EcoNet HTPG0125 Enabled Unit Coolers
Specifications
- Product: EcoNet Enabled Unit Coolers
- Designed for: Walk-in coolers and freezers
- Features: Energy-saving, precise superheat and space temperature control, fan cycling, reduced defrosts, reduced compressor runtime, reduced liability, improved product quality
- Compatibility: Single or dual evaporator coils, condensing unit in single and multiple evaporator installations
System Installation
Follow the installation guidelines provided in the manual to set up the EcoNet Enabled Unit Coolers in walk-in coolers or freezers.
Start-Up/Commissioning
Initiate the system by accessing the General Settings, Status Screens, Basic Settings, Lead/Lag Settings, Defrost Settings, Auxiliary Relay Settings, Digital Input Settings, and BACnet MS/TP Settings as outlined in the manual.
Operational Overview
Understand how the unit operates to maximize its efficiency andperformance in controlling space temperature and superheat while reducing energy consumption.
Diagnostics
Learn how to troubleshoot and identify any issues with the unit by referring to the diagnostic section of the manual.
Compressor Control
For packaged refrigeration units, follow the instructions provided to control the compressor efficiently.
Defrost Pump Down Delay
Set up the defrost pump down delay feature to optimize defrost cycles and energy usage.
Leak Detection
Utilize the leak detection functionality to promptly identify and address any refrigerant leaks.
Lead/Lag
Configure lead/lag settings to ensure proper operation and maximize energy efficiency in multi-unit installations.
Operational Limits
Understand and adhere to the operational limits to prevent any potential damage or malfunctions.
Replacement Parts
If replacement parts are needed, refer to the list provided in the manual for compatibility and proper installation.
FAQs
Q: How do I replace a Legacy EcoNet Controller with a New EcoNet Controller?
A: Refer to page 22 of the manual for detailed instructions on replacing the legacy controller with the new one.
Q: What are the key features of the EcoNet Enabled Unit Coolers?
A: The key features include precise superheat and space temperature control, fan cycling, reduced defrosts, reduced compressor runtime, reduced liability, improved product quality, and energy savings.
“`
EcoNet Enabled Unit Coolers are intelligent, electronically operated evaporators for walk-in coolers and freezers designed for easier installation and energy savings. Developed in conjunction with Rheem Manufacturing, it builds on the success, reliability, and efficiency of the EcoNet technology and brings it to commercial refrigeration.
EcoNet Enabled Unit Coolers save energy in refrigeration systems through precise superheat and space temperature control, fan cycling, and controlling how often the system goes into defrost based on compressor runtime.
It eliminates unnecessary defrosts, maximizes energy efficiency with less compressor runtime, reduces liability by eliminating icing issues, reduces fan speed to 50% during off cycle to save energy, and reduces temperature fluctuations by regulating defrosts for improved product quality. EcoNet Enabled Unit Coolers can be configured to work on a single or dual evaporator coil and can be used with a condensing unit in single and multiple evaporator installations as a group.
ECONET BOARD
Auxiliary Temp Sensor BACnet MS/TP
Drain Temp Sensor
24VDC Power Supply
EcoNet Communication Terminals
Space Temperature Sensor
Wire Harness Connector Terminal · Suction Pressure Transducer · Suction Temperature Sensor · Evap. Temperature Sensor 1 · Evap. Temperature Sensor 2 (center mount/low velocity evaporators only) · EXV Connector
Digital Input Terminals
Controller Display and Navigation Buttons
Analog Fan Control Terminal
Auxiliary Relay Outputs
Figure 1
Defrost Relay Outputs
UNIT COOLERS // ECONET ENABLED
Main Power Terminal
PAGE 3
SAFETY CONSIDERATIONS
Failure to read and follow all instructions carefully before installing or operating this control and system could cause personal injury and/or property damage.
NOTES: All wiring must comply with national, local, and state codes.
· Before service, power to the unit should be disconnected per proper lockout procedures. · After power is disconnected wait 5 minutes before touching the board for power stored
to fully discharge. · The control board has no user serviceable parts, do not try to repair. · Do not wire the control board while powered. · If the board becomes corroded replace immediately. Cleaning of the control board is
not recommended.
PAGE 4
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
SYSTEM INSTALLATION
EVAPORATOR
· EcoNet Enabled Unit Coolers ship with the EcoNet controller installed and all sensors and relays wired. Prior to installation, you must verify that all sensors, defrost heaters and wire harnesses are securely connected to the controller board and terminal board.
· Connect main power to the evaporator unit at the L1/L2 and GND terminals on the terminal board as shown in the wiring diagram (Figures 1 & 2).
EcoNet controller supports 230 VAC or 115 VAC, 50/60 Hz power supply. Controller will automatically detect voltage and operate accordingly.
CAUTION: If changing the supply voltage from 115 to 230 VAC, wait until the board is completely drained and no lights are visible before applying new power supply, or damage to controller may occur.
WARNING: Disconnect power to the outdoor and indoor units before beginning installation
· Only a trained service professional/ contractor should use or interact with the control board.
· Except for the display navigation buttons, never touch the control board surface directly to avoid static shock damage or exposure to high voltages.
Figure 2
UNIT COOLERS // ECONET ENABLED
PAGE 5
Main Power L1/L2 Terminals GND Terminals
Figure 3
NOTE: If the controller loses power, it will close the EXV automatically. · Prior to installation, please refer to factory label at evaporator unit for correct voltage and amp draw requirements to verify circuit breaker size where unit will be connected to.
CONDENSING UNIT
1. If a defrost timer is installed on the condensing unit, make sure it is disconnected/ disabled (all switches on time clock should be in the OFF position) (Figure 4). All defrost functions are performed by the controller board.
2. Please refer to factory label at condensing unit for correct voltage and amp draw requirements.
PAGE 6
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
Figure 4
DURING SYSTEM INSTALLATION
1. Refrigerant Line Brazing a. Cover EXV with wet rag to protect from excess heat from torch. b. Suction Temp Sensor (Figure 5) must be removed from the suction line prior to brazing. The sensor must be reinstalled on the suction line (10 or 2 o’clock position) after brazing is completed and the tubing has been allowed to cool down. Secure the Suction Temp thermistor to suction line as shown in Figure 5. After suction temp sensor is installed, suction line should be insulated, and the sensor should be covered with the insulation.
Figure 5
2. Purging Lines (pulling vacuum), two options:
a. To purge lines on system with EXV closed, make sure that controller is off, and pull vacuum from both suction and discharge ports at the condensing unit.
b. OR, to purge lines on system with EXV open, power up the controller and wait a couple of minutes for the controller to command the valve to open. Leave controller powered on while system evacuation is being done.
3. While charging the system with refrigerant, ensure that the EXV is open by powering up the controller and waiting a couple of minutes for the controller to command the EXV to open. With the controller powered on while the system is being charged, make sure to monitor the suction pressure, suction temperature, and superheat via the controller display and also via installer’s gauges. Please refer to Display Status under the Start-Up/Commissioning section to show on the controller display the current suction temperature, suction pressure, EXV position and calculated superheat.
UNIT COOLERS // ECONET ENABLED
PAGE 7
NOTES: If there is a power loss at any time during normal system operation, the controller will close the EXV, forcing a pumpdown. When starting up the system for the first time, the controller will turn the fans on when the Evap Temp gets below a preset temperature.
4. Power Supply a. Please refer to factory label on evaporator and condensing unit for MCA/MOPD ratings. If powering up evaporator on same circuit as condensing unit, please refer to evaporator wiring diagram on cover panel for compressor lockout terminal wiring (if available).
START UP | COMMISSIONING
1. Local Display (Figure 6) a. Use the UP/DOWN/SEL/BACK buttons to navigate through the display. b. To change a parameter, navigate to it using the UP/DOWN buttons, press SEL to have selection start flashing intermittently, use the UP/DOWN buttons to cycle through the selection, then press SEL again to confirm the selection.
UP/DOWN
Navigation
Buttons
SEL/BACK
Navigation
Buttons
Figure 6
PAGE 8
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
2. Navigation Overview a. Main Screen
SPACE TEMP Press “SEL”
XX.XX F
Press “BACK”
SETTINGS
STATUS
SERVICE
b. Settings Overview – see page 10 c. Status Overview – see page 11 d. Service
SERVICE
Press “SEL” Press “BACK”
CURRENT ALARMS
ALARM HISTORY
DEFROST CONTROL START/STOP/OFF
SOFTWARE VERSION HT-PG02-00-01-00
UNIT COOLERS // ECONET ENABLED
PAGE 9
b. SETTINGS OVERVIEW
SETTINGS
Press “SEL” Press “BACK”
Set Point XX.XX F
System Enabled Yes/No
Group- Member Cfg. No/Gx-L
Network Instance 1-32
See BACnet Settings on
page 20
Press “SEL”
EQUIPMENT
Press “BACK”
BASIC
See Basic Settings on page 12
Press “SEL”
TIME & DATE
Press “BACK”
Year 20XX
DEFROST
See Defrost Settings on
page 14
Month of Year Jan-Dec
AUX RELAY CONTROL
See Aux Relay
Settings on page 16
BACnet
Day of Month XX
Hour of Day XX
See Digital
DIGITAL INS Input Settings
CFG.
on page 17
See Lead Lag
LEAD/LAG Settings on
page 18
GENERAL SETTINGS MENU
Minute of Hour XX
BASIC SETTINGS
Set Point
RANGE
Freezer: -40°F to 60°F; Cooler:
25°F to 60°F
System Enabled
Yes/No
Group Member Cfg
Network Instance Equipment
*See group member list on
page 27
1 – 32
–
Time and Date
–
BACnet
–
DEFAULT -10°F for Freezer; 35°F for Cooler
Yes
No
1 –
DESCRIPTION
Configure the desired temperature setpoint. This setting is synced between Leader and Followers in a Group, and also between Manager and Partner controllers in Lead-Lag operation.
Set to YES to enable controller cooling operation. Set to NO to force system pump down; controller will close the EEV and turn the fans off. Allows for system pump down while controller is still powered on. NOTE: There is no time limit on this setting; make sure System Enable is set back to YES to allow controller to resume cooling operation. This setting is to address the controller as part of a group if multiple evaporators will be wired together to cool the same space. See Group Operation section on page 27 for more details. This setting is to address the controller to work as a standalone unit, but wired to other evaporators on the same communication bus with a Command Center Display. See Equipment Settings section starting on page 12 for details. Configure hour, minute, day, month and year on the controller for Alarm History time stamp. See BACnet MS/TP section on page 20 for configuration details.
