The Level Display | Controller is designed for industrial use
and must not be used in a household environment or similar
settings. It is essential to follow all safety guidelines and
recommendations provided in the user manual to ensure proper
operation and prevent accidents.

Product Usage Instructions

Safety Information

Before using the unit, ensure to de-pressurize and vent the
system. Confirm chemical compatibility and do not exceed maximum
temperature or pressure specifications to prevent equipment damage
or safety hazards.

Basic Requirements & User Safety

  • Avoid using the unit in areas with excessive shocks,
    vibrations, dust, humidity, corrosive gases, and oils.
  • Do not use tools during installation to prevent damage that may
    void the product warranty.
  • Avoid areas at risk of explosions, significant temperature
    variations, condensation, ice, or direct sunlight.
  • Maintain ambient temperature within recommended values;
    consider forced cooling if necessary.
  • Installation should be done by qualified personnel following
    safety requirements and regulations.
  • Ensure proper grounding and connection to PE wire.
  • Set up the unit correctly according to the application to avoid
    defective operation or accidents.
  • Use additional safety systems in case of unit malfunction that
    poses a serious threat.
  • Always switch off and disconnect the unit from power before
    troubleshooting malfunctions.
  • Ensure neighboring equipment meets safety standards and
    regulations with proper filters.
  • Do not attempt to disassemble, repair, or modify the unit;
    submit defective units for repairs at an authorized service
    center.

Technological Progress

The manufacturer may update the product to the latest technology
without prior notice. For more information on updates and additions
to operating instructions, visit www.iconprocon.com.

Frequently Asked Questions (FAQ)

Q: Can I use the unit in a household environment?

A: No, the unit is designed for industrial use only and should
not be used in a household environment or similar settings.

Q: What should I do if there is a risk of unit
malfunction?

A: In case of a unit malfunction posing a serious threat, use
additional independent systems to prevent harm to people or
property.

LevelPro® — ShoPro
Level Display | Controller
Quick Start Manual

Read the user’s manual carefully before starting to use the unit. Producer reserves the right to implement changes without prior notice.

25-0638 © Icon Process Controls Ltd.

1

LevelPro® — ShoPro
Level Display | Controller

Safety Information
De-pressurize and vent system prior to installation or removal!
Confirm chemical compatibility before use! DO NOT exceed maximum temperature or
pressure specifications!

Warning | Caution | Danger
Indicates a potential hazard. Failure to follow all warnings may lead to equipment damage, or failure, injury, or death.
Note | Technical Notes

ALWAYS wear safety goggles or face-shield during installation and/or service!

Highlights additional information or detailed procedure.

DO NOT alter product construction!
Basic Requirements & User Safety
? Do not use the unit in areas threatened with excessive shocks, vibrations, dust, humidity, corrosive gasses and oils.

Do Not Use Tools
Use of tool(s) may damage produced beyond repair and potentially void product warranty.

? Do not use the unit in areas where there is risk of explosions.
? Do not use the unit in areas with significant temperature variations, exposure to condensation or ice. ? Do not use the unit in areas exposed to direct sunlight.
? Make sure that the ambient temperature (e.g. inside the control box) does not exceed the recommended values. In such cases forced cooling of the unit must be considered (e.g. by using a ventilator).

? The manufacturer is not responsible for any damages caused by inappropriate installation, not maintaining the proper environmental conditions and using the unit contrary to its assignment.
? Installation should be conducted by qualified personnel . During installation all available safety requirements should be considered. The fitter is responsible for executing the installation according to this manual, local safety and EMC regulations.
? GND input of device should be connected to PE wire.
? The unit must be properly set-up, according to the application. Incorrect configuration can cause defective operation, which can lead to unit damage or an accident.

? If in the case of a unit malfunction there is a risk of a serious threat to the safety of people or property additional, independent systems and solutions to prevent such a threat must be used.
? The unit uses dangerous voltage that can cause a lethal accident. The unit must be switched off and disconnected from the power supply prior to starting installation of troubleshooting (in the case of malfunction).
? Neighboring and connected equipment must meet the appropriate standards and regulations concerning safety and be equipped with adequate overvoltage and interference filters.
? Do not attempt to disassemble, repair or modify the unit yourself. The unit has no user serviceable parts. Defective units must be disconnected and submitted for repairs at an authorized service center.

The unit is designed for operation in an industrial environment and must not be used in a household environment or similar.

