai #2 – 7
    Relai ini adalah S Tetaptage Keluaran Panas.

URUTAN OPERASI

Mode Operasi 
PREHEAT-X dapat digunakan sebagai modul mandiri atau berkomunikasi dengan pengontrol unit AAON menggunakan kabel modular.

Mode Berdiri Sendiri
Saat digunakan dalam Mode Stand-Alone, PREHEAT-X akan memodulasi Panas SCR atau SSR dan stage setiap tambahan tetap staguntuk mempertahankan Titik Setel Suhu Udara Keluar yang dikonfigurasi pada layar LCD PREHEAT-X. PREHEAT-X diaktifkan oleh sinyal 24 VAC ke input HEAT EN.

Modus Komunikasi

  • Saat PREHEAT-X terhubung dan berkomunikasi dengan pengontrol unit AAON melalui kabel modular, informasi yang diperlukan akan diteruskan antara PREHEAT-X dan pengontrol unit AAON agar dapat beroperasi dengan benar dalam Mode Pemanasan.
  • Jika komunikasi antara PREHEAT-X dan pengontrol unit AAON terputus, kedua papan akan menampilkan alarm dan output PREHEAT-X akan mati. Ketika komunikasi pulih, alarm akan hilang.
  • Dalam konfigurasi ini, Titik Setel Suhu Udara Keluar dan Titik Aktifkan Pemanasan Awal ditetapkan menggunakan pengontrol unit AAON utama.

Aktifkan Pemanasan Awal

Mode Berdiri Sendiri
Diaktifkan saat Input Biner tertutup dan Suhu Udara yang Masuk berada di bawah titik yang ditetapkan.

Mode Komunikasi E-BUS
Diaktifkan oleh perintah E-BUS ketika Suhu Udara Masuk turun di bawah Titik Setel Pemanasan Awal.

Mode Komunikasi BACnet
Diaktifkan oleh perintah BACnet® atau Input Biner, mana pun yang terjadi lebih dulu.

Meninggalkan Sensor Udara 
PREHEAT-X dapat dikonfigurasikan untuk menggunakan salah satu dari tiga konfigurasi sensor untuk kontrol.

  • Meninggalkan Sensor Udara 1 saja (LAT1)
  • Meninggalkan Sensor Udara 2 saja (LAT2)
  • Rata-rata Suhu Udara Keluar yang merupakan rata-rata LAT1 dan LAT2

Titik Setel Udara Keluar

Berdiri Sendiri

  • Titik Tetap Suhu Udara Keluar dapat diatur ulang antara Titik Tetap LAT dan Batas Atur Ulang Titik Tetap LAT.
  • Sumber Reset didasarkan pada input 0-10 VDC dan jangkauannya dapat disesuaikan menggunakan Sumber Reset Titik Tetap LAT Rendah dan Sumber Reset Titik Tetap LAT Tinggi.

E-BUS and BACnet Communications Mode

  • Titik Setel Suhu Udara Keluar akan dikirim ke pengontrol.
  • Nilai ini disimpan dalam memori volatil dan akan hilang saat direset.
  • Terdapat titik setel Suhu Udara Keluar yang terpisah, tergantung pada apakah unit berada dalam Mode Pemanasan, Ventilasi, atau Pendinginan.

Modulasi Panas

  • Jika dikonfigurasi, Output Panas Modulasi akan digunakan sebagai s pertamatage. panas.
  • Volume AnalogtagOutput dapat disesuaikan antara 0-10 VDC sesuai kebutuhan untuk mempertahankan Titik Setel Udara Keluar.
  • Dikendalikan oleh Loop PID Internal.

Panaskan StagNaik
Kondisi berikut harus dipenuhi sebelum s pertama (berikutnya)tage panas dapat diberi energi:

  • Sinyal/Perintah Pengaktifan Pemanasan Awal harus aktif.
  • LAT harus berada di bawah Titik Tetap LAT dengan jumlah berapa pun.
  • Jika Mod Heat dikonfigurasi, maka harus pada 100% untuk Stage Penundaan Naik.
  • Waktu Istirahat Minimum harus dipenuhi.
  • Stage Up Delay harus dipenuhi (untuk detiktage dan di atas).