PAGE 10
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
c. STATUS OVERVIEW
STATUS
Press “SEL”
STATUS
Press “BACK” SENSORS
STATUS INPUTS STATUS OUTPUTS
STATUS EXV
STATUS DEFROST LEAD/LAG
Press “SEL” Press “BACK”
Space Temp XX.XX F
Evap Temp XX.XX F
Evap Temp 2 XX.XX F
Suction Temp XX.XX F
Sat. Suction Temp XX.XX F
Suction Pressure XX.XX PSIG
Drain Temp XX.XX F
Auxiliary Temp XX.XX F
Press “SEL” Press “BACK”
Press “SEL” Press “BACK”
Press “SEL” Press “BACK”
Press “SEL” Press “BACK”
See LEAD/LAD Section on page
18
Digital #1 Input On/Off
Digital #2 Input On/Off
Defrost #1 Relay On/Off
Digital #3 Input On/Off
Defrost #2 Relay On/Off
Aux #1 Relay On/Off
Aux #2 Relay On/Off
EXV Current Pos 50.00%
Superheat X.X F
Superheat Setpt 6.5 F
Last Defr. Time 25.0 MIN
Nxt.Def.Cmp.Time 360.0 MIN
UNIT COOLERS // ECONET ENABLED
PAGE 11
d. BASIC SETTINGS OVERVIEW
BASIC
Press “SEL” Press “BACK”
Cooler/Freezer Freezer
Refrigerant R448A
Evap Coil Type Single/Dual
Fan Control Cnfg Relays/Analog
SetPoint Control 2.0 F
Cmp. Min Run Time 5 Mins
Comp Run Time Alert 120 Mins
EXV Stepper Type 2500 Bi-Polar
EXV SH Set Point 6.5 F
SUPPORTED REFRIGERANTS
R404A R407A R407C R448A (Default) R449A R450A R507A R513A R454C* R455A* R454A*
R22 CO2** R454B* R32*
*Leak Detector required for A2L evaporator models. **700 PSI transducer required (HTPG part no. 08540186)
NOTE: See Leak Detection section on Page 37 for details
Figure 7
EXV Start Delay 60 sec.
EXV Last Pos. Min. 35%
EXV Last Pos. Max 65%
EXV STEPPER TYPE
2500 Bi-Polar 480 Bi-Polar 2600 Bi-Polar 500 Uni-Polar
APPLICABLE VALVE MAKE & MODEL
Sporlan SER ***Carel E2V, E3V, E4V
***Sanhua VPF Sporlan OEV OR ***Sanhua LPF
***Check with Applications Engineering for availability.
PAGE 12
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
BASIC SETTINGS MENU
BASIC SETTINGS
RANGE
DEFAULT
DESCRIPTION
Cooler/ Freezer
Refrigerant
Cooler or Freezer
*See Refrigerants table on page
12
Freezer R448A
Set the controller for the type of operation it will be used in. If set as “Freezer”, the controller will use the defrost relays to activate the electric heaters in the evaporator and allow a drain time at the end of the defrost cycle. If set as “Cooler”, the unit will operate as air defrost (offcycle).
Set the refrigerant that will be used in the system from among the list of supported refrigerants. See page 12 for list of refrigerants.
Evap Coil Type
Single or Dual
Single
Set for the type of evaporator being used. “Single” applies to Low Profile, Medium Profile, Warehouse, Heavy Duty and Packaged Refrigeration Units. “Dual” applies for Center Mount/ Low Velocity evaporators where Evap Temp 2 sensor is used.
Fan Control
Setpoint Control
Relays or Analog
0.5 to 20.0 dF
Relays 2.0 dF
Configure the evaporator fan motor type to be used. “Relays” will have the controller use the Aux Relays to control the fan motor; “Analog” will have the controller use the Analog Output port to control the evaporator fan motor (check with HTPG Applications Engineering for analog fan motor availability). Set to configure desired hysteresis range for space temperature control. When the system is in Refrigeration mode, if the Setpoint is -10F with a default Setpoint Control of 2.0 dF, the unit will continue to cool the space until Space Temp reaches -10F. When Space Temp rises above -8F, the controller will start a new cooling cycle.
Cmp. Min Run Time
3 min; 4 min; 5 min
Cmp. Run Time Alert
0 to 480 mins.
EXV Stepper Type
EXV SH Setpoint
2500 Bi-Polar; 480
Bi-Polar; 2600 Bi-Polar; 500
Uni-Polar
4.0 to 20.0 dF
EXV Start Delay
0-255 sec.
5 min
120 min
2500 Bi-Polar
6.5 dF
60 sec.
Adjust the minimum compressor run time for each cooling cycle. When refrigeration mode starts, the system will run for the minimum time that has been configured, regardless of space temperature having reached setpoint.
Set to configure the allowed refrigeration run time until a temperature alarm is flagged. If the unit is on an active refrigeration cycle for longer than this period, the “A108 Cooler/Freezer not Satisfying Setpnt. Alert” will be generated to indicate that the system has not achieved setpoint.
Configure the stepper valve type used with the controller. This setting will be configured at the factory on new evaporators to match the valve that is installed. Refer to the list on page 12 for each valve manufacturer. See Addendum B for valve wiring pinout information.
Set to configure desired superheat setpoint.
When a cooling cycle starts, the controller will open and hold the EXV at a fixed position for this delay duration. After the delay, the EXV will start modulating position to reach superheat setpoint.
EXV Last Pos. Min.
15% – 100%
When a cooling cycle starts, the controller will open and hold the EXV to the last known
35%
position from the previous cooling cycle, but no less than the EXV Last Pos. Min. setting and no more than the EXV Last Pos. Max. setting. The controller will not allow this setting to be
greater than EXV Last Pos. Max. setting.
EXV Last Pos. Max
65% – 100%
When a cooling cycle starts, the controller will open and hold the EXV to the last known
65%
position from the previous cooling cycle, but no less than the EXV Last Pos. Min. setting and no more than the EXV Last Pos. Max. setting. The controller will not allow the EXV Last Pos.
Min. setting to be greater than this setting.
UNIT COOLERS // ECONET ENABLED
PAGE 13
e. DEFROST SETTINGS OVERVIEW
DEFROST
Press “SEL” Press “BACK”
Defrost Type Timed/Adaptive
Def. Max Run Time 60 min
Def.Cmp.Run Time 360 min
Def.Adpt.Run Time 720 min
Def. Term Temp 55 F
Fan Delay Temp 35 F
Def.Rly1 Control No Pulse Relay 1
Drain Temp Def. SP 40°F
Drain Tmp. Def. Offs 10°F
Def.Pmp.Dn.Delay 1 min
Def. Drain Time 300 sec
PAGE 14
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
DEFROST SETTINGS MENU
DEFROST SETTINGS
RANGE
DEFAULT
DESCRIPTION
Defrost Type
Timed; Adaptive
Def. Max Run Time
10-60 min
Timed
Select desired defrost algorithm: Timed or Adaptive. Note: Adaptive defrost only applies if controller is set to Freezer. If controller is set to Cooler, Timed defrost will always remain as the functional setting. See Defrost Mode section on page 24 for more information.
60 min
Set to configure the maximum allowed defrost time.
Def. Cmp. Run Time
0-900 min
360 min
Set to configure the allowed compressor run time before the unit goes into defrost when controller is set to Timed Defrost. See Defrost Mode section on page 24 for more information.
Def. Adpt. Run 360-900
Time
min
720 min
Set to configure allowed compressor run time before unit goes into defrost when controller is set to Adaptive Defrost. See Defrost Mode section on page 24 for more information.
Def. Term. Temp
35°F – 65°F
55°F (Freezer);
40F (Cooler)
Sets the Defrost Termination Temperature; the temperature that the evaporator must reach to terminate the defrost cycle. Note: if the Cooler/Freezer setting is manually adjusted, the Defrost Termination Temp setting will revert to default (55°F for Freezer, 40°F for Cooler); if a value other than default is desired, make sure that Cooler/Freezer is set prior to adjusting the Defrost Termination Temperature.
Fan Delay Temp
25°F – 70°F
35°F (Freezer);
55°F (Cooler)
Sets the temperature that the evaporator must reach before allowing the fans to run during an active cooling cycle. Note: if the Cooler/Freezer setting is manually adjusted, the Fan Delay Temp setting will revert to default (35°F for Freezer, 55°F for Cooler); if a value other than default is desired, make sure that Cooler/Freezer is set prior to adjusting the Fan Delay Temperature.
Def. Rly 1 Control
No Pulse Relay 1; Drain Pan Defrost
No Pulse Relay 1
A. No Pulse Relay 1: relay remains continuously on for the duration of the electric defrost cycle. B. Drain Pan Defrost: relay will cycle on and off depending on Drain Temperature sensor. Note: Drain Temp sensor must be installed and connected, otherwise the controller will alarm “A104 Drain Temp Thermistor Failure” and keep the relay on for the duration of the defrost cycle. See Page 25 for more details.
Drain Temp Def. SP
20°F-80°F
40°F
When Defrost Relay 1 Control is set to “Drain Pan Defrost”, this is the cut-in setpoint for Defrost Relay 1. See page 25 for more details.
Drain Tmp Def. Offs.
1°F – 20°F
10°F
When Defrost Relay 1 Control is set to “Drain Pan Defrost”, this is the cut-out offset for Defrost Relay 1. See page 25 for more details.
Def. Pmp. Dn. Delay
0 – 5 min
Def. Drain Time
0 – 600 sec
1 min
Set desired delay for pump down before electric heaters become active at the start of an electric defrost cycle. See page 35 for more details.
300 sec Adjust the drain time duration following an electric defrost cycle.
UNIT COOLERS // ECONET ENABLED
PAGE 15
f. AUX RELAY SETTINGS OVERVIEW
AUX RELAY CONTROL
Press “SEL” Press “BACK”
Aux Relay Config Comp/Fan Control
Cmp.CutOut Setp. 0 PSIG
Cmp.Cut-In Offs. 20 PSIG
Aux Sensor ? Yes/No
AuxTemp Cond Setp 50°F
AUX RELAY CONTROL SETTINGS MENU
AUX RELAY CONTROL
RANGE
DEFAULT
AuxTemp Cond Diff 5 F
DESCRIPTION
Aux Relay Config
Comp/Fan Control; Fan Control;
Cmp/Cond Control;
Alarm/Alert OUT; None
Comp/ Fan
Control
Configure how the Aux Relays on the controller will be used: A. Comp/Fan Control: controller will use Aux Relay 1 for evaporator fan on/off control, and Aux Relay 2 for compressor on/off control. Note: This setting is for Packaged Refrigeration Systems with dual speed evaporator fan motor. See Packaged Refrigeration System section on page 33 for more details.