Technological Progress
The manufacturer reserves the right to revise, alter, or modify the flow meter to the most current technology without special prior notice. Further information about the latest updates and potential additions to these operating instructions are available from www.iconprocon.com

Product Description
The ShoPro® Series Level Display | Controller is the industry’s most rugged and reliable wall-mount remote display.
The ShoPro® comes as a complete all-in-one unit, out of the box it is ready to use. Included is a bright LED display, NEMA 4X enclosure, Polycarbonate faceplate, cord grips and plastic captive screws.
The industrial design ensures that it will withstand the industry’s most corrosive environments. Available with two 5A relays + 4-20mA output.

NEMA 4X Polycarbonate
Enclosure
Wall Mount Brackets
Push Button Easy-Learn® Programming

(cable grips included)

25-0638 © Icon Process Controls Ltd.

2

LevelPro® — ShoPro
Level Display | Controller

Technical Specifications

General

Display Displayed Values Transmission Parameters Stability Housing Material

LED | 5 x 13mm High | Red -19999 ~ 19999 1200…115200 bit/s, 8N1 / 8N2 50 ppm | °C Polycarbonate

Protection Class

NEMA 4X | IP67

Input Signal | Supply

Standard Voltage

Current: 4-20mA 85 – 260V AC/DC | 16 – 35V AC, 19 – 50V DC*

Output Signal | Supply

Standard Voltage Passive Current Output *

2 x Relays (5A) + 4-20mA 24VDC 4-20mA | (Operating Range Max. 2.8 – 24mA)

Performance

Accuracy

0.1% @ 25°C One Digit

Accuracy According to IEC 60770 – Limit Point Adjustment | Non-Linearity | Hysteresis | Repeatability

Temperatures

Operating Temperatures

-20 to 158°F | -29 to 70°C

*Optional

Working Principle
Junction Box ShoPro® Series
Submersible Level Sensor

Features
? All-in-one | Out of the Box Ready to Use ? Visual Alarm — High | Low Level ? 4-20mA Output ? Power Supply Output 24V DC ? New Easy-Learn® Programming ? NEMA 4X Enclosure ? Corrosion Resistant Thermoplastic ? Cord Grips Included ­ No Tools Required

Model Selection

ShoPro® SP100 — Liquid Level LED Display

Part Number SP100
SP100-A SP100-V SP100-A-V

Input 4-20mA 4-20mA 4-20mA 4-20mA

Output 4-20mA 4-20mA + Audible 4-20mA + Visual 4-20mA + Audible & Visual

ABS

PC

25-0638 © Icon Process Controls Ltd.

3

LevelPro® — ShoPro
Level Display | Controller

Installation Instructions
The unit has been designed and manufactured in a way assuring a high level of user safety and resistance to interference occurring in a typical industrial environment. In order to take full advantage of these characteristics installation of the unit must be conducted correctly and according to the local regulations. ? Read the basic safety requirements on page 3 prior to starting the installation. ? Ensure that the power supply network voltage corresponds to the nominal voltage stated on the unit’s identification label.
The load must correspond to the requirements listed in the technical data. ? All installation works must be conducted with a disconnected power supply. ? Protecting the power supply connections against unauthorized persons must be taken into consideration.
Package Contents
Please verify that all listed parts are consistent, un-damaged and included in the delivery/your specified order. After removing the unit from the protective packaging, please verify that all listed parts are consistent, un-damaged and included in the delivery/your specified order.
Any transportation damage must be immediately reported to the carrier. Also, write down the unit serial number located on the housing and report the damage to the manufacturer.
User Manual
Warranty

Wall Mounting

1

2

3

00 mm

00 mm

Ø4.4
Ø8.4
To install device on the wall, a pinholes should be made. The Dimensions of the device and distances between holes.
This part of the case should be mounted to a wall by screws.

R

dSP

SET

F

Sht

www.iconprocon.com

AL SP100

Loosen Screws for Open Display Cover

R

dSP SET F

Sht

www.iconprocon.com

AL SP100

Remove Transparent Cover

4

5

6

R

dSP SET F

Sht

www.iconprocon.com

AL SP100

Mounted to a wall by Screws 25-0638 © Icon Process Controls Ltd.

