ICON PROCESS CONTROLS TIF Series Batching Paddle Wheel Flow Meter Sensor
Specifications
- Operating Voltage
- Current Compensation Control
- Communication Transmitter
- Relay Output
- Flow Rate GPM | LPM
- Fluid Accuracy
- Response Frequency
- Max Flow Rate
- Min Flow Rate
- Materials of Construction
- O-ring material
- Operating Temperature
- Protection Rating
- Approval *Optional
Product Usage Instructions
Safety Information:
Before installation, ensure to de-pressurize and vent the system. Confirm chemical compatibility and do not exceed maximum temperature or pressure specifications. Always wear safety goggles during installation. Do not alter product construction.
Installation:
- Lubricate O-rings with silicone provided.
- Carefully lower the sensor into the fitting using an alternating twisting motion. Do not force it.
- Ensure tab/notch are parallel to flow direction.
- Hand tighten the sensor cap. Do not use tools.
Correct Sensor Position Setup:
Ensure there are no air bubbles in the liquid media being measured. The pipe must always remain full. The flow meter needs to be placed in a straight run pipe with a minimum distance upstream and downstream of the flow sensor for accurate measurement.
FAQ
Q: What should I do if I encounter sediment during installation?
A: If sediment is present, refer to Figure-3 for the preferred installation method.
Q: Can I use tools to tighten the sensor cap?
A: No, hand tightening is recommended to prevent damage to the product.
Read the user’s manual carefully before starting to use the unit. Producer reserves the right to implement changes without prior notice.
Safety Information
- De-pressurize and vent system prior to installation or removal
- Confirm chemical compatibility before use
- DO NOT exceed maximum temperature or pressure specifications
- ALWAYS wear safety goggles or face-shield during installation and/or service
- DO NOT alter product construction
General Information
Function/Description | Specification |
Operating Voltage | 10 – 30VDC |
Current Compensation | 60mA max. |
Control Communication | RS-485 Modbus |
Transmitter | 4-20mA |
Relay Output | 10A 30VDC | NO | NC |
Flow Rate GPM | LPM | 0.0 – 999.9 |
Fluid | H2O | Liquid Chemical Media |
Accuracy | ± 0.5% of F.S. @25ºC |
Response Frequency | 5K Hz |
Max Flow Rate | 10m/s | 33ft/s |
Min Flow Rate | 0.1m/s | 0.3ft/s |
Materials of Construction | Rotor: ETFE Tefzel® | Rotor Pin: Zirconium Ceramic | Rotor Bushings: Ceramic Sensor Body: PVC/PP/PVDF/316SS |
O-ring material | FPM | EPDM* | FFKM* |
Operating Temperature | PVC < 60ºC | PP < 80ºC | PF < 100ºC |
Protection Rating | NEMA 4X | IP66 | General Purpose |
Approval | CE | RoHS |
Installation
Very Important
- Lubricate O-rings with silicone (provided).
- Using an alternating twisting motion, carefully lower the sensor into the fitting. | Do Not Force | See Fig 5
- Ensure tab/notch are parallel to flow direction | See Fig-2
Hand-tighten the sensor cap. DO NOT use tools.
Correct Sensor Position
- Locate the flow meter positioning tab and clamp saddle notch.
- Engage one thread of the sensor cap, then turn the sensor until the alignment tab is seated in the fitting notch.
Ensure tab is parallel to flow direction. - Hand tighten
DO NOT use tools
Ensure meter is firmly in place
Correct Sensor Position Setup
TI Series flow meters measure liquid media only. There should be no air bubbles and the pipe must always remain full. To ensure accurate flow measurement, the placement of the flow meter needs to adhere to specific parameters. This requires a straight run pipe with a minimum number of pipe diameters distance upstream and downstream of the flow sensor.
Terminal Connections
Fittings and K-Factor
Programming
Programming Frequency Pulse Relay Output
Programming Relay Output
Relay Selection Mode
ALT NO. | Description |
ALt = 0 | CV > SV ▶ ON: CV < SV – HyS ▶ OFF “Normally Closed Relay” |
ALt = 1 | CV < SV ▶ ON: CV > SV + HyS ▶ OFF “Normally Open Relay” |
ALt = 2 | SV + HyS > CV > SV – HyS ▶ ON: CV > SV + HyS or CV < SV – HyS ▶ OFF |
ALt = 3 | SV + HyS > CV > SV – HyS ▶ OFF: CV > SV + HyS or CV < SV – HyS ▶ ON |
HyS = Hysteresis — Acts like a buffer ± around pulse output (measured in GPM) | |
CV: Current Value = Flow Rate | SV = Selected or Programmed Value |
Reset Flow Totalizer
Press keys for 3 seconds to reset the flow totalizer.