B. Fan Control: controller will use Aux Relays 1 and 2 for evaporator fan on/off and speed control. Not for use with Packaged Refrigeration Systems!!
C. Cmp/Cond Control: controller will use Aux Relay 1 for condenser fan speed control, and Aux Relay 2 for compressor on/off control. Note: This setting is intended for Packaged Refrigeration Systems with analog fan motor on the evaporator. Under this setting, the evaporator fan is controlled by the Analog Output port. Please check with Application Engineering for analog fan motor availability. D. Alarm/Alert OUT: controller will turn on Aux Relay 1 if there is a critical alarm active, and Aux Relay 2 if there is a non-critical alert active. Note: Under this setting, the evaporator fan is controlled by the Analog Output port. Please check with Application Engineering for analog fan motor availability.
E. None: Aux Relays are not used.
Cmp. Cut Out Setpoint
-5 PSIG to 60 PSIG
0 PSIG (Freezer); 20 PSIG (Cooler)
Cmp. Cut In 10 PSIG to 50
Offset
PSIG
20 PSIG
Aux Sensor? Yes/No
No
Aux Temp Cond Setp.
0°F to 80°F
50°F
Aux Tmp Cond Diff.
2°F to 40°F
5°F
Pressure setpoint at which the compressor (Aux Relay 2) will turn off when Aux Relay Config. is set to either Comp/Fan Control or Cmp/Cond Control. Please refer to Packaged Refrigeration System section on page 33 for more details. Note: if the Cooler/Freezer setting is manually adjusted, the CutOut Setpoint setting will revert to default (0 PSIG for Freezer, 20 PSIG for Cooler); if a value other than default is desired, make sure that Cooler/Freezer is set prior to adjusting the Cut-Out Setpoint.
Pressure differential for compressor (Aux Relay 2) to turn on when Aux Relay Config. is set to either Comp/Fan Control or Cmp/Cond Control. Please refer to Packaged Refrigeration System section on page 33 for more details.
Configure Aux Temperature sensor for Aux Relay 2 condenser fan speed control. This setting only applies if Fan Control is set to “Analog” for evaporator fans and Aux Relay Config. is set to “Cmp/ Cond Control.” Please check with Application Engineering for analog fan motor availability. Temperature setpoint for Aux Temp sensor to cycle condenser fan to low speed on a Packaged Refrigeration System. This setting only applies if Fan Control is set to “Analog” for evaporator fans and Aux Relay Config. is set to “Cmp/Cond Control.” Please check with Application Engineering for analog fan motor availability. Temperature differential setpoint for Aux Temp sensor to cycle condenser fan to high speed on a Packaged Refrigeration System. This setting only applies if Fan Control is set to “Analog” for evaporator fans and Aux Relay Config. is set to “Cmp/Cond Control.” Please check with Application Engineering for analog fan motor availability.
PAGE 16
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
g. DIGITAL INS CFG. SETTINGS OVERVIEW
DIGITAL INS CFG.
Press “SEL” Press “BACK”
Door SW.Config Off
Door SW.Time 0 sec
Leak SW. Config
N.O.
DIGITAL INPUT SETTINGS MENU
DIGITAL INS CFG.
RANGE
DEFAULT
DESCRIPTION
Door Sw. Config.
Door Sw. Time
Leak Sw. Config.
Off/N.O./ N.C.
Off
0 sec/30 sec/1 min/2 min/3 min/4 min/5 min
0 sec
Off/N.O./N.C. N.O.
Configure the use of a door switch on Digital Input #1 to be either Normally Open (N.O.) or Normally Closed (N.C.). Default setting is Off. Please refer to Door Switch section on page 29 for more details.
If using a door switch, this setting adjusts the delay for the “T003 Door Open Alert” notification to appear and the system to pump down. Please refer to Door Switch section on page 29 for more details.
Configure the use of a leak detector device on Digital Input #2 to be either Normally Open (N.O.) or Normally Closed (N.C.). Please refer to Leak Detection section on page 37 for more details.
UNIT COOLERS // ECONET ENABLED
PAGE 17
h. LEAD/LAG SETTINGS SUB-MENU OVERVIEW
LEAD/LAG
Press “SEL” Press “BACK”
Lead/Lag Select Off
Partner Instance No
Cmp. Run Limit Hrs 112
Set Point XX.XX °F
Cmp. Run Time Alert 120 min
i. LEAD/LAG STATUS SUB-MENU
STATUS LEAD/LAG
Press “SEL” Press “BACK”
Lead/Lag Control Mngr./Partner/Both/
Neither
Run Status Okay
Run Stat Partner
***
Okay
Disable Command Yes/No
Time Until Switch 112 Hrs
*** Visible only if controller is set to Lead/Lag Manager.
PAGE 18
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
LEAD/LAG SETTINGS MENU
LEAD/LAG
RANGE
DEFAULT
DESCRIPTION
Lead/Lag Select
Off/Manager/Partner
Off
Configure the controller to be either the Manager or the Partner on a lead/lag setup, or None for no lead/lag control. Please refer to Lead/ Lag section on page 41 for more details.
Partner Instance
No,1-32,G1,G2,G3,G4
No
At the Manager controller, select the Instance number of the Partner controller that will be paired for lead/lag operation. Please refer to Lead/Lag section on page 41 for more details.
Cmp. Run Limit Hrs.
Set Point
16 to 240 hours in increments of 16, then 240 to 960 hours in increments
of 80
Freezer: -40°F to 60°F; Cooler: 25°F to
60°F
112 hours
-10°F for Freezer; 35°F for Cooler
Configure the amount of run time hours that must elapse until cooling functions are switched between the Manager and Partner units to equalize compressor run time between the two. Please refer to Lead/ Lag section on page 41 for more details.
Configure the desired temperature setpoint. This setting is configured at the Manager controller and is automatically synced to the Partner controller.
Comp. Run Time Alert
0 to 480 min
120 min
Configuration for the allowed refrigeration run time until the “A108 Cooler/Freezer not Satisfying Setpnt. Alert” is flagged. If the active unit (Manager or Partner) is on a refrigeration cycle for longer than this period, this alarm will be generated to indicate that the box has not been able to achieve setpoint. Under Lead/Lag operation, this alarm will signal the inactive backup unit (Manager or Partner) to assist to meet refrigeration demand. This setting is configured at the Manager controller and is automatically synced to the Partner controller.
UNIT COOLERS // ECONET ENABLED
PAGE 19
j. BACNET MS/TP OVERVIEW
BACnet
Press “SEL” Press “BACK”
MAC Address
BAUD Rate 38.4 kbps
Slave/Master MS/TP Master
Max Master Addr. 127
Device Instance 4194303
BACNET SETTINGS MENU
BACNET SETTINGS
MAC Address
RANGE
DEFAULT
DESCRIPTION
0 – 127 (Master); 0-254 (Slave)
1
MAC address must be unique among all devices on a given BACnet network segment. MAC address 0 should be avoided.
BAUD rate
9.6 kbps; 19.2 kbps; 38.4 kbps; 57.6 kbps; 76.8
kbps
38.4 kbps
The rate at which data is communicated to the devices. Please make sure that all the devices on the BACnet MS/TP network are set to the same BAUD rate.
Slave/ Master
MS/TP Master; MS/TP Slave
MS/TP Master
EcoNet controller should always remain set to MS/TP Master.
Max Master Addr.
0 – 127
127
The maximum MAC address among the devices on a network segment. Qualified technicians may adjust this value to improve performance.
Device Instance
0000000 4194303
The default value 4194303 indicates unassigned instance, and cannot be 4194303 used in operation. Instance must be assigned for use. Must be unique across
devices on all BACnet network segments of the BACnet internetwork.
BACNET SETTINGS CONFIGURATION AND DEVICE WIRING MUST BE PERFORMED BY A QUALIFIED TECHNICIAN.
FOR MORE INFORMATION, PLEASE VISIT HTTPS://WWW.ASHRAE.ORG/
PAGE 20
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
BACNET SETTINGS CONFIGURATION AND DEVICE WIRING MUST BE PERFORMED BY A QUALIFIED TECHNICIAN.
FOR MORE INFORMATION, PLEASE VISIT HTTPS://WWW.ASHRAE.ORG/
PINOUT
BACnet Communication Terminal
TERMINAL
DESCRIPTION
P
RS-485 Positive (+)
N
RS-485 Negative (-)
Common (for use when
RT
RS-485 port is optically
isolated)
NOTE: Please see Addendum C on page 56 for a complete list of BACnet objects.
UNIT COOLERS // ECONET ENABLED
PAGE 21
REPLACING LEGACY ECONET CONTROLLER WITH NEW ECONET CONTROLLER
If retrofitting new EcoNet controller on existing Unit Cooler, configure the following settings to match the existing system:
1. Under Basic Settings (see pages 12-13) a. Cooler/Freezer b. Refrigerant c. Set Evap Coil Type to “Dual” if using Center Mount/Low Velocity evaporator. d. Set Fan Control to “Relays” e. Set EXV Stepper Type to “2500 Bi-Polar” for Sporlan SER valve
2. Under Defrost Settings (see pages 14-15) a. Set Defrost Type b. Set Defrost Max Time c. Set Runtime for Timed or Adaptive defrost d. Set desired Defrost Termination Temp e. Set desired Fan Delay Temp f. Set Def. Relay 1 Control to “No Pulse Relay 1” g. Set desired Defrost Pump Down Delay h. Set Defrost Drain Time (if Freezer)
3. Under Aux Relay Control (see page 16) a. Set Aux Relay Config to “Fan Control” for Unit Coolers, or “Comp/Fan Control” for Packaged Refrigeration Units b. Set Cut-Out Setpoint, Cut-In Offset for Packaged Refrigeration Units
4. Under Digital Ins Cfg. (see page 17) a. Set Door Sw. Config and Door Sw. Time if using a Door Switch b. Set Leak Sw. Config to “N.O.” if using a leak detector (A2L evaporators only).
5. Under Settings (see General Settings, page 10) a. Setpoint b. Group Member Cfg. c. Network Instance
PAGE 22
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
OPERATIONAL OVERVIEW
REFRIGERATION MODE
When the controller is powered up it will go through an initial startup procedure driving the EXV closed to ensure the valve is properly sealed. After 1 minute, if the space temperature is higher than the Space Temp Setpoint, the controller will start a cooling cycle and open the EXV in an attempt to cool the space.