Panaskan StagTurun
Kondisi berikut harus dipenuhi sebelum:tage panas dapat dihilangkan energinya:

  • Preheat Enable Signal/Command is deactivated -ORthe LAT must be above the LAT Setpoint by the LAT Deadband.
  • Jika Modulasi Panas dikonfigurasi, maka harus pada 0% untuk Stage Penundaan Turun.
  • Waktu Berjalan Minimum harus dipenuhi.
  • Stage Down Time harus dipenuhi.

Pemadaman Darurat
Input Mati Darurat harus selalu digunakan dan dihubungkan sebagai kontak 24 VAC yang biasanya tertutup. Jika Mati Darurat terjadi, dan kontak tersebut terbuka:

  • Semua keluaran akan segera dimatikan.
  • Alarm akan berbunyi.

Alarm Suhu Udara Keluar Tinggi
If the Leaving Air Temperature is above the LAT High  Temperature Alarm Limit for more than the Alarm Delay, all heating outputs will be de-energized immediately.

  • Alarm akan berbunyi.
  • Pengaturan ulang manual akan diperlukan.

Alarm Suhu Udara Keluar Rendah
Jika Suhu Udara Keluar berada di bawah Batas Alarm Suhu Rendah LAT selama lebih dari dua menit, pemanas akan tetap menyala tetapi alarm akan berbunyi.

LAYAR LCD

Tombol Navigasi

Layar Tampilan LCD & Tombol Navigasi
Layar tampilan LCD dan tombol memungkinkan Anda untuk view status dan alarm, serta mengaktifkan mode paksa. Lihat Gambar 4 di halaman ini dan lihat Tabel 3 dan 4 di halaman ini untuk penjelasannya.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (4) AAON-PREHEAT-X-Series-Module-Controller-FIG- (5)AAON-PREHEAT-X-Series-Module-Controller-FIG- (6)

LAYAR LCD

Peta Layar Utama

AAON-PREHEAT-X-Series-Module-Controller-FIG- (7)

Layar Utama
Refer to the following map when navigating through the LCD  Main Screens. The first screen is an initialization screen. To scroll through the rest of the screens, press the <MENU> button.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (10)

  • Tekan AAON-PREHEAT-X-Series-Module-Controller-FIG- (8)untuk menggulir Layar PREHEAT-X.
  • TekanAAON-PREHEAT-X-Series-Module-Controller-FIG- (9) untuk membuka Layar STATUS.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (11)

  • TekanAAON-PREHEAT-X-Series-Module-Controller-FIG- (8) untuk menggulir Layar STATUS.
  • TekanAAON-PREHEAT-X-Series-Module-Controller-FIG- (9) untuk membuka Layar SETPOINTS.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (12)

  • TekanAAON-PREHEAT-X-Series-Module-Controller-FIG- (8)untuk menggulir Layar SETPOINTS.
  • TekanAAON-PREHEAT-X-Series-Module-Controller-FIG- (9) untuk membuka Layar ALARM.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (13)

  • TekanAAON-PREHEAT-X-Series-Module-Controller-FIG- (8) untuk menggulir Layar ALARM.
  • Tekan AAON-PREHEAT-X-Series-Module-Controller-FIG- (9)untuk membuka Layar KONFIGURASI.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (14)

  • Tekan AAON-PREHEAT-X-Series-Module-Controller-FIG- (8)untuk menggulir Layar KONFIGURASI.
  • TekanAAON-PREHEAT-X-Series-Module-Controller-FIG- (9) untuk membuka Layar KONFIGURASI KOMUNIKASI.

  • Tekan AAON-PREHEAT-X-Series-Module-Controller-FIG- (8)untuk menggulir Layar KONFIGURASI KOMUNIKASI.