R

dSP SET F

Sht

www.iconprocon.com

AL SP100

Tighten Srews

R

dSP SET F

Sht

www.iconprocon.com

AL SP100

Insert Transparent Cover
4

LevelPro® — ShoPro
Level Display | Controller

Pipe Clamping Installation

1

2

Do Not Use Tools

3
Do Not Use Tools

Do Not Use Tools

Open Clamp

Quick Wire Connection

1

2

R

SP100

ddSSPP SSEETT F

FSht

www.iconprocon.com

AL AL
R1 SP100
R2

R
SP100

dSP dSP

SET SET

F

F

Sht
F

w w www.wi.cicoonpnropcorn.ococm o n . c o m

AL AL
R1 SP100
R2

Insert Pipe & Lock Clamp

3

R

SP100

dSP dSP

SET SET

F

F

Sht
F

w w w ww.wi.cicoonpnropcorn.ococmo n . c o m

AL R1 SAPL100
R2

Wire Clamp Open

Turn Cable Grip Nut Counter-Clockwise

4

R SP100

dSP

SET

F

dSP SET

F

Sht F

w w w ww.wi.cicoonpnropcorn.ococm o n . c o m

AL AL
R1 SP100
R2

Power Red Terminals : 120V AC wire Blue Terminals : 0V AC wire
4-20mA Output
Sensor Red Terminals : Red wire (+) Blue Terminals : Black wire (-)

Remove Nut and Cable Grip

5

6

R
SP100

dSP dSP

SET SET

F

F

Sht
F

w w www.wi .cicoonpnropcorn.ococmo n . c o m

AL AL
R1 SP100
R2

Insert Cable in Terminal | Wire Clamp Close

Insert Wire in Cable Grip Nut

R

SP100

dSP

SET

F

dSP SET

F

Sht
F

w w w ww.wi.cicoonpnropconr.ocom c o n . c o m

AL R1 SP A1L 00
R2

Turn Cable Grip Nut Clockwise

25-0638 © Icon Process Controls Ltd.

5

LevelPro® — ShoPro
Level Display | Controller

Internal Wire Connection Wiring to a Loop Powered Display :

Examples : Pump Shut-Off Valve Shut-Off
Pump Contactor-Valve

Relay 2
Magnetic Contactor Relay

Relay 1
ProAlert Alarm
Audible / Visual

ShoPro® Channel Terminals
12 11 10 9 8 7 6 5 4 3 2 1 +

R

SP100

ddSSPP SEETT FF

SFht

www.iconprocon.com www.iconprocon.com

AL AL
R1 SP100
R2

100 Series Level Sensor
Shielded cable is recommended for control loop wiring. Use the Red wire as the (+) and the Black wire as the (-).
Exploded View

Power Supply 85-280V Terminal 1 & 2

25-0638 © Icon Process Controls Ltd.

6

LevelPro® — ShoPro
Level Display | Controller

Display Description & Button Functions

Bright Large Display

Programming Push SP100

Buttons

dSP SET F

F

www.iconprocon.com

Alarm LED Indicator (AL)
AL
Relay 1 & 2 LED Indicators (R)

dSP = Display Programming Menu (Press + Hold for at least 3 sec.)

SET = Save the Value

F

=

[F] []

Press + HOLD Back Menu

3

SEC

for

Alarm

Set

= Changing the Values

F

=

[F] Back to Main Display [ ] Changing Menu

Programming Display

STEPS

1

Main Menu

DISPLAY

OPERATION

dSP
3 Sec.

2

Low Level Value

SET

Low Value ­ 4mA = 0

Press SET key for Low Value.

3

Low Value Set

SET

Default Preset = 0000.0 No need to Change.

R

SP100

ddSPP SSEETT FF

FSht

www.iconprocon.com www.iconprocon.com

AL AL R1 R1 SP100 RR22

Default Set to

4mA Empty

4

High Level Value

SET

5

High Level Set

SET

6

Return to Main Display

Enter Max. Tank Value

Press + F to Change # to Desired Value. Note: This value is your max. tank value.

Set High Liquid Level Value

R

SP100

ddSSPP SEETT FF

SFht

w w w . iwcwow.incopnprroococn.coomn . c o m

AL AL

R R1

1

SP100

RR2 2

Press SET to Save.

20mA Value = Max. Fill Height

Return to Main Display

dSPL = Low Value – Empty or Lowest Liquid Level – Factory Default is 0. dSPH = High Value – Enter Figure for Maximum Tank Fill Height.

25-0638 © Icon Process Controls Ltd.

7

LevelPro® — ShoPro
Level Display | Controller

Alarm Set

STEPS

1

Main Display

dSP
3 Sec.