During normal refrigeration mode, the EXV will continuously modulate to maintain superheat setpoint. The evaporator fans will turn on when Evap Temp drops below the Fan Delay Temp setting. To prevent compressor short cycling, the active refrigeration mode will run for a minimum of 5 minutes (adjustable via Cmp. Min Run Time; see pages 12-13 for Basic Settings).
When the space temperature drops below the Space Temp Setpoint, the EXV will close forcing a pump down, and the fans will cycle to half speed. To prevent compressor short cycling, this inactive mode will run for a minimum of 2 minutes.
When the space temperature rises 2 degrees above the Setpoint (can be adjusted via Setpoint Control parameter, see pages 12-13 for Basic Settings), the EXV will open again and then fans will cycle back to full speed.
UNIT COOLERS // ECONET ENABLED
PAGE 23
DEFROST MODE
TIMED DEFROST (DEFAULT SETTING) With the controller set to Timed defrost, the defrost start time will vary depending on compressor run time. The controller will automatically start defrost when the Def. Comp. Run Time has elapsed (default 360 minutes), or manually when set by the user on the display ServiceDefrost ControlStart Defrosting.
NOTE: When the unit is actively cooling the space (EXV is metering, fans running at full speed) the controller is counting runtime towards the next defrost. When the space temperature setpoint is satisfied (EXV closes for pumpdown, fans running at half speed) the controller does not count this as runtime towards the next defrost.
ADAPTIVE DEFROST (OPTIONAL SETTING) With Adaptive defrost selected, the controller continuously monitors coil operation as indicated by EXV position over time and by temperatures. When both EXV and temperature conditions degrade past a certain point, the controller will automatically start a defrost cycle. Otherwise, a defrost will be started anyway after the Def. Adpt. Run Time (default 720 minutes) has expired. Alternatively, a defrost can be manually started by the user via the display by navigating to ServiceDefrost ControlStart Defrosting.
NOTE: Adaptive defrost is only available when the controller is set to Freezer. If the controller is set to Cooler, Timed defrost will always remain as the functional setting.
When a defrost cycle starts, the EXV will close for pumpdown.
If unit is set as “Freezer”, the electric heaters will be energized via the defrost relays after a short delay (if Defrost Pump Down Delay is configured), and the fans will cycle off. Defrost will end when evaporator coil reaches termination temperature or when Max. Defrost Run Time has elapsed (whichever comes first). The unit will then begin a 5-minute drain time. After the drain time has finished, the unit will resume normal refrigeration operation: EXV opens, and fans turn on when Evap Temp drops below Fan Delay Temp setting.
If unit is set as “Cooler” the fans will remain on after the EXV has closed. Defrost will end when evaporator coil reaches termination temperature or when Max. Defrost Run Time has elapsed (whichever comes first). After the defrost cycle ends, the unit will resume normal refrigeration operation: EXV opens and fans will run when Evap Temp drops below the Fan Delay Temp setting.
NOTE: If there is a power loss while the unit is in the middle of an automatic defrost cycle, the controller will keep the EXV closed. When power is restored, the controller will go through its initial startup before resuming the defrost cycle. When the defrost cycle ends, the controller will resume refrigeration functions.
PAGE 24
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
DEFROST RELAY 1 CONTROL (DRAIN PAN HEATER PULSING ON LOW-PROFILE MODELS ONLY) · Defrost Relay 1 needs to be wired to Drain Pan Heater, while Defrost Relay 2 gets wired to Top and
Bottom heaters. · No Pulse Relay 1: Defrost Relay 1 stays On continuously during the Defrost Cycle. · Drain Pan Defrost: Defrost Relay 1 will turn ON while Defrost Mode is “Defrosting” and Drain Temp is
less than Drain Temp Def. Setpoint. Defrost Relay 1 will turn OFF while Defrost Mode is “Defrosting” and Drain Temp is greater than Drain Temp Def. Setpoint + Drain Temp Def. Offset. · Only applies when controller is configured as Freezer · If Drain Temp sensor is disconnected while controller is configured to Drain Pan Defrost, the controller will flag “A104 Drain Temp Thermistor Failure” and keep Defrost Relay 1 on for the duration of the electric defrost cycle.
RECOMMENDED FREEZER DEFROST PARAMETER SETTINGS · Low Profile Evaporators: Set Defrost Termination Temperature between 55°F and 65°F. · Center Mount Evaporators: Set Defrost Termination Temperature between 35°F and 40°F (adjust as
necessary if defrost cycle is too long and steaming occurs); Coil Type should be set to Dual. · If defrost cycle is too long, keep in mind that the Max Defrost Time can also be adjusted down to
terminate defrost before steaming occurs. Default is 60 minutes. · If more defrost cycles are desired, the Runtime Until Defrost can be adjusted down so the unit will
defrost more often throughout the day. Default is 360 minutes (6 hours of runtime).
UNIT COOLERS // ECONET ENABLED
PAGE 25
DIAGNOSTICS
The following alarms and alerts can be flagged by the controller. When a critical alarm is active, the controller will flash a red LED above the display. When the alarm condition is no longer true, the alarm will clear and the red LED will stop flashing. The alarm will remain logged in the Alarm History. Noncritical alerts also get logged in the Alarm History, but do not cause the red LED to flash when active.
NON-CRITICAL ALERTS: · T001 Defrost Failure: Max Time Expired (If Freezer) · T003 Door Open Alert
CRITICAL ALARMS: · A004 Refrigerant Leak Detect Alarm · A005 Lead/Lag Communication Failure · A100 Suction Temp Thermistor Failure · A101 Evaporator Temp Sensor Failure · A102 Evap Temp 2 Thermistor Failure · A103 Space Temp Thermistor Failure · A104 Drain Temp Thermistor Failure · A105 Aux Temp Thermistor Failure · A106 Suction Pressure Sensor Failure · A108 Cooler/Freezer not Satisfying Setpnt. Alert · A500 Configuration Data Restore Failure · A502 Time Clock needs to be programmed · A503 Time Clock not advancing time properly
PAGE 26
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
GROUP OPERATION
The EcoNet application supports multiple evaporator controllers to be connected together and work under a Leader/Follower setup as shown below. A maximum of 6 evaporators (1 Leader plus 5 Followers) can be configured onto a single group, and a maximum of 4 groups can be connected onto the same communication bus (see Figure 8). When multiple controllers are addressed and connected to work as a group, the Leader of each group will command its followers when to cool the space, when to pump down, and when to start a defrost.
Each group will work from a calculated average space temperature to determine if the space needs cooling. When a group is in active cooling mode, each evaporator in the group will meter its own EXV based on its individual superheat calculation.
The Leader will keep track of the system runtime and command the Followers in its group to start a defrost cycle as necessary. When a defrost cycle ends, the Leader will command the Followers in its group to start cooling the space simultaneously after every member of the group has finished defrosting.
Each controller to be connected on the communication bus should be powered up and addressed individually before being connected to the other controllers in the daisy chain.
To address each individual controller via the display select SettingsGroup Member Cfg. To “daisy chain” the units on the network, each unit should be connected to the EcoNet communication terminals (E1, E2, RT) as shown below. Use minimum 18 to 22 AWG shielded cable with shunt capacitance of 16 pF per foot and 100 ohm impedance.
Leader/Follower Wiring Diagram Figure 8
GROUP MEMBER CFG.
DESCRIPTION
No
Standalone Unit
G1-L
Group 1 Leader
G1-2 G1-3 G1-4 G1-5 G1-6
G2-L
Group 1 Followers
Group 2 Leader
G2-2
G2-3
G2-4
G2-5
G2-6 G3-L
G3-2 G3-3 G3-4 G3-5 G3-6 G4-L
G4-2 G4-3 G4-4 G4-5 G4-6
Group 2 Followers
Group 3 Leader
Group 3 Followers
Group 4 Leader
Group 4 Followers
UNIT COOLERS // ECONET ENABLED
PAGE 27
When setting up a group for the first time, the following parameters only need to be set at the Leader. The Leader will broadcast these settings to any connected followers in its group. 1. Setpoint 2. Refrigerant 3. Cooler/Freezer 4. Runtime Until Defrost, Timed (Def. Cmp. Run Time) 5. Defrost Pump Down Delay 6. Defrost Type 7. Runtime Until Defrost, Adaptive (Def. Adpt. Run Time) 8. System Enabled 9. Cmp Run Time Alert 10. Setpoint Hysteresis 11. Door Switch Config. 12. Door Switch Alert Time 13. Comp. Minimum Run Time
· Ensure that communication wiring polarity is consistent on all controllers being wired together. · A maximum of 32 devices including the Command Center can be daisy chained together on a
single communication bus. If using the Web Portal with a Command Center display connected to WiFi, the maximum number of controllers connected to the Command Center is 8 (Please refer to Web Portal IOM for more details). · Maximum wiring length of communication bus from first device to last device is 1,000 ft. · The controllers can be wired in any order.
PAGE 28
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
DOOR SWITCH
The EcoNet evaporator controller can be paired with a door switch to pump down the system and turn off the fans. Please follow the steps below to wire and configure a door switch. 1. Wiring the Door Switch
Wire door switch or toggle switch to Digital Input #1 (terminals 1A and 1B) using 18-20 AWG wire. Input is a dry contact; no external voltage source needed.
2. Configuring the Door Switch Under Equipment, navigate to Door Sw. Config. Press SEL button, default setting (Off) will start flashing. Default setting is “Off”; can be configured as Normally Open (N.O.), or Normally Closed (N.C.).
UNIT COOLERS // ECONET ENABLED
PAGE 29
NORMALLY OPEN (N.O.) DOOR SWITCH
Active StateClosed Contact: System runs. Digital Input #1 (Door Switch Input) displayed on Status screen as ON.
Inactive StateOpen Contact: System pumps down, fans turn off, T003 Door Open Alert is generated. Digital Input #1 (Door Switch Input) displayed on Status screen as OFF.
NORMALLY CLOSED (N.C.) Active StateOpen Contact: System runs. Digital Input #1 (Door Switch Input) displayed on Status screen as OFF
PAGE 30
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
Inactive StateClosed Contact: System pumps down, fans turn off, T003 Door Open Alert is generated.