Layar Status
Lihat peta berikut saat menavigasi Layar Status. Dari Layar STATUS, tekan untuk menggulir layar.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (16)AAON-PREHEAT-X-Series-Module-Controller-FIG- (17)

Setpoint Screens
Lihat peta berikut saat menavigasi Layar Setpoint. Dari Layar SETPOINTS, tekan untuk menggulir layar dan mengubah titik setel. Gunakan Dan tombol panah untuk mengubah pilihan Anda. Lalu tekan untuk menyimpan titik setel baru.

CATATAN: When the PREHEAT-X-EXT is operating in Communications Mode, these setpoint screens will not appear on the LCD display because they are controlled by the main controller.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (18)

MENINGGALKAN TITIK SET SUHU UDARA
Hanya akan ditampilkan dalam Mode Mandiri. Ini adalah suhu target saat pemanas diaktifkan. Jika Anda menggunakan sinyal reset, ini adalah titik setel yang akan dihitung hingga nol volt.

Minimum Bawaan Maksimum
0ºF 70ºF 90ºF
-17.7ºC 21ºC 32ºC

AAON-PREHEAT-X-Series-Module-Controller-FIG- (19)

RESET BATAS TITIK SET
Akan ditampilkan dan digunakan hanya dalam Mode Stand-Alone. Jika Remote Reset digunakan, ini akan menjadi Titik Setel Leaving Air saat Reset Vol.tage Input pada 10 VDC.

Minimum Bawaan Maksimum
0ºF 70ºF 120ºF
-17.7ºC 21ºC 48.8ºC

AAON-PREHEAT-X-Series-Module-Controller-FIG-31

MEMASUKI TITIK SET UDARA
Ini adalah suhu saat Preheat diaktifkan. Titik Setel Pengaktifan Udara Masuk diatur oleh layar LCD dalam Mode Mandiri dan diatur oleh pengontrol unit AAON dalam Mode Komunikasi.

Minimum Bawaan Maksimum
-40ºF 55ºF 90ºF
-40ºC 12.7ºC 32ºC

AAON-PREHEAT-X-Series-Module-Controller-FIG- (20)

MENINGGALKAN SENSOR UDARA 1 OFFSET KALIBRASI
Jika sensor membaca secara tidak benar, Anda dapat menggunakan layar ini untuk memasukkan suhu offset guna menyesuaikan suhu sensor.

Minimum Bawaan Maksimum
-100ºF 0ºF 100ºF
-55.5ºC 0ºC 55.5ºC

AAON-PREHEAT-X-Series-Module-Controller-FIG- (21)

MENINGGALKAN SENSOR UDARA 2 OFFSET KALIBRASI
Jika sensor membaca secara tidak benar, Anda dapat menggunakan layar ini untuk memasukkan suhu offset guna menyesuaikan suhu sensor.

Minimum Bawaan Maksimum
-100ºF 0ºF 100ºF
-55.5ºC 0ºC 55.5ºC

AAON-PREHEAT-X-Series-Module-Controller-FIG- (22)

MEMASUKI OFFSET KALIBRASI SENSOR UDARA
Jika sensor membaca secara tidak benar, Anda dapat menggunakan layar ini untuk memasukkan suhu offset guna menyesuaikan suhu sensor.

Minimum Bawaan Maksimum
-100ºF 0ºF 100ºF
-55.5ºC 0ºC 55.5ºC

Layar Alarm

  • Lihat peta berikut saat viewLayar ALARM. Layar ini akan ditampilkan secara otomatis saat alarm aktif. Untuk pemecahan masalah alarm, lihat halaman 22-23.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (23)

ALARM
Alarmnya adalah sebagai berikut:

  • NO ALARMS: This will be shown if there are no current alarms.
  • E-SHUTDN: If 24 VAC is removed from the Emergency Shutdown Input, this alarm will activate and the controller will turn off all outputs. The alarm will be disabled when voltage telah kembali.
  • LA1 SENS: The first Leaving Air Temperature sensor has been disconnected, shorted, open, or missing for more than 60 seconds. This alarm will be disabled when the sensor is working again.
  • LA2 SENS: The second Leaving Air Temperature sensor has been disconnected, shorted, open, or missing for more than 60 seconds. This alarm will be disabled when the sensor is working again.
  • LOW LAT: This indicates a Leaving Air Temperature Cutoff alarm condition which is activated if the Controlling Leaving Air Temperature has dropped below 35ºF for more than two minutes. The alarm will be disabled if after a fixed delay period the Leaving  Air Temperature has risen above 35ºF.
  • HI LAT: This indicates a Leaving Air Temperature Cutoff alarm condition which is activated if the Controlling Leaving Air Temperature has risen above 120ºF. All outputs will stagmati.
  • EA SENS: The Entering Air Temperature sensor has been disconnected, open, shorted, or missing for more than 60 seconds. This alarm will be disabled when the sensor is working again.
  • COM STAT: Communications have been lost with the main controller for more than 30 seconds. This alarm will disable when communications resume.

Layar Konfigurasi

  • Lihat peta berikut saat menavigasi Layar Konfigurasi. Dari Layar KONFIGURASI, tekan untuk menggulir layar dan mengubah titik setel. Gunakan Dan tombol panah untuk mengubah pilihan Anda. Tekan untuk menyimpan perubahan apa pun.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (24) AAON-PREHEAT-X-Series-Module-Controller-FIG- (25)LAYAR LCD

Layar Konfigurasi Komunikasi

  • Lihat peta berikut saat menavigasi Layar Konfigurasi Komunikasi. Dari Layar KONFIGURASI KOMUNIKASI, tekan untuk menggulir layar dan mengubah titik setel. Gunakan Dan tombol panah untuk mengubah pilihan Anda. Tekan untuk menyimpan perubahan apa pun.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (26) AAON-PREHEAT-X-Series-Module-Controller-FIG- (26)

PENYELESAIAN MASALAH

Umum 
The PREHEAT-X is equipped with LEDs that can be used to verify operation and perform troubleshooting. See Figure 6, this page for the LED locations. The LEDs associated with these inputs and outputs allow you to see what is active without using a voltmeter.

The LEDs and their uses are as follows:

  • LED STATUS
    DAYA – LED hijau ini akan menyala untuk menunjukkan bahwa daya 24 VAC telah diterapkan ke pengontrol.
  • LED diagnostik
    ALARM – Lampu LED merah yang terletak di penutup PREHEAT-X, di atas layar LCD, akan menyala untuk menandakan alarm. Jenis alarm akan ditampilkan di layar LCD.

LED komunikasi
COMM – LED kuning ini akan menyala dan berkedip saat komunikasi terdeteksi.

LED relai
RLY 1-6 – LED hijau ini akan menyala dan tetap menyala selama Relai Panas aktif.

LED Input Biner

  • PANAS EN – LED hijau ini akan menyala saat Panas diaktifkan.
  • PEMUTUSAN DARURAT – LED hijau ini akan menyala saat input Pematian Darurat memiliki tegangan 24 VAC yang diterapkan padanya.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (28)

Alarm

Pemecahan Masalah Alarm

Kegagalan Mekanis:

  • Periksa keluaran relai pada PREHEAT-X untuk keluaran 24 VAC.
  • Verifikasi keluaran voltage (VOUT dan GND) ke SCR atau PWM.
  • Verifikasi bahwa Sensor Suhu Udara Keluar terhubung ke AI1 dan/atau AI2 dan GND pada PREHEAT-X.
  • Verifikasi apakah probe Sensor Suhu Udara Keluar terpasang dengan benar.
  • Lepaskan kabel AI1, AI2, dan GND dari PREHEAT-X, lalu ukur ohm sensor (ini mungkin menunjukkan kabel putus atau rusak). Lihat bagan di bagian belakang panduan ini untuk pembacaan.

Leaving Air Temperature Failure:

  • Verifikasi bahwa sensor Suhu Udara Keluar terhubung ke AI1 dan/atau AI2 dan GND pada PREHEAT-X.
  • Lepaskan kabel AI1, AI2, dan GND dari PREHEAT-X, lalu ukur ohm sensor (ini mungkin menunjukkan kabel putus atau rusak). Lihat bagan di bagian belakang panduan ini untuk pembacaan.