Min | Max Flow Rates
PIPE SIZE | GPM | LPM |
½” | DN15 | 1.0 | 3.5 | 32 | 120 |
¾” | DN20 | 1.5 | 5 | 45 | 170 |
1″ | DN25 | 2.5 | 9 | 79 | 300 |
1½” | DN40 | 6.5 | 25 | 225 | 850 |
2″ | DN50 | 10.5 | 40 | 357 | 1350 |
PIPE SIZE | GPM | LPM |
3″ | DN80 | 24 | 90 | 739 | 2800 |
4″ | DN100 | 33 | 125 | 1149 | 4350 |
6″ | DN150 | 60 | 230 | 1997 | 7590 |
8″ | DN200 | 82 | 315 | 2735 | 10395 |
Rotor Pin | Paddle Replacement
Warranty, Returns and Limitations
Warranty
Icon Process Controls Ltd warrants to the original purchaser of its products that such products will be free from defects in material and workmanship under normal use and service in accordance with instructions furnished by Icon Process Controls Ltd for a period of one year from the date of sale of such products. Icon Process Controls Ltd obligation under this warranty is solely and exclusively limited to the repair or replacement, at Icon Process Controls Ltd option, of the products or components, which Icon Process Controls Ltd examination determines to its satisfaction to be defective in material or workmanship within the warranty period. Icon Process Controls Ltd must be notified pursuant to the instructions below of any claim under this warranty within thirty (30) days of any claimed lack of conformity of the product. Any product repaired under this warranty will be warranted only for the remainder of the original warranty period. Any product provided as a replacement under this warranty will be warranted for the one year from the date of replacement.
Returns
Products cannot be returned to Icon Process Controls Ltd without prior authorization. To return a product that is thought to be defective, go to www.iconprocon.com, and submit a customer return (MRA) request form and follow the instructions therein. All warranty and non-warranty product returns to Icon Process Controls Ltd must be shipped prepaid and insured. Icon Process Controls Ltd will not be responsible for any products lost or damaged in shipment.
Limitations
This warranty does not apply to products which: 1) are beyond the warranty period or are products for which the original purchaser does not follow the warranty procedures outlined above; 2) have been subjected to electrical, mechanical or chemical damage due to improper, accidental or negligent use; 3) have been modified or altered; 4) anyone other than service personnel authorized by Icon Process Controls Ltd have attempted to repair; 5) have been involved in accidents or natural disasters; or 6) are damaged during return shipment to Icon Process Controls Ltd reserves the right to unilaterally waive this warranty and dispose of any product returned to Icon Process Controls Ltd where: 1) there is evidence of a potentially hazardous material present with the product; or 2) the product has remained unclaimed at Icon Process Controls Ltd for more than 30 days after Icon Process Controls Ltd has dutifully requested disposition. This warranty contains the sole express warranty made by Icon Process Controls Ltd in connection with its products.
ALL IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE EXPRESSLY DISCLAIMED. The remedies of repair or replacement as stated above are the exclusive remedies for the breach of this warranty. IN NO EVENT SHALL Icon Process Controls Ltd BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND I NCLUDING PERSONAL OR REAL PROPERTY OR FOR INJURY TO ANY PERSON. THIS WARRANTY CONSTITUTES THE FINAL, COMPLETE AND EXCLUSIVE STATEMENT OF WARRANTY TERMS AND NO PERSON IS AUTHORIZED TO MAKE ANY OTHER WARRANTIES OR REPRESENTATIONS ON BEHALF OF Icon Process Controls Ltd. This warranty will be interpreted pursuant to the laws of the province of Ontario, Canada.
If any portion of this warranty is held to be invalid or unenforceable for any reason, such finding will not invalidate any other provision of this warranty.
For additional product documentation and technical support visit:
www.iconprocon.com | e-mail: sales@iconprocon.com or support@iconprocon.com | Ph: 905.469.9283