Digital Input #1 (Door Switch Input) displayed on Status screen as ON
CONFIGURING DOOR SWITCH DELAY
Under Equipment, navigate to Door Sw.Time. Default 0 second delay: system will pump down and fans turn off immediately when Door Open Alert is generated. Delay can be configured for 30 seconds, 1 minute, 2 minutes, 3 minutes, 4 minutes or 5 minutes. With Door Switch configured as N.O. or N.C., contact has to be in its inactive state continuously for the configured Delay time before Door Open Alert is generated, system pumps down and fans turn off.
DOOR SWITCH SEQUENCE OF OPERATIONS With Door Switch configured, T003 Door Open Alert will cause system to pump down and fans to turn off immediately when Digital Input is in its inactive state (open contact for N.O. or closed contact for N.C.). Once system pumps down and fans turn off, a 2-minute minimum off time is observed where the EXV will remain closed regardless of Door Switch Input status. After Digital Input changes back to its active state and remains there for 5 seconds, the T003 Door Open Alert will clear, and system will be allowed to run again. If input changes back to its active state before the 2-minute minimum, fans will run at 50% speed. After the 2-minute minimum, cooling mode resumes (EXV opens, fans cycle to 100% speed). If Door Open Alert is generated during a defrost cycle (Air or Electric), defrost cycle continues unaffected. There is a mandatory 5-minute minimum cooling period following the defrost cycle, regardless of Door Switch input status. NOTE: The Door Open Alert does not reset the Space Temperature Alarm delay timer (set by Cmp. Run Time Alert under Settings), nor does it clear the “A108 Cooler/ Freezer not Satisfying Setpnt. Alert” once it has been generated. See Cmp. Run Time Alert setting on page 13.
UNIT COOLERS // ECONET ENABLED
PAGE 31
DOOR SWITCH SEQUENCE IN A GROUP
Only the group Leader needs the Door Switch wired and configured.
T003 Door Open Alert is generated at Leader when input is in inactive state for the configured Delay. Follower evaporators will receive pump down command from Leader and their fans will turn off.
Minimum 2 minute off time applies to entire Group. If Digital Input at Leader changes back to its active state before the 2 minutes are up, Leader and Followers will turn their fans to 50% after the Door Open Alert is cleared. After the 2 minutes have elapsed, Group resumes cooling as soon as the Door Open Alert has cleared.
If Door Open Alert is generated during a defrost cycle (Air or Electric), defrost cycle continues unaffected for the entire Group. There is a mandatory 5 minute minimum cooling period following the defrost cycle, regardless of Door Switch input status. Door Open Alert does not clear “A108 Cooler/Freezer not Satisfying Setpnt. Alert” or reset its timer count.
PAGE 32
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
COMPRESSOR CONTROL
PACKAGED REFRIGERATION UNITS
The EcoNet Evaporator Controller can be set to cycle the compressor ON or OFF via Aux Relay 2 by configuring the Aux Relay Config. setting to Comp-Fan Control. The controller will use the Suction Pressure transducer reading to determine if the compressor needs to run. This setting is required for Packaged Refrigeration Units.
CONFIGURATION Aux Relay Config. Cut-Out Setpoint
Cut-In Offset
ADJUSTMENT RANGE Comp-Fan Control;Fan Control
-2 PSIG to 60 PSIG 10 PSIG to 50 PSIG
DEFAULT SETTING
“Comp-Fan Control” “0 PSIG” for Freezer units;”20 PSIG” for
Cooler units “20 PSIG”
1. Aux Relay Config.
a. Fan Control: Controller will use Auxiliary Relays 1 and 2 for Evaporator Fan ON/OFF control and fan speed control. This setting is applicable for all other evaporator unit models. Not applicable for Packaged Refrigeration Units!
b. Comp-Fan Control: Controller will use Auxiliary Relay 1 for Evaporator Fan ON/OFF control and Auxiliary Relay 2 for Compressor ON/OFF control based on Suction Pressure transducer reading.
NOTE: This setting only applies to Packaged Refrigeration Units. Packaged Refrigeration Units MUST be set to Comp Fan Control or damage to equipment could result!
UNIT COOLERS // ECONET ENABLED
PAGE 33
2. Cut-Out Setpoint: Pressure setpoint at which the compressor will turn off when Aux Relay Config. is set to Comp-Fan Control.
3. Cut-In Offset: Pressure differential for compressor to turn on when Aux Relay Config. is set to Comp-Fan Control.
COMPRESSOR OPERATION When a cooling cycle starts, the controller will open the Electronic Expansion Valve (EEV) which will cause the Suction Pressure to increase.
The compressor will turn ON when: Suction Pressure (PSIG) is greater than Cut-Out Setpoint + Cut-In Offset. The controller will keep the compressor on for a minimum amount of time while the EEV is open, even if the Suction Pressure briefly gets below the Cut-Out Setpoint to prevent compressor from short cycling.
Example 1 (Low Temperature Unit): Cut-Out Setpoint = 0 PSIG | Cut-In Offset= 20 PSIG Compressor will turn ON when Suction Pressure is greater than 20 PSIG. Compressor will turn OFF when Suction Pressure is less than 0 PSIG.
Example 2 (Medium Temperature Unit): Cut-Out Setpoint = 20 PSIG | Cut-In Offset= 20 PSIG Compressor will turn ON when Suction Pressure is greater than 40 PSIG. Compressor will turn OFF when Suction Pressure is less than 20 PSIG.
When a cooling cycle ends (setpoint is satisfied, defrost starts, etc.) the controller will close the EEV and the compressor will turn OFF.
PAGE 34
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
DEFROST PUMP DOWN DELAY
Configurable delay to allow compressor to pump down before electric heaters are activated at the start of a defrost cycle.
Default setting is “1-minute”; Available delay configuration of None, 1 minute, 2 minutes, 3 minutes, 4 minutes, 5 minutes.
Only applicable when controller is configured as “Freezer”; delay will have no effect if controller is configured as “Cooler.”
CONFIGURING DEFROST PUMP DOWN DELAY
Under Defrost settings, scroll down to Def. Pmp. Dn. Delay.
Press SEL button, default setting (1-minute) will start flashing. Use UP or DOWN buttons to adjust to desired delay. Press SEL button again to confirm change.
UNIT COOLERS // ECONET ENABLED
PAGE 35
When defrost cycle starts, display will show “Initialize” for the duration of the delay. Fans cycle to 50% speed after EXV has closed.
When “Defrosting” appears on display, the heater relays are active, and fans turn off. After defrost terminates (Due to time or temperature), drain time will follow as normal.
PAGE 36
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
LEAK DETECTION
The EcoNet evaporator controller can be paired with a leak detection device to assist with mitigation procedures in case of a refrigerant leak.
NOTE: THIS FEATURE IS INTENDED FOR USE WITH A2L REFRIGERANTS (R454A,R454C, R455A,R454B,R32). REQUIRES INSTALLATION OF A LIQUID LINE SOLENOID VALVE UPSTREAM, AND A SUCTION LINE CHECK VALVE DOWNSTREAM OF THE EVAPORATOR TO INTERRUPT REFRIGERANT FLOW WHEN A LEAK IS DETECTED.
WIRING THE LEAK DETECTOR DEVICE TO THE ECONET CONTROLLER
Wire the leak detector device to Digital Input #2 (terminals 2A and 2B) using 18-20 AWG wire.
Input is a dry contact; no external voltage source needed.
CONFIGURING THE LEAK DETECTOR INPUT Under Equipment, navigate to Leak Sw. Config. Press SEL button, setting will start flashing. Use UP or DOWN buttons to adjust to desired leak detector input operation. Press SEL button again to confirm change. It can be configured as Normally Open (N.O.), Normally Closed (N.C.), or Off to disable leak detector input.
Note: A2L evaporator models will come with a leak detector installed and this setting configured from the factory.
UNIT COOLERS // ECONET ENABLED
PAGE 37
NORMALLY OPEN (N.O.) LEAK DETECTOR RELAY Active StateClosed Contact: Leak Alarm Active. “A004 Refrigerant Leak Detect Alarm” generated. Digital Input #2 displayed on Status screen as ON.
Inactive State Open Contact: System runs. Digital Input #2 displayed on Status screen as OFF.
PAGE 38
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
NORMALLY CLOSED (N.C.) LEAK DETECTOR RELAY Active StateOpen Contact: Leak Alarm Active. “A004 Refrigerant Leak Detect Alarm” generated. Digital Input #2 displayed on Status screen as OFF.
Inactive State Closed Contact: System runs. Digital Input #2 displayed on Status screen as ON.
When the leak detection input (Digital Input #2) becomes active, the EcoNet controller shall do the following:
1. Keep evaporator fans turned on. 2. Electronic Expansion Valve will stay at an open position. (Installation of solenoid and check valves required on liquid and suction lines) 3. Controller display will read “Leak Alarm Active.” 4. “A004 Refrigerant Leak Detect Alarm” will appear on the active alarm screen and logged in the alarm history. 5. If Aux Relay Config. is set to Comp-Fan Control (Packaged Refrigeration Units), the Aux Relay #2 for the compressor will remain OFF.
The leak alarm condition will stay on for as long as Digital Input #2 is in its active state. If the leak detection input becomes active while the controller is undergoing a defrost cycle, the defrost cycle will be suspended.
UNIT COOLERS // ECONET ENABLED
PAGE 39
NOTE: The leak alarm condition will also override the Door Switch and System Enable functions.
When Digital Input #2 becomes inactive, the controller will wait 10 seconds before resuming normal operation.
On group operation, each group member will generate a leak alarm only when their own individual leak detector input (Digital Input #2) becomes active.
When a group member generates a leak alarm, that group member will follow the steps described above. Other group members will also display “Leak Alarm Active” on their display screens but may continue their refrigeration functions if their respective leak detector inputs are not active.
PAGE 40
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
LEAD/LAG
Lead/Lag will allow the linking of two redundant systems for backup cooling and ability to equalize compressor runtime between the two systems. This will be accomplished by designating one of the two evaporators to be the Manager, and the other evaporator to be the Partner. The controller designated to be the Manager will constantly communicate via the EcoNet communication port to the Partner controller. The Manager controller will monitor its own status as well as the Partner status and coordinate cooling operations between the two systems.
LEAD/LAG MANAGER SETUP To configure two controllers to work under Lead/Lag operation:
1. At the designated Partner controller, set the Instance number address. See Network Instance setting on Page 10.
2. Connect 18-22 AWG shielded wire between the two controllers at the EcoNet communication port.
3. At the designated Manager controller: a. Set the Instance number address. See Network Instance setting on Page 10 (must be different number from Partner). b. Set Lead/Lag Select to “Manager” c. Select Partner Instance number (same number configured on step #1; this is the address that the Manager will communicate with).
d. Set the Compressor Run Limit Hours to the desired switching time interval.