Communications Loss:

  • Periksa LED KOM pada PREHEAT-X.
  • Verifikasi daya 24 VAC ke semua pengontrol yang saling terhubung.
  • Verifikasi koneksi antara PREHEAT-X dan pengontrol terkait.
  • Dalam Mode Komunikasi (terhubung dengan kabel modular), verifikasi konfigurasi PREHEAT-X pada pengontrol.

Memasang Sensor Suhu Udara Keluar

  • Sensor Leaving Air Temperature (LAT) harus ditempatkan di lokasi keluaran kotak PREHEAT-X.
  • Tempatkan sensor di tengah bagian terluas dinding kotak PREHEAT-X. Gunakan templat yang tersedia dan bor 5/16 inci untuk membuat lubang bagi sensor.
  • Pasang gasket di atas probe dan pasang dengan aman ke dinding kotak menggunakan sekrup lembaran logam yang disertakan. Pastikan gasket terkompresi untuk memberikan segel kedap udara.

Untuk akurasi terbaik, pasang insulasi di bagian luar dinding kotak, di atas sensor. Ini akan membantu mencegah gradien termal memengaruhi sensor.

PERINGATAN:
Pastikan Sensor Suhu Udara Keluar Anda terpasang dan terhubung kabel sesuai petunjuk ini sebelum menguji unit, jika tidak, katup modulasi tidak akan terkontrol dengan baik dan dapat merusak peralatan Anda.

AAON-PREHEAT-X-Series-Module-Controller-FIG- (29)

LAMPIRAN A: SENSOR LAT

Meninggalkan Sensor Suhu Udara

  • Jika Anda menduga sensor Suhu Udara Masuk atau Keluar tidak terbaca dengan benar, pastikan sambungan terminal kabel kencang dan semua sambungan kabel terhubung dengan benar. Anda dapat memeriksa pengoperasian sensor Suhu Udara Keluar dengan mengukur resistansi atau vol.tagGunakan multimeter digital. Atur meter ke Volt DC. Pasang probe positif pada terminal AI dan probe negatif pada terminal GND. Baca Volt DC dan temukan bahwa volttage pada Tabel 5, halaman ini.
  • Baca suhu yang sesuai dengan volume tersebuttage and determine if this is close to the actual temperature the sensor is exposed to. If the temperature from the chart is different by more than a few degrees, you probably have a defective or damaged sensor.
  • You can also check the sensor resistance to determine correct operation.

Petunjuk Pengujian Sensor Termistor

  • Untuk membaca resistansi, atur meter ke ohm. Cabut konektor sensor dari papan dan ukur resistansi pada kabel yang terputus. Resistansi ini harus sesuai dengan suhu yang sesuai dari Tabel 5 di halaman ini.

Petunjuk Pengujian Sensor Termistor

  1. Gunakan kolom resistansi untuk memeriksa sensor termistor saat terputus dari pengontrol (tidak diberi daya).
  2. Gunakan voltagKolom e untuk memeriksa sensor saat terhubung ke pengontrol bertenaga. Baca vol.tage dengan meter diatur pada voltase DC. Pasang kabel "-" (minus) pada terminal GND dan kabel "+" (plus) pada terminal input sensor yang sedang diselidiki.
Suhu ke Resistansi/Voltage Bagan
Suhu (°C) Suhu suhu udara Perlawanan (Ohm) Jil.tage @ Masukan (VDC) Suhu (°C) Suhu suhu udara Perlawanan (Ohm) Jil.tage @ Masukan (VDC)
-10 -23.3 93333 2.98 72 22.2 11136 1.74
-5 -20.6 80531 2.94 73 22.8 10878 1.72
0 -17.8 69822 2.89 74 23.3 10625 1.70
5 -15 60552 2.83 75 23.9 10398 1.68
10 -12.2 52500 2.77 76 24.4 10158 1.66
15 -9.4 45902 2.71 78 25.6 9711 1.63
20 -6.6 40147 2.64 80 26.7 9302 1.59
25 -3.9 35165 2.57 82 27.8 8893 1.55
30 -1.1 30805 2.49 84 28.9 8514 1.52
35 1.7 27140 2.41 86 30 8153 1.48
40 4.4 23874 2.33 88 31.1 7805 1.45
45 7.2 21094 2.24 90 32.2 7472 1.41
50 10 18655 2.15 95 35 6716 1.33
52 11.1 17799 2.11 100 37.8 6047 1.24
54 12.2 16956 2.08 105 40.6 5453 1.16
56 13.3 16164 2.04 110 43.3 4923 1.09
58 14.4 15385 2.00 115 46.1 4449 1.02
60 15.6 14681 1.96 120 48.9 4030 .95
62 16.7 14014 1.93 125 51.7 3656 .88
64 17.8 13382 1.89 130 54.4 3317 .82
66 18.9 12758 1.85 135 57.2 3015 .76
68 20 12191 1.81 140 60 2743 .71
69 20.6 11906 1.79 145 62.7 2502 .66
70 21.1 11652 1.78 150 65.6 2288 .61
71 21.7 11379 1.76  

Catatan: Jika voltage di atas 3.3 VDC, sensor atau kabelnya “terbuka.” Jika voltage kurang dari 0.05 VDC, sensor atau kabel mengalami hubungan pendek.

Tabel 5: Sensor Suhu 0-3V – Voltage & Resistansi untuk Sensor Tipe III

LAMPIRAN B: BACnet®

Koneksi ke Jaringan MS/TP

AAON-PREHEAT-X-Series-Module-Controller-FIG- (30)

OBYEK PARAMETER KETERANGAN BATAS
AI: 1 Titik Setel Pengendalian Aktif Titik Kontrol Aktif saat ini Hanya Baca
AI: 2 Jumlah Panas Stages Aktif Jumlah panas saat initages pada Hanya Baca
AI: 3 Modulasi Posisi Output Posisi Output Modulasi saat ini Hanya Baca
AI: 4 Semua Alarm Bitfield Status Alarm Saat Ini di Bitfield Hanya Baca, lihat bit alarm, halaman 27
AI: 5 Memasuki Suhu Udara Suhu Udara Masuk Saat Ini Hanya Baca
AI: 6 Meninggalkan Sensor Suhu Udara 1 Sensor Udara Keluar Saat Ini 1 Suhu Hanya Baca
AI: 7 Meninggalkan Sensor Suhu Udara 2 Sensor Udara Keluar Saat Ini 2 Suhu Hanya Baca
AI: 8 Suhu Rata-rata Udara Keluar Suhu Udara Keluar Rata-rata Saat Ini Hanya Baca
AI: 9 Setel Ulang Persen Inputtage Persen Input Reset Setpoint Saat Initage Hanya Baca
BI: 1 Aktifkan Nilai Input Nilai saat ini dari Aktifkan Input Biner Hanya Baca, 0 = Mati, 1 = Hidup
BI: 2 Nilai Input Matikan Nilai saat ini dari Input Biner Penutupan Darurat Hanya Baca, 0 = Mati, 1 = Hidup
BI: 3 Status Aktifkan Pemanasan Awal Status Aktifkan pengontrol saat ini Hanya Baca, 0 = Mati, 1 = Hidup
BI: 4 Status Relai Alarm Status Alarm Relay saat ini Hanya Baca, 0 = Mati, 1 = Hidup
BI: 5 Status Estafet Panas 1 Status terkini dari Heat 1 Relay Hanya Baca, 0 = Mati, 1 = Hidup
BI: 6 Status Estafet Panas 2 Status terkini dari Heat 2 Relay Hanya Baca, 0 = Mati, 1 = Hidup
BI: 7 Status Estafet Panas 3 Status terkini dari Heat 3 Relay Hanya Baca, 0 = Mati, 1 = Hidup
BI: 8 Status Estafet Panas 4 Status terkini dari Heat 4 Relay Hanya Baca, 0 = Mati, 1 = Hidup
BI: 9 Status Estafet Panas 5 Status terkini dari Heat 5 Relay Hanya Baca, 0 = Mati, 1 = Hidup
BI: 10 Status Estafet Panas 6 Status terkini dari Heat 6 Relay Hanya Baca, 0 = Mati, 1 = Hidup
BI: 11 Alarm Mati Darurat Status Alarm Mati Darurat saat ini Hanya Baca, 0 = Mati, 1 = Hidup
BI: 12 Alarm Sensor Udara Keluar 1 Status Alarm Sensor Udara Keluar 1 saat ini Hanya Baca, 0 = Mati, 1 = Hidup
BI: 13 Alarm Sensor Udara Keluar 2 Status Alarm Sensor Udara Keluar 2 saat ini Hanya Baca, 0 = Mati, 1 = Hidup
BI: 14 Alarm Suhu Udara Keluar Rendah Status Alarm Suhu Udara Keluar Rendah saat ini Hanya Baca, 0 = Mati, 1 = Hidup
BI: 15 Alarm Suhu Udara Keluar Tinggi Status Alarm Suhu Udara Keluar Tinggi saat ini Hanya Baca, 0 = Mati, 1 = Hidup
BI: 16 Alarm Sensor Udara Masuk Status Alarm Sensor Udara Masuk saat ini Hanya Baca, 0 = Mati, 1 = Hidup
 

AV: 1

 

Aktifkan Jarak Jauh

 

Mengaktifkan Pemanasan Awal dari ujung depan BACnet®

Baca / Tulis Volatil
0 = Dinonaktifkan, 1 = Diaktifkan
 

AV: 2

 

Titik Setel Udara Keluar Jarak Jauh

 

Mengontrol Titik Setel Udara Keluar dari ujung depan BACnet®

Baca/Tulis Volatil
35.0 derajat Fahrenheit 90.0 derajat Fahrenheit
 

AV: 3

 

Titik Setel Udara Masuk Jarak Jauh

 

Memasukkan Titik Setel Pengaktifan Udara dari ujung depan BACnet®

Baca / Tulis Volatil
-40.0 ºF 90.0 derajat Fahrenheit

Pengidentifikasi Properti PREHEAT-X BACnet®

BACNETPropertyIdentifier : AllAlarmGroup1Bits ::= BIT STRING {

  • Dicadangkan (0),
  • BadLeavingAir1 (1),
  • BadLeavingAir2 (2),
  • LowLeavingAir (3),
  • HighLeavingAir (4),
  • Dicadangkan (5),
  • BadEnteringAir (6),
  • Alarm Komunikasi (7),
  • Alarm Mati (8)

PREHEAT-X Technical Guide G086640 · Rev. F · 240202

  • Dukungan Kontrol AAON:
  • Dukungan Kontrol Weblokasi:
  • Dukungan Teknis Pabrik AAON:
  • Telepon Telepon: 866-918-1100
  • Senin sampai Jumat, pukul 7 hingga 00 Waktu Tengah
  • CATATAN: Sebelum menghubungi Dukungan Teknis, harap siapkan model dan nomor seri unit.
  • BAGIAN: Untuk suku cadang pengganti, silakan hubungi Perwakilan AAON setempat.
  • Apakah Anda seorang Perwakilan AAON?
    • Anda dapat mengunjungi My AAON untuk membuka tiket dukungan baru, berkomunikasi langsung dengan tim dukungan kami, dan melacak kemajuan dukungan Anda dengan mudah dari satu tempat!

Alamat: 2425 South Yukon Ave • Tulsa, OK • 74107-2728

Tanya Jawab Umum

Dokumen / Sumber Daya

AAON PREHEAT-X Series Module Controller [Bahasa Indonesia:] Panduan Pengguna
VCCX-IP Controller, VCCX2 Controller, VCB-X Controller, VCM-X E-BUS Controller, ASM01688, ASM07424, ASM01698, ASM01862, PREHEAT-X Series Module Controller, PREHEAT-X Series, Module Controller, Controller

Referensi

Tinggalkan komentar

Alamat email Anda tidak akan dipublikasikan. Bidang yang wajib diisi ditandai *