2

Alarm Setting Status

SET

3

Alarm Value Setting

SET

4

Alarm Setting Status

SET

5

Alarm Value Setting

SET

6 Alarm Hysteresis Setting Status

SET

5

Alarm Hysteresis Setting

SET

DISPLAY

OPERATION
1. ALt.0 : 2. ALt.1 :
· PV AL1 AL1 Relay ON · PV < (AL1-HYS) AL1 Relay OFF · PV AL2 AL2 Relay ON · PV < (AL2-HYS) AL2 Relay OFF 3. ALt.2 : · PV AL1 AL1 Relay ON · PV < (AL1-HYS) AL1 Relay OFF · PV AL2 AL2 Relay ON · PV > (AL2+HYS) AL2 Relay OFF 4. ALt.3 : · PV AL1 AL1 Relay ON · PV > (AL1+HYS) AL1 Relay OFF · PV AL2 AL2 Relay ON · PV > (AL2+HYS) AL2 Relay OFF

25-0638 © Icon Process Controls Ltd.

8

LevelPro® — ShoPro
Level Display | Controller
Warranty, Returns and Limitations
Warranty
Icon Process Controls Ltd warrants to the original purchaser of its products that such products will be free from defects in material and workmanship under normal use and service in accordance with instructions furnished by Icon Process Controls Ltd for a period of one year from the date of sale of such products. Icon Process Controls Ltd obligation under this warranty is solely and exclusively limited to the repair or replacement, at Icon Process Controls Ltd option, of the products or components, which Icon Process Controls Ltd examination determines to its satisfaction to be defective in material or workmanship within the warranty period. Icon Process Controls Ltd must be notified pursuant to the instructions below of any claim under this warranty within thirty (30) days of any claimed lack of conformity of the product. Any product repaired under this warranty will be warranted only for the remainder of the original warranty period. Any product provided as a replacement under this warranty will be warranted for the one year from the date of replacement.
Returns
Products cannot be returned to Icon Process Controls Ltd without prior authorization. To return a product that is thought to be defective, go to www.iconprocon.com, and submit a customer return (MRA) request form and follow the instructions therein. All warranty and non-warranty product returns to Icon Process Controls Ltd must be shipped prepaid and insured. Icon Process Controls Ltd will not be responsible for any products lost or damaged in shipment.
Limitations
This warranty does not apply to products which: 1) are beyond the warranty period or are products for which the original purchaser does not follow the warranty procedures outlined above; 2) have been subjected to electrical, mechanical or chemical damage due to improper, accidental or negligent use; 3) have been modified or altered; 4) anyone other than service personnel authorized by Icon Process Controls Ltd have attempted to repair; 5) have been involved in accidents or natural disasters; or 6) are damaged during return shipment to Icon Process Controls Ltd reserves the right to unilaterally waive this warranty and dispose of any product returned to Icon Process Controls Ltd where: 1) there is evidence of a potentially hazardous material present with the product; or 2) the product has remained unclaimed at Icon Process Controls Ltd for more than 30 days after Icon Process Controls Ltd has dutifully requested disposition. This warranty contains the sole express warranty made by Icon Process Controls Ltd in connection with its products. ALL IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE EXPRESSLY DISCLAIMED. The remedies of repair or replacement as stated above are the exclusive remedies for the breach of this warranty. IN NO EVENT SHALL Icon Process Controls Ltd BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING PERSONAL OR REAL PROPERTY OR FOR INJURY TO ANY PERSON. THIS WARRANTY CONSTITUTES THE FINAL, COMPLETE AND EXCLUSIVE STATEMENT OF WARRANTY TERMS AND NO PERSON IS AUTHORIZED TO MAKE ANY OTHER WARRANTIES OR REPRESENTATIONS ON BEHALF OF Icon Process Controls Ltd. This warranty will be interpreted pursuant to the laws of the province of Ontario, Canada.
If any portion of this warranty is held to be invalid or unenforceable for any reason, such finding will not invalidate any other provision of this warranty.
For additional product documentation and technical support visit:
www.iconprocon.com | e-mail: sales@iconprocon.com or support@iconprocon.com | Ph: 905.469.9283

by

Phone: 905.469.9283 · Sales: sales@iconprocon.com · Support: support@iconprocon.com

25-0638 © Icon Process Controls Ltd.

9

Documents / Resources

ICON ShoPro Level Display and Controller Process Controls [pdf] User Manual
ShoPro Level Display and Controller Process Controls, ShoPro, Level Display and Controller Process Controls, Display and Controller Process Controls, Controller Process Controls, Process Controls, Controls

References

Leave a comment

Your email address will not be published. Required fields are marked *