UNIT COOLERS // ECONET ENABLED
PAGE 41
e. Set the desired temperature Setpoint (Manager will sync Partner to the same Setpoint)
f. Set the desired Compressor Run Time Alert (Manager will sync Partner to the same run time alert setting)
NOTE: Manager will also sync Partner to the same Cooler/Freezer setting. LEAD/LAG SEQUENCE OF OPERATIONS Once both controllers are set up and communicating, the Manager controller will keep track of compressor runtime and coordinate operational turns between the Manager and Partner controllers. After the initial setup and synchronization the Manager controller will start first, and the Partner controller will remain disabled (EXV closed, fans off). When the Manager controller reaches its configured Compressor Run Limit Hours it will disable (EXV closed, fans off), and the Partner controller will continue cooling operation. The Manager will receive periodic updates on the Partner run time hours, and when the Compressor Run Limit Hours are reached the Partner will be disabled and the Manager will resume cooling operations. When the active controller (Manager or Partner) starts a defrost cycle, the inactive controller will remain disabled. When the next cooling cycle starts, the controller that underwent the defrost cycle will resume cooling operation until the Compressor Run Limit Hours are reached.
PAGE 42
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
If the active system (Manager or Partner) is unable to reach setpoint within the configured Compressor Run Time Alert setting:
1. The active controller will flag the “A108 Cooler/Freezer Not Satisfying Setpoint Alert” 2. The inactive system will be enabled to assist cooling operation 3. Both Manager and Parter will remain active until each satisfies its own Setpoint 4. When the next cooling cycle starts, the controller that did not flag the alarm on the previous
cycle will take first turn and continue cooling operation until the Compressor Run Limit Hours are reached. The controller that flagged the alarm on the previous cycle will remain disabled.
If at any time the communication between Manager and Partner is interrupted, each controller will individually resume cooling operations as needed, and each controller will flag “A005 Lead/Lag Communication Failure” alarm.
NOTE: To use the door switch function with two redundant systems linked for lead-lag operation, each system will need its own door switch with a single pole-single throw (SPST) contact, or one door switch with a double pole-single throw (DPST) contact. The Digital Input #1 on BOTH controllers must be inactive simultaneously for both systems to remain off with “Door Open Alert”. Otherwise, when one system is off due to “Door Open Alert”, the lead-lag operation will cause the other system to run. See Door Switch Operation on page 29 for more details.
LEAD LAG WIRING DIAGRAM
UNIT COOLERS // ECONET ENABLED
PAGE 43
LEAD LAG INSTALLATION
Lead Lag: 100% load requirement each compressor
PAGE 44
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
LEAD/LAG IN GROUPS Lead-Lag coordination between two different groups is handled between each of the group leaders. One Group Leader will be the Manager, and another Group Leader will be the Partner. Each Group Leader will handle its respective Group Followers as described in the Group Operation section on page 27.
To set up Lead Lag between two different groups:
1. Set up “Group Member Cfg.” address for each group (i.e. Group 1 Leader and all its Followers, and Group 2 Leader and all its Followers). See Group Operation section on page 27 for details on how to set up a Group.
2. Connect communication wire in a daisy chain pattern between all controllers from both groups. They can be wired in any order.
3. On the Group Leader controller that will be the Manager: a. Configure Lead Lag Select to “Manager” b. Configure Partner Instance to G1, G2, G3 or G4 (the group whose leader is going to be the Partner; must be different than the Manager Group) c. Configure Compressor Run Limit Hours d. Set the desired Setpoint (Manager Group Leader will sync this setting to the Partner Group Leader) e. Set the desired Compressor Run Time Alert (Manager Group Leader will sync this setting to the Partner Group Leader).
LEAD LAG GROUP WIRING DIAGRAM
UNIT COOLERS // ECONET ENABLED
PAGE 45
LEAD LAG GROUP INSTALLATION
EXAMPLE 1
Group operation: 50% load requirement each compressor
EXAMPLE 2
Lead Lag: 100% load requirement each compressor
PAGE 46
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
LEAD/LAG OPERATION SUMMARY *Status viewed from Manager controller display
SYSTEM STATUS MANAGER MGR STATUS* PARTNER PTNR STATUS*
Manager Running
Active
Partner Running
Disabled
Manager Setpoint Alarm
Manager on Setpoint Alarm
and starts defrosting
Manager on Setpoint Alarm and Partner starts
defrosting
Active Defrosting Disabled
Partner Setpoint Alarm
Partner on Setpoint Alarm
and starts defrosting
Partner on Setpoint Alarm and Manager starts defrosting
Manager & Partner Setpoint
Alarm
Manager Space Temp Fail Alarm
Partner Space Temp Fail Alarm
Active Disabled Defrosting
Active Disabled
Active
Okay Okay Satisfy No
Disabled Active Active
Okay
Disabled
Okay Okay Okay
Okay
Okay
Defrosting
Okay
Okay
Active
Satisfy No
Okay
Defrosting
Okay
Okay
Disabled
Okay
Satisfy No
Active
Satisfy No
Space Fail Okay
Active Disabled
Okay Space Fail
LEAD LAG CONTROL
Manager Partner
Both Neither
Neither
Both Neither
Neither
Both Partner Manager
UNIT COOLERS // ECONET ENABLED
PAGE 47
*Status viewed from Manager controller display
SYSTEM STATUS MANAGER MGR STATUS* PARTNER PTNR STATUS*
Communication lost between Manager and Partner
Manager running and set to System
Enable = No
Active Disabled
Okay Can’t Run
Active Active
Okay Okay
Partner running and set to System
Enable = No
Active
**Manager running gets Door Open Alert
**Partner running gets Door Open
Alert
Disabled Active
Manager running gets Leak Alarm
Disabled
Manager running and Partner gets
Leak Alarm
Active
Partner running gets Leak Alarm
Active
Partner running and Manager gets
Leak Alarm
Disabled
Okay
Disabled
Can’t Run
Active
Okay
Disabled
Can’t Run
Active
Okay
Disabled
Okay
Disabled
Can’t Run
Active
Can’t Run Okay
Can’t Run Okay
Can’t Run Can’t Run
Okay
LEAD LAG CONTROL
Off Partner
Manager Partner Manager Partner Manager Manager Partner
**NOTE: To use the door switch function with two redundant systems linked for leadlag operation, each system will need its own door switch with a single pole-single throw (SPST) contact, or one door switch with a double pole-single throw (DPST) contact. The Digital Input #1 on BOTH controllers must be inactive simultaneously for both systems to remain off with “Door Open Alert”. Otherwise, when one system is off due to “Door Open Alert”, the lead-lag operation will cause the other system to run.
PAGE 48
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
OPERATIONAL LIMITS
1. Voltage: 115V/230V, 50/60 Hz. 2. Operating Temp range: -40°F to 140°F 3. Operating Humidity range: 0% to 97% RH condensing 4. Defrost Relay #1: 24A at 240VAC 5. Defrost Relay #2: 24A at 240VAC 6. Aux Relay #1: 3A at 120VAC 7. Aux Relay #2: 3A at 120VAC
REPLACEMENT PARTS | NUMBERS 1. EcoNet Control Board (08536930) 2. Space/Drain Temp (08219623) 3. Evap Temp (08219636) 4. Suction Temp (08219637) 5. Suction Pressure 0-150 PSIA (08219621) 6. Suction Pressure 0-700 PSIA for CO2 only (08540186) 7. Wire Harness
a. 63″ Controller wire harness, Sporlan SER valve only (0821963501) b. 96″ Controller wire harness, Sporlan SER valve only (0821963502) c. 126″ Controller wire harness, Sporlan SER valve only (0821963503) d. 63″ Controller wire harness, multi valve (0853669601) e. 96″ Controller wire harness, multi valve (0853669602) f. 126″ Controller wire harness, multi valve (0853669603) 8. 10′ Harness Extension a. 120″ harness extension, SER valve only (08532293) b. 120″ harness extension, multi valve (08537410) 9. Sporlan SER Bi-Polar valve adapter (08536760) 10. Sporlan OEV Uni-Polar valve adapter (08537865) 11. Sporlan rubber O-ring for use with OEV Uni-Polar valve (08539677) 12. Carel E2V/E3V/E4V Bi-Polar valve adapter (08536993) 13. Sanhua LPF Uni-Polar valve adapter (08536992) 14. Controller Power Harness (08219638)
For help with replacement parts, e-mail or call our Parts Department at: parts@htpg.com or 1-855-HTPARTS (1-855-487-2787).
