ICP DAS DL-100TM485S Thermohygro Meter

ICP-DAS DL-100TM485S-Thermohygro-Meter - product

Specifications

Humidity & Temperature Sensor

  • Humidity Range: 1/4
  • Humidity Resolution: 1/3
  • Humidity Accuracy: 3.0 V
  • Humidity Precision: 64 Hz
  • Temperature Range: +10 ~ +30
  • Temperature Resolution: 0.15 W @ 24 VDC
  • Temperature Accuracy: 82 mm x 172 mm x 55 mm
  • Temperature Precision: 380 mm
  • Dew Point Range: -20 ~ +60
  • Dew Point Resolution: -30 ~ +80

LCD Display

  • LCD Duty: Relative Humidity
  • LCD Bias: 5 ~ 95 RH, Non-condensing
  • LCD Operating Voltage: RS-485; non-isolated
  • LCD Operating Frequency: 1200 ~ 115200 bps

Power

  • Power Protection Required: Power reverse polarity
    protection
  • Supply Voltage: +10 ~ +30 VDC
  • Power Consumption: 0.15 W @ 24 VDC

Mechanical Dimensions

  • Dimensions (W x L x H): 82 mm x 172 mm x 55 mm
  • Cable Length: 380 mm
  • Waterproof Level: IP66
  • Installation: DIN-Rail; Wall mount

Environment

  • Operating Temperature: -20 ~ +60
  • Storage Temperature: -30 ~ +80

Product Usage Instructions

  1. Choose a suitable location based on the environmental requirements.
  2. Mount the device securely using the DIN-Rail or wall mount method.
  3. Ensure proper cable connections following pin assignments.

Modbus RTU Protocol Configuration

To configure the Modbus RTU protocol, follow these steps:

  1. Set the communication Baud Rate to 9600bps.
  2. Ensure parity is set to no parity, data bits to 8, and stop bits to 1.

FAQ (Frequently Asked Questions)
Q: What is the warranty period for DL-100TM485S/DL-100TM485(P)S-W?
A: All products manufactured by ICP DAS are under warranty  regarding defective materials for a period of one year from the date of delivery to the original purchaser.

DL- 100TM485S/DL-100TM485(P)S-W
DL- 100TM485(P)S/

DL- 100TM485(P)S-W User Manual

Warranty
All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery to the original purchaser.

Warning
ICP DAS assumes no liability for any damage resulting from the use of this product. ICP DAS reserves the right to change this manual at any time without notification. The information furnished by ICP DAS is believed to be accurate and reliable. However, no responsibility is assumed by ICP DAS for its use, nor for any infringements of patents or other rights of third parties resulting from its use.

Copyright
Copyright© 2023 ICP DAS. All rights reserved.

Trademarks
Names are used for identification purposes only and may be registered trademarks of their respective companies.

Date: 2023/4/21
DL-100TM485S/DL-100TM485(P)S-W User Manual, V1.00

Introduction

The DL-100TM485S series are the one-channel temperature and humidity data logger module. It contains a single built-in RS-485 communication interface and an LCD indicator to display the module ID, temperature and humidity data, and allows you define the log time interval depending on your application.
The DL-100TM485S series support the Modbus RTU protocol. Refer to Section 2 for more details.
We also provide software Utility that can be used to retrieve log data and display it in a chart on your desktop, and also allow you save the log data into an Excel format file.

