HONEYWELL DEV200 Variable Frequency Drive

Variable Frequency Drive DEV200 Specifications
The table below has the basic unit specifications without any extensions
| Main supply (L1, L2, L3) | DEV200 |
| Power range 380-500 V AC | 1.1-75 kW / 1.5-100 hp |
| Supply frequency | 50/60 Hz |
| Displacement power factor (cos φ) near unity | > 0.98 |
| Switching on input supply L1, L2, L3 | 1-2 times/min. |
| Output data (U, V, W) | |
| Output voltage | 0-100% of supply voltage |
| Output frequency | 0-590 Hz (0-300 Hz in FluxMode) |
| Output frequency (OL) | 0-590 Hz |
| Switching on output | Unlimited |
| Motor control and supported motor types | |
| Ramp times | 0.01-3600 s |
| EMC and motor cable length | |
| Cable length – screened/unscreened | 150/300 m |
| Functional Safety | |
| Safety function Safe Torque Off (STO – EN 61800-5-2) | standard |
| Digital inputs | |
| Programmable digital inputs | 6 |
| Changeable to digital output | 2 (terminal 27, 29) |
| Logic | PNP or NPN |
| Voltage level | 0-24 V DC |
| Maximum voltage on input | 28 V DC |
| Input resistance, Ri | Approx. 4 k |
| Scan interval | 1 ms |
| Analog inputs | |
| Analog inputs | 2 |
| Modes | Voltage or current |
| Voltage level | -10 to +10 V (scaleable) |
| Current level | 0/4 to 20 mA (scaleable) |
| Accuracy of analog inputs | Max. error: 0.5% of full scale |
| Pulse inputs / Encoder inputs | |
| Programmable pulse inputs | 2 |
| Voltage level | 0-24 V DC (PNP positive logic) |
| Pulse input accuracy (0.1-1 kHz) | Max. error: 0.1% of full scale |
| * Two of the digital inputs can be used for pulse inputs. | |
| Digital outputs | |
| Programmable digital/pulse outputs | 2 |
| Voltage level at digital/frequency output | 0-24 V DC |
| Max. output current (sink or source) | 40 mA |
| Maximum output frequency at frequency output | 32 kHz |
| Accuracy on frequency output | Max. error: 0.1% of full scale |
| Analog outputs | |
| Programmable analog outputs | 1 |
| Current range at analog output | 0/4-20 mA |
| Max. load to common at analog output (clamp 30) | 500 |
| Accuracy on analog output | Max. error: 0.5 % of full scale |
| Relay outputs | |
| Programmable relay outputs | 2 |
| Max. terminal load (AC) on 1-3 (NC), 1-2 (NO), 4-6 (NC) power card | 240 V AC, 2 A |
| Max. terminal load (AC -1) on 4-5 (NO) power card | 400 V AC, 2 A |
| Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO) power
card |
24 V DC 10 mA, 24 V AC 20 mA |
| Control card | |
| USB interface | 1.1 (Full Speed) |
| USB plug | Type “B” |
| RS485 interface | Up to 115 kBaud |
| Max. load (10 V) | 15 mA |
| Max. load (24 V) | 200 mA |
| Surroundings/external | |
| Ingress protection class | IP: 20, 21 & 55
UL Type: Chassis, Type 1 & Type 12 |
| Vibration test | 0.7 g |
| Max. relative humidity | 5-95% (IEC 721-3-3); Class 3K3
(non-condensing) during operation |
| Ambient temperature | Max. 50 °C without derating, – Operating temperature range is -10 °C to 50 °C without derating Max 55 °C with derating |
| Galvanic isolation of all | I/O supplies according to PELV |
| Aggressive environment | Designed for 3C2 (IEC 60721-3-3) |
| Fieldbus communication | |
| Standard built-in: Protocol Modbus RTU | Optional with separate Fieldbus communication card:
|
| Inbuilt protection | |
| – Electronic motor thermal protection against overload | |
| – Protection against overtemperature | |
| – The AC drive is protected against short circuits on motor terminals U, V, W | |
| – The AC drive is protected against ground faults on motor terminals U, V, W | |
| – Protection against mains phase loss | |
Electrical Data for A, B, and C Enclosures
[T5] 3 x 380-500 V AC – high overload
| High overload (160% 1 min/10 min) | Enclosure size | |||||||||
| Type code | Output current | Typical shaft output power | Continuous input current | Estimated power loss | Protection rating [IEC/UL] | |||||
| (3 x 380-440 V) | (3 x 441-500 V) | IP20/21 | IP55 | |||||||
|
DEV200 |
Con. IN |
Inter. IMAX (60
s) |
Con. IN |
Inter. IMAX (60 s) | kW @ 400 V | hp @ 460 V | [A] @ 400 V |
[W] |
Chassis |
Type 12 |
| P1K1 | 3 | 4.8 | 2.7 | 4.3 | 1.1 | 1.5 | 2.7 | 58 | A2 | A4 |
| P2K2 | 6 | 9.0 | 5 | 8 | 2 | 3 | 5 | 88 | A2 | A4 |
| P4K0 | 10 | 16.0 | 8.2 | 13.1 | 4.0 | 5.0 | 9.0 | 124 | A2 | A4 |
| P7K5 | 16 | 25.6 | 15 | 23 | 8 | 10 | 14 | 255 | A3 | A5 |
| P15K | 32 | 51.2 | 27.0 | 43.2 | 15.0 | 20.0 | 29.0 | 379 | B3 | B1 |
| P30K | 61 | 91.5 | 52 | 78 | 30 | 40 | 55 | 570 | B4 | C1 |
| P45K | 90 | 135.0 | 80.0 | 120.0 | 45.0 | 60.0 | 82.0 | 891 | C3 | C1 |
| P75K | 147 | 221.0 | 130 | 195 | 75 | 100 | 133 | 1232 | C4 | C2 |
[ T5] 3 x 380-500 V AC – normal overload
| Normal overload (110% 1 min/10 min) | Enclosure size | |||||||||
| Type code | Output current | Typical shaft output power | Continuous input current | Estimated power loss | Protection rating [IEC/UL] | |||||
| (3 x 380-440 V) | (3 x 441-500 V) | IP20/21 | IP55 | |||||||
| DEV200 | Con. IN | Inter.
I MAX (60 s) |
Con. IN | Inter. I AX
M (60 s) |
kW @ 400 V | hp @ 460 V | [A] @ 400 V | [W] | Chassis | Type 12 |
| P1K1 | 3 | 4.8 | 2.7 | 4.3 | 1.1 | 1.5 | 2.7 | 58 | A2 | A4 |
| P2K2 | 6 | 9 | 5 | 8 | 2 | 3 | 5 | 88 | A2 | A4 |
| P4K0 | 10 | 16.0 | 8.2 | 13.1 | 4.0 | 5.0 | 9.0 | 124 | A2 | A4 |
| P7K5 | 16 | 26 | 15 | 23 | 8 | 10 | 14 | 255 | A3 | A5 |
| P15K | 38 | 41.3 | 34.0 | 37.4 | 18.5 | 25.0 | 34.0 | 465 | B3 | B1 |
| P30K | 73 | 80 | 65 | 72 | 37 | 50 | 66 | 698 | B4 | C1 |
| P45K | 106 | 117.0 | 105.0 | 116.0 | 55.0 | 75.0 | 96.0 | 1083 | C3 | C1 |
| P75K | 177 | 195 | 160 | 176 | 90 | 125 | 161 | 1474 | C4 | C2 |
Dimensions and Sizes for Enclosures A, B, and C

| Enclosure size | A2 | A3 | A4 | A5 | B1 | B2 | B3 | B4 | C1 | C2 | C3 | C4 | |||
|
Protection rating [IEC/UL] |
IP20
Chassis |
IP21
Type 1 |
IP20
Chassis |
IP21
Type 1 |
IP55 / Type 12 |
IP55 / Type 12 |
IP20 / Chassis |
IP55 / Type 12 |
IP20 / Chassis |
||||||
|
[mm] |
(H) Height of back plate | 268 | 375 | 268 | 375 | 390 | 420 | 480 | 650 | 399 | 520 | 680 | 770 | 550 | 660 |
| (H1) Height with decoupling plate
for fieldbus cables |
374 | – | 374 | – | – | – | – | – | 420 | 595 | – | – | 630 | 800 | |
| (H2) Distance to Mounting holes | 254 | 350 | 257 | 350 | 401 | 402 | 454 | 624 | 380 | 495 | 648 | 739 | 521 | 631 | |
| (W) Width | 90 | 90 | 130 | 130 | 200 | 242 | 242 | 242 | 165 | 230 | 308 | 370 | 308 | 370 | |
| (W1) Distance to Mounting holes | 70 | 70 | 110 | 110 | 171 | 215 | 210 | 210 | 140 | 200 | 272 | 334 | 270 | 