UNIT COOLERS // ECONET ENABLED
PAGE 49
ADDENDUM A
Evap Temp Thermistor Resistance Table
FAHRENHEIT KILO-OHMS FAHRENHEIT KILO-OHMS
-40
346.62
-4
99.20
-39
335.84
-3
-38
325.06
-2
-37
314.28
-1
-36
303.50
0
-35
292.71
1
-34
281.93
2
96.44
93.68 90.92 88.16 85.41 82.65
-33
271.15
3
79.89
-32
260.37
4
77.13
-31
249.59
5
-30
242.04
6
-29
234.49
7
-28
226.95
8
-27
219.40
9
-26
211.85
10
-25
204.30
11
-24
196.76
12
-23
189.21
13
-22
181.66
14
-21
176.32
15
74.37 72.36 70.35 68.33 66.32 64.31 62.30 60.29 58.27 56.26 54.78
-20
170.98
16
53.30
-19
165.63
17
51.82
-18
160.29
18
-17
154.95
19
50.34 48.86
-16
149.61
20
47.38
-15
144.26
21
45.90
-14
138.92
22
44.42
-13
133.58
23
42.94
-12
129.76
24
41.84
-11
125.94
25
40.74
-10
122.12
26
39.64
-9
118.30
27
38.54
-8
114.48
28
37.44
-7
110.66
29
36.34
-6
106.84
30
35.24
-5
103.02
31
34.14
Part no. 08219636
FAHRENHEIT KILO-OHMS FAHRENHEIT KILO-OHMS
32
33.04
69
12.24
33
32.22
70
11.96
34
31.39
71
11.68
35
30.57
72
11.40
36
29.75
73
11.12
37
28.92
74
10.84
38
28.10
75
10.56
39
27.28
76
10.28
40
26.46
77
10.00
41
25.63
42
25.01
78
9.78
43
24.39
79
9.56
44
23.77
80
9.35
45
23.15
81
9.13
46
22.52
82
8.91
47
21.90
83
8.69
48
21.28
84
8.48
49
20.66
85
8.26
50
20.04
86
8.04
51
19.57
87
7.87
52
16.29
88
7.70
53
16.22
89
7.53
54
16.14
90
7.36
55
16.07
91
7.19
56
16.00
92
7.02
57
15.93
93
6.85
58
15.86
94
6.68
59
15.78
95
6.51
60
15.42
96
6.37
61
15.06
97
6.24
62
14.70
98
6.10
63
14.33
99
5.97
64
13.97
100
5.83
65
13.61
101
5.70
66
13.25
102
5.57
67
12.88
103
5.43
68
12.52
104
5.30
PAGE 50
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
Space/Drain Temp Thermistor Resistance Table
FAHRENHEIT KILO-OHMS FAHRENHEIT KILO-OHMS
-40
169.16
-4
48.61
-39
163.89
-3
-38
158.63
-2
-37
153.37
-1
-36
148.11
0
-35
142.84
1
-34
137.58
2
47.27
45.92 44.58 43.23 41.89 40.54
-33
132.32
3
39.19
-32
127.06
4
37.85
-31
121.80
5
-30
118.13
6
-29
114.46
7
-28
110.79
8
-27
107.12
9
-26
103.45
10
-25
99.78
11
-24
96.11
12
-23
92.44
13
-22
88.77
14
-21
86.16
15
36.50 35.52 34.54 33.56 32.58 31.60 30.62 29.64 28.66 27.68 26.96
-20
83.56
16
26.23
-19
80.96
17
-18
78.35
18
-17
75.75
19
-16
73.15
20
-15
70.54
21
-14
67.94
22
-13
65.34
23
-12
63.48
24
-11
61.62
25
-10
59.76
26
-9
57.90
27
-8
56.05
28
-7
54.19
29
-6
52.33
30
-5
50.47
31
25.51 24.79 24.06 23.34 22.61 21.89 21.17
20.63
20.09 19.55 19.02 18.48 17.94 17.40 16.87
Part no. 08219623
FAHRENHEIT KILO-OHMS FAHRENHEIT KILO-OHMS
32
16.33
69
6.11
33
15.93
70
5.97
34 35
15.52 15.12
71
5.83
36
14.71
72
5.69
37
14.31
73
5.55
38
13.91
74
5.42
39
13.50
75
5.28
40
13.10
76
5.14
41
12.70
77
5.00
42
12.39
78
4.89
43
12.09
79
4.78
44
11.78
80
4.68
45
11.48
81
4.57
46
11.17
82
4.46
47
10.87
83
4.35
48
10.56
84
4.24
49
10.26
85
4.14
50
9.95
86
4.03
51
9.72
87
3.94
52
8.10
88
3.86
53
8.07
89
3.77
54
8.03
90
3.69
55
8.00
91
3.61
56
7.96
92
3.52
57
7.93
93
3.44
58
7.89
94
3.35
59
7.85
95
3.27
60
7.68
96
3.20
61
7.50
97
3.13
62
7.32
98
3.07
63
7.14
99
3.00
64
6.96
100
2.93
65
6.78
101
2.87
66 67
6.60 6.42
102 103
2.80 2.73
68
6.25
104
2.66
UNIT COOLERS // ECONET ENABLED
PAGE 51
Suction Temp Thermistor Resistance Table
FAHRENHEIT KILO-OHMS
-40
336.50
-39
326.07
-38
315.63
-37
305.20
-36
294.77
-35
284.33
-34
273.90
-33
263.47
-32
253.03
-31
242.60
-30
235.31
-29
228.02
-28
220.73
-27
213.44
-26
206.16
-25
198.87
-24
191.58
-23
184.29
-22
177.00
-21
171.82
FAHRENHEIT KILO-OHMS
-4
97.07
-3
94.39
-2
91.71
-1
89.02
0
86.34
1
83.66
2
80.98
3
78.29
4
75.61
5
72.93
6
70.97
7
69.02
8
67.06
9
65.11
10
63.15
11
61.20
12
59.24
13
57.29
14
55.33
15
53.88
16
52.44
-20
166.64
17
-19
161.47
18
-18
156.29
19
-17
151.11
20
-16
145.93
21
-15
140.76
22
-14
135.58
23
-13
130.40
24
-12
126.70
25
-11
122.99
26
-10
119.29
27
-9
115.59
28
-8
111.88
29
-7
108.18
30
-6
104.48
31
-5
100.77
32
50.99
49.55 48.10 46.66 45.21 43.77 42.32 41.25
40.17
39.10 38.02 36.95 35.87 34.80 33.72 32.65
Part no. 08219637
FAHRENHEIT KILO-OHMS FAHRENHEIT KILO-OHMS
33
31.84
69
12.21
34
31.04
70
11.94
35
30.23
71
11.66
36
29.42
72
11.38
37
28.62
73
11.11
38
27.81
74
10.83
39
27.00
75
10.55
40
26.20
76
10.28
41
25.39
77
10.00
42
24.78
78
9.78
43
24.17
79
9.57
44
23.56
80
9.35
45
22.95
81
9.14
46
22.34
82
8.92
47
21.73
83
8.70
48
21.12
84
8.49
49
20.51
85
8.27
50
19.90
86
8.06
51
19.43
87
7.89
52
16.21
88
7.72
53
16.14
89
7.55
54
16.07
90
7.38
55
15.99
91
7.21
56
15.92
92
7.04
57
15.85
93
6.87
58
15.78
94
6.70
59
15.71
95
6.53
60
15.35
96
6.40
61
14.99
97
6.26
62
14.64
98
6.13
63
14.28
99
6.00
64
13.92
100
5.86
65
13.56
101
5.73
66
13.21
102
5.59
67
12.85
103
5.46
68
12.49
104
5.33
PAGE 52
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
Pressure Transducer Voltage Table
Vout (DC)
PSIA
PSIG
0.50
0
-14.7
0.55
2
-12.7
0.61
4
-10.7
0.66
6
-8.7
0.71
8
-6.7
0.77
10
-4.7
0.82
12
-2.7
0.87
14
-0.7
0.93
16
1.3
0.98
18
3.3
1.03
20
5.3
1.09
22
7.3
1.14
24
9.3
1.19
26
11.3
1.25
28
13.3
1.30
30
15.3
1.35
32
17.3
1.41
34
19.3
1.46
36
21.3
1.51
38
23.3
1.57
40
25.3
1.62
42
27.3
1.67
44
29.3
1.73
46
31.3
1.78
48
33.3
1.83
50
35.3
1.89
52
37.3
1.94
54
39.3
1.99
56
41.3
2.05
58
43.3
2.10
60
45.3
2.15
62
47.3
2.21
64
49.3
2.26
66
51.3
2.31
68
53.3
2.37
70
55.3
2.42
72
57.3
2.47
74
59.3
UNIT COOLERS // ECONET ENABLED
Part no. 08219621
Vout (DC)
PSIA
PSIG
2.53
76
61.3
2.58
78
63.3
2.63
80
65.3
2.69
82
67.3
2.74
84
69.3
2.79
86
71.3
2.85
88
73.3
2.90
90
75.3
2.95
92
77.3
3.01
94
79.3
3.06
96
81.3
3.11
98
83.3
3.17
100
85.3
3.22
102
87.3
3.27
104
89.3
3.33
106
91.3
3.38
108
93.3
3.43
110
95.3
3.49
112
97.3
3.54
114
99.3
3.59
116
101.3
3.65
118
3.70
120
3.75
122
3.81
124
3.86
126
3.91
128
3.97
130
4.02
132
4.07
134
4.13
136
4.18
138
4.23
140
4.29
142
4.34
144
4.39
146
4.45
148
4.50
150
103.3 105.3 107.3 109.3 111.3 113.3 115.3
117.3
119.3 121.3 123.3 125.3 127.3 129.3 131.3 133.3 135.3
PAGE 53
ADDENDUM B
CONTROLLER WIRE PINOUT FOR ELECTRONIC EXPANSION VALVES
SPORLAN SER (2500 Bi-Polar)
WIRE PIN
ECONET OLD HARNESS
082196350X
1
BROWN
2
WHITE
3
BLUE
4
BLACK
5
N/A
NEW HARNESS
085366960X
ORANGE YELLOW
RED BLACK GRAY
SPORLAN CABLE (P/N 805194)
GREEN WHITE
RED BLACK
N/A
SPORLAN OEV or SANHUA LPF (500 Uni-Polar)
ECONET
WIRE PIN
NEW HARNESS 085366960X
SPORLAN CABLE (P/N 953447)
1
ORANGE
ORANGE
2
YELLOW
3
RED
4
BLACK
5
GRAY
YELLOW
RED BLACK GRAY
SANHUA CABLE (PQM24012)
ORANGE YELLOW
RED BLACK GRAY
*Legacy EcoNet harness (082196350X) does not have wire for Pin 5, so it cannot be used with Uni-Polar valve.
PAGE 54
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
CAREL E2V/E3V/E4V (480 Bi-Polar)
WIRE PIN
ECONET OLD HARNESS
082196350X
NEW HARNESS 085366960X
1
BROWN
ORANGE
2
WHITE
YELLOW
3
BLUE
4
BLACK
5
N/A
RED BLACK GRAY
CAREL CABLE (E2VCAB0300)
4 – WHITE 3 – BROWN 2 – YELLOW 1 – GREEN
N/A
SANHUA VPF (2600 Bi-Polar)
WIRE PIN
ECONET OLD HARNESS 082196350X
1
BROWN
2
WHITE
3
BLUE
4
BLACK
5
N/A
NEW HARNESS 085366960X
ORANGE YELLOW
RED BLACK GRAY
SANHUA CABLE (P/N 66078)
RED WHITE GREEN BLACK
N/A
UNIT COOLERS // ECONET ENABLED
PAGE 55
ADDENDUM C
BACnet Objects List
NO.