Hardware Information

Specifications

Humidity & Temperature Sensor
Humidity Range 0 ~ 100% RH (Relative Humidity)
Humidity Resolution 0.1% RH
Humidity Accuracy ±3.0% RH for non-P version

±1.8% RH for P version

Max.: Refer to Figure 1
Humidity Precision ±0.1% RH
Temperature Range -20 ~ +60℃
Temperature Resolution 0.1℃
Temperature Accuracy ±0.4℃  for non-P version

±0.3℃  for non-P version

Max.: refer to Figure 2.
Temperature Precision ±0.1℃
Dew Point Range Calculated using temperature and

relative humidity

Dew Point Resolution 0.1℃
LCD Display
LCD Duty 1/4
LCD Bias 1/3
LCD Operating Voltage 3.0 V
LCD Operating Frequency 64 Hz
Power
Protection Power reverse polarity protection
Required Supply Voltage +10 ~ +30 VDC
Power Consumption ≤ 0.15 W @ 24 VDC
Mechanical
Dimensions (W x L x H) 82 mm x 172 mm x 55 mm
Cable Length 380 mm
Waterproof Level IP66
Installation DIN-Rail; Wall mount
Environment
Operating Temperature -20 ~ +60℃
Storage Temperature -30 ~+80℃

DL-100TM485S/DL-100TM485(P)S-W

Relative Humidity 5 ~ 95% RH, Non-condensing
Communication
Interface RS-485; non-isolated
Baud Rate 1200 ~ 115200 bps
Protocol Modbus RTU

DL-100TM485S/DL-100TM485(P)S-W

ICP-DAS DL-100TM485S-Thermohygro-Meter - (1)

ICP-DAS DL-100TM485S-Thermohygro-Meter - (2)

Function Block

ICP-DAS DL-100TM485S-Thermohygro-Meter - (2)

Pin Assignments

ICP-DAS DL-100TM485S-Thermohygro-Meter - (3)

Modbus RTU Protocol

The Modbus protocol was originally developed for Modicon controllers by Modicon Inc. Detailed information can be found at http://www.modicon.com/techpubs/toc7.html.

Visit http://www.modbus.org to find more valuable information.
The DL-100TM485S module supports the Modbus RTU protocol. The communication Baud Rate is 9600bps, and the parity, data bits and stop bits are fixed as no parity, 8 data bits and 1 stop bit. The following Modbus functions are supported.

Code Description Address
0x01 Read coils status 0xxxx
0x02 Read discrete inputs 1xxxx
0x03 Read multiple registers 4xxxx
0x04 Read multiple input registers 3xxxx
0x05 Write single coils 0xxxx
0x06 Write single register 4xxxx
0x0F Write multiple coils 0xxxx
0x10 Write multiple register 4xxxx

If the function specified in the message is not supported, then the module responds as follows.

Error Response

00 Address 1 Byte 1 ~ 247
01 Function code 1 Byte Function code + 0x80
02 Exception code 1 Byte 01

If a CRC mismatch occurs, the module will not respond.

Modbus Mapping Table
DL-100TM485S Modbus RTU Tables Coils

Number Address

(Hex)

Function

Code(s)

Access Data

Type

Name Comments
00257 256 01, 02, R/W Bit Enables or disables the logging 0: Disabled
(0x100) 05, 15 Function. 1: Enabled
00258 257 01, 02, R/W Bit Resets the value of the log records Set this bit to on to clear the log data counter
(0x101) 05, 15 counter to 0. value. This bit will be set to 0 when cleared
successfully.
00259 258 01, 02, R/W Bit Set the page of the first log data which There are two pages of log space available in
(0x102) 05, 15 you want to read. the DL-50M, and each page contains 32760
humidity and temperature data records.
10260 259 01, 02 R Bit Reset Bit. This bit only returns a value of 1 when you read
(0x103) it for the first time. In all other cases, it always
returns a value of 0.
10261 260 01, 02 R Bit The page number where the first log data 0: First page
(0x104) record is stored. 1: Second page
10262 261 01, 02 R Bit The page number where the last log data 0: First page
(0x105) record is stored. 1: Second page

Input Registers

Number Address

(Hex)

Function

Code(s)

Access Data

Type

Name Comments
30001 0

(0)

03, 04 R Word Humidity value. The response value is the result of the original

value multiplied by 100.

30002 1

(1)

03, 04 R Word Temperature value in degrees Celsius. The response value is the result of the original

value multiplied by 100.