DESCRIPTION
BN OBJECT NAME
BN TYPE
1
—
Rheem HTPG DEVICE
2
Setpoint
SETPOINT
ANALOG
3
Defrost Mode
DEFRMODE MULTISTATE
4
Defrost Mode Group
DEFRMODG BINARY
5
Space Temp
SPACETMP
ANALOG
6
Average Space Temp (Group)
SPACEALL
ANALOG
7
Evap Temp 1
EVAPTEMP
ANALOG
8
Evap Temp 2
EVTEMP2T
ANALOG
9
Suction Temp
SUCTIONT
ANALOG
10
Saturated Suction Temp SAT_SUCT
ANALOG
11
Suction Pressure (gauge) PRESGSUC
ANALOG
12
Drain Temp
13
Aux Temp
14
Fan Speed
15
Compressor Request
DRAINTMP AUX_TEMP PWM_FANC COMP_REQ
ANALOG ANALOG ANALOG BINARY
16
Lifetime Compressor Cycles COMPCYCL ANALOG
17
Group Member Cfg.
18
Instance
19
Cooler/Freezer
20
Refrigerant
EVPGROUP INSTANCE COOLTYPE REFRIGER
MULTISTATE ANALOG MULTISTATE MULTISTATE
21
Coil Type
COILTYPE
MULTISTATE
22
Drain Temp Sensor Y/N? DRAINCFG
BINARY
23
Drain Pan Heater Cut-In Offset
DRAINSET
ANALOG
24
Drain Pan Heater Cut-Out Setpoint
DRAINHYS
ANALOG
25
EXV Stepper Type
EXVSTEPR
MULTISTATE
26
EXV Superheat Setpoint EXV_SHSP
ANALOG
27
Setpoint Control/Hysteresis SETPHYST
ANALOG
28
Defrost Type
DEFRTYPE
MULTISTATE
29
Max Defrost Time
DEFRMAXT
ANALOG
EcoNet Software Version: HT-PG02-00-01-00
BN ACCESS
EN LIMITS
BN UNITS
RW
-40, 60, -10 DEGREES_FAHRENHEIT
RO
0, 4
—
RO
0, 1
—
RO
-60, 250
DEGREES_FAHRENHEIT
RO
-60, 250
DEGREES_FAHRENHEIT
RO
-60, 250
DEGREES_FAHRENHEIT
RO
-60, 250
DEGREES_FAHRENHEIT
RO
-60, 250
DEGREES_FAHRENHEIT
RO
-60, 250
DEGREES_FAHRENHEIT
RO
0, 400
POUNDS_FORCE_PER_ SQUARE_INCH
RO
-60, 250
DEGREES_FAHRENHEIT
RO
-60, 250
DEGREES_FAHRENHEIT
RO
0, 100
PERCENT
RO
0, 1
—
0,
RO
4294967295, NO_UNITS
0
RO
0, 24, 0
—
RO
1, 32, 1
RW
0, 1, 1
NO_UNITS —
RW
0, 11, 3
—
RW
0, 1, 0
—
RO
0, 1,
—
RW
20, 80, 40 DEGREES_FAHRENHEIT
RW
1, 20, 5
DEGREES_FAHRENHEIT
RW
0, 3, 0
—
RW
4, 20, 6.5
DELTA_DEGREES_ FAHRENHEIT
RW
0.5, 20, 2
DELTA_DEGREES_ FAHRENHEIT
RW
0, 1, 0
—
RW
10, 60, 60
MINUTES
PAGE 56
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
ADDENDUM C
BACnet Objects List Continued
NO.
DESCRIPTION
BN OBJECT NAME
BN TYPE(_VALUE – BN EXPECT DEVICE ACCESS
EN LIMITS
BN UNITS (BACNET_UNITS_)
30
Runtime Until Defrost (Timed)
DEFRCNTM
ANALOG
31
Runtime Until Defrost (Adaptive)
DEFRCATM
ANALOG
32
Defrost Termination Temp DEFRTTMP
ANALOG
33
Defrost Relay 1 Control
DEFPOVER
MULTISTATE
34
Minimum Cooling Run Time CRQMINON MULTISTATE
RW
0, 900, 360 MINUTES
RW
360, 900, 720 MINUTES
RW
35, 65, 55
DEGREES_FAHRENHEIT
RW
0, 1, 0
—
RW
0, 2, 2
—
35
Comp. Run Time Alert
CREQTIME
ANALOG
RW
0, 480, 120
MINUTES
36
Door Switch Config.
DOORCNFG MULTISTATE
37
Door Switch Time Delay DOORATIM
MULTISTATE
38
Defrost Pump Down Delay DFEXVTIM
MULTISTATE
39
Fan Control
FAN_CTRL
MULTISTATE
RW
0, 2, 0
—
RW
0, 6, 0
—
RW
0, 5, 0
—
RO
0, 1, 0
—
40
Aux Relay Config.
AUX_CNFG
MULTISTATE
41
Cut-Out Setpoint (Pack. Unit Comp. Ctrl.)
CUTOSETP
ANALOG
42
Cut-In Offset (Pack. Unit Comp. Ctrl.)
CUTIOFFS
ANALOG
43
Last Defrost Duration
DEFRTIMM
ANALOG
44
Runtime Until Next Defrost DEFRNEXT
ANALOG
RO
0, 3, 0
—
RW
-5, 60, 0
POUNDS_FORCE_PER_ SQUARE_INCH
RW
10, 50, 20
POUNDS_FORCE_PER_ SQUARE_INCH
RO
0, 4294967295 MINUTES
RO
0, 4000000000
MINUTES
45
Lifetime Defrost Cycles
DEFRCYCL
ANALOG
RO
0, 65535, 0 NO_UNITS
46
Force a Defrost?
47
Digital Input #1
48
Digital Input #2
49
Digital Input #3
50
Defrost Relay 1
51
Defrost Relay 2
52
Aux Relay 1
DEFFORCE DIGITAL1 DIGITAL2 DIGITAL3 DEF1RELY DEF2RELY
AUX1RELY
BINARY BINARY BINARY BINARY BINARY BINARY
BINARY
RW
0, 1
—
RO
0, 1
—
RO
0, 1
—
RO
0, 1
—
RO
0, 1
—
RO
0, 1
—
RO
0, 1
—
53
Aux Relay 2
AUX2RELY
BINARY
54
EXV Current Position %
EXACTUAL
ANALOG
55
Calculated Superheat
EXVSUPER
ANALOG
56
Control Superheat Setpoint EXVCSHSP
ANALOG
RO
0, 1
—
RO
0, 100
PERCENT
RO
-999, 999
DELTA_DEGREES_ FAHRENHEIT
RO
0, 25
DELTA_DEGREES_ FAHRENHEIT
UNIT COOLERS // ECONET ENABLED
PAGE 57
ADDENDUM C
BACnet Objects List Continued
NO.
DESCRIPTION
BN OBJECT NAME
BN TYPE(_VALUE EXPECT DEVICE
BN ACCESS
EN LIMITS
BN UNITS (BACNET_UNITS_)
57 Alarm #1
ALARM_01 CHARACTERSTRING RO
58 Alarm #2
59 Alarm History #1 60 Alarm History #2
61
Alarm History #3
ALARM_02 ALARMH01 ALARMH02 ALARMH03
CHARACTERSTRING RO CHARACTERSTRING RO CHARACTERSTRING RO CHARACTERSTRING RO
62
Alarm History #4
ALARMH04 CHARACTERSTRING RO
63 Product Model Number PRODMODN CHARACTERSTRING RO
64 Product Serial Number PRODSERN CHARACTERSTRING RO
65 Product Location
PRODLOCA CHARACTERSTRING RW
66 EcoNet Software Version SW_VERSN CHARACTERSTRING RO
67
Product Description
PRODDESC CHARACTERSTRING RO
68 Leak Detector Config. LEAKCNFG MULTISTATE
RW
69
Leak Alarm Recovery Timer Config.
LRECTIMC
ANALOG
RW
70 Leak Alarm
LEAKALRM BINARY
RO
71
Comp. Minimum ON Timer (Pack. Unit)
AUX2CTMR ANALOG
RW
72
System Enable Y/N
HTPGENAB BINARY
RW
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0, 2, 0
—
5, 600, 300 SECONDS
0, 1
—
10, 120, 60 SECONDS
0, 1, 1
—
73
Superheat Setpoint Offset
EXVOSHSP ANALOG
74
Alarm History Clear? ALHISCLR
BINARY
75 Unit is in Follower Mode? FOLLOWER BINARY
76
Lead Lag Control Configuration
LEAD_LAG MULTISTATE
77
Lead Lag Partner Instance
LLMPINST
MULTISTATE
78
Lead Lag Comp. Run Time Limit (HOURS)
LLCLIMIT
MULTISTATE
79
Lead Lag Control Status LLAGCTRL MULTISTATE
RW
0, 10, 3.5
DELTA_DEGREES_ FAHRENHEIT
RW
0, 1
—
RO
0, 1
—
RW
0, 2, 0
—
RW
0, 36, 0
—
RW
0, 23, 6
—
RO
0, 4
—
80 Lead Lag Run Status LDLGSTAT MULTISTATE
RO
0, 4
—
81
Lead Lag Run Status -Partner
LDLGSTAP
MULTISTATE
RO
0, 4
—
PAGE 58
INSTALLATION · MAINTENANCE · OPERATION
HTPG0425_IOM
ADDENDUM C
BACnet Objects List Continued
NO.
DESCRIPTION
82
Lead Lag Disable Command
83
Comp. Run Time Until Lead Lag Switch
84 Fan Delay Temp
85 Defrost Drain Time
86
EXV Last Position Minimum
87
EXV Last Position Maximum
88 EXV Start Delay
BN OBJECT NAME
BN TYPE(_VALUE EXPECT DEVICE
BN ACCESS
EN LIMITS
BN UNITS (BACNET_UNITS_)
LLDISABL
BINARY
RO
0, 1
—
LLSWNEXT EVLOTRIP DEFDTIME ELASTMIN
ELASTMAX EXVDELAY
ANALOG ANALOG ANALOG ANALOG
ANALOG ANALOG
RO
0, 10000000 HOURS
RW
25, 70, 35 DEGREES_FAHRENHEIT
RW
0, 600, 300 SECONDS
RW
15, 100, 35 PERCENT
RW
65, 100, 65 PERCENT
RW
0, 255, 60 SECONDS
UNIT COOLERS // ECONET ENABLED
PAGE 59
HTPG.com
©2025 Heat Transfer Products Group Published January 2025 HTPG0425_EN_IOM
Documents / Resources
![]() |
HTPG HTPG0125 EcoNet Enabled Unit Coolers [pdf] Installation Guide HTPG0425, HTPG0125, HTPG0125 EcoNet Enabled Unit Coolers, EcoNet Enabled Unit Coolers, Enabled Unit Coolers, Unit Coolers, Coolers |