30003 2

(2)

03, 04 R Word Temperature value in degrees

Fahrenheit.

The response value is the result of the original

value multiplied by 100.

*30004 3

(3)

03, 04 R Word Dew point temperature value in

degrees Celsius.

The response value is the result of the original

value multiplied by 100.

*30005 4

(4)

03, 04 R Word Dew point temperature value in

degrees Fahrenheit.

The response value is the result of the original

value multiplied by 100.

365521 65520 (FFF0) 03, 04 R Word Firmware version. The response value is a hex value. The high byte denotes major version, the low byte

denotes minor version.

365522 65521

(FFF1)

03, 04 R Long HI Module Name. The response value is a hex value. The high

byte denotes ‘D’, the low byte denotes ‘L’.

365523 65522

(FFF2)

03, 04 R Long LO Module Name. The response value is a hex value. The high

byte denotes ‘0’, the low byte denotes ‘50’.

365524 65523

(FFF3)

03, 04 R Word The number of log records. Please refer to Table 1.

DL-100TM485S/DL-100TM485(P)S-W

Value Time Value Time Value Time Value Time
0 10 seconds 3 1 minute 6 1 hour 9 6 hours
1 20 seconds 4 5 minutes 7 2 hours 0x0A 12 hours                 10/22
2 30 seconds 5 10 minutes 8 6 hours 0x0B 1 day

*Requires firmware version V2.02 or higher

Holding Registers

365525 65524 (FFF4) 03, 04

06, 16

R/W Byte The high byte: Module address 1~248
Bit The low byte: The logging mode. 0: The module will stop logging if the EEPROM memory is full.

1: The earliest stored data record will be

overwritten if the EEPROM memory is full.

365526 65525 (0xFFF5) 03, 04

06, 16

R/W Byte The high byte: LCD display items 00~3F
The low byte: The logging time

interval.

The allowed range is from 0 to 0x0B. Refer to

Table 1 for more information.

365527 65526 (0xFFF6) 03, 04

06, 16

R/W Sign Byte The high byte: Module baud rate 06~07

06: 9600 bps; 07:19200 bps

The low byte: The temperature offset

value.

The unit is 0.1 degrees in Celsius, the range is

from -12.8℃ ~ 12.7℃.

365528 65527

(0xFFF7)

03, 04

06, 16

R/W Word The starting address of the logging

data record you want to read.

The response value will be filled with 0x7777

when this value is higher than the last address.

365529 65528

(0xFFF8)

03, 04

06, 16

R/W Byte The numbers of logging data records

you want to read.

The response value will be filled with 0x7777

when this value is higher than the last address.

 

365530

65529 (0xFFF9) 03, 04

06, 16

R/W Word The base year and month values. The response value is a hex value. The high byte denotes the ‘year’, the low byte denotes the

‘month’.

365531 65530 03, 04 R/W Word The base day and hour values. The response value is a hex value. The high byte
(0xFFFA) 06, 16 denotes the ‘day’, the low byte denotes the

‘hour’.

365532 65531 (0xFFFB) 03, 04

06, 16

R/W Word The base minutes and seconds values. The response value is a hex value. The high byte

denotes the ‘minutes’, the low byte denotes the ‘seconds’.

365533 65522 (0xFFFC) 03, 04

06, 16

R/W Word The current year and month values. The response value is a hex value. The high byte denotes the ‘current year’, the low byte denotes

the ‘the month’.

365534 65533 (0xFFFD) 03, 04

06, 16

R/W Word The current day and hour values. The response value is a hex value. The high byte denotes the ‘current day’, the low byte denotes

the ‘current hour’.

365535 65534 (0xFFFE) 03, 04

06, 16

R/W Word The current minute and second values. The response value is a hex value. The high byte denotes the ‘current minute’, the low byte

denotes the ‘current second’.

*365536 65535 03, 04

06, 16

R/W Word The humidity offset value. The unit is 0.01 %, the range is from -100 ~ 100%.

Utility Software

Before you use the Utility Software

  1. Before you use this Utility, please make sure you have installed Microsoft .NET Framework 4. If you haven’t installed .NET Framework yet, please refer to section 2 for more information, or refer to section 3 for more information about the installation of this Utility.
  2. To download .NET Framework, refer:
    http://www.microsoft.com/downloads/en/details.aspx?FamilyID=9cfb2d51-5ff4-4491-b0e5-b386f32c0992&displaylang=en
  3. You also can find the Microsoft .NET Framework 4 web installer package in the following location on the enclosed CD
    (Napdos\Net_FrameWork\dotNetFx40_Full_setup.exe).
  4.  The Utility software is located in the following location on the attached CD: Napdos\DL_100\Utility

 DL-100TM485S Utility

  1. After launching the Utility, the program interface will be displayed, as shown below:
    ICP-DAS DL-100TM485S-Thermohygro-Meter - (3)
    • Clicking “File” or the icon ICP-DAS DL-100TM485S-Thermohygro-Meter - (4) opens a previous DL-100TM485S logging data file stored on your PC.
    • Clicking “Connection->Connect->RS-232/RS-485” or the iconICP-DAS DL-100TM485S-Thermohygro-Meter - (5) creates a connection from the serial port.
    • Clicking “Connection->Disconnect” or the icon ICP-DAS DL-100TM485S-Thermohygro-Meter - (6) disconnects the connection between the PC and the DL-100TM485S.
    • Clicking *“Functions->Get Records” or the icon ICP-DAS DL-100TM485S-Thermohygro-Meter - (7) retrieves the logging data which is stored in the EEPROM of the DL-100TM485S module.
      Clicking *“Functions->Configuration” or the icon ICP-DAS DL-100TM485S-Thermohygro-Meter - (4) enables you to configure the DL-100TM485S module.
    • Clicking “Exit” or the iconICP-DAS DL-100TM485S-Thermohygro-Meter - (9) closes the Utility software.

*This function is only valid when a connection has been successfully established between the PC and the DL-100TM485S module.

Configuration

After a connection between the PC and the DL-100TM485S has been established, click the “ ICP-DAS DL-100TM485S-Thermohygro-Meter - (4) ” icon to configure the

DL-100TM485S. The configuration details are shown follows:

  1. A new menu window would be created and the current module configurations will be displayed. After changing the values, click the “Set” button to update the configurations of the module.
  2.  The Log function would be disabled when you connect to the
    DL- 100 by this Utility software, please remember to enable the log function before you terminate the Utility software.

Appendix

LCD Information

  • Module Address:

ICP-DAS DL-100TM485S-Thermohygro-Meter - (10)

Area LCD value Details
Id Indicates that the currently displayed information is the module address.
00~FF Indicates the current module address.

Temperature Value
ICP-DAS DL-100TM485S-Thermohygro-Meter - (4)

Area LCD value Details
ICP-DAS DL-100TM485S-Thermohygro-Meter - (5)

icon

Indicates that the currently displayed information is the

temperature.

DDD.D~-DD.D Indicates the current temperature value.
℃ or ℉ icon Indicates the temperature units.
  • Dew Point Temperature Value

ICP-DAS DL-100TM485S-Thermohygro-Meter - (6)

Area LCD value Details
ICP-DAS DL-100TM485S-Thermohygro-Meter - (7)

icon

Indicates that the currently displayed information is the

dew point temperature.

DDD.D~-DD.D Indicates the current temperature value.
℃ or ℉ icon Indicates the dew point temperature units.
  • Humidity Value

ICP-DAS DL-100TM485S-Thermohygro-Meter - (1)

Area LCD value Details
icon Indicates that the currently displayed information is the humidity.
DD.D Indicates the current humidity value.
% icon Indicates the humidity units.

DL-100TM485S/DL-100TM485(P)S-W User Manual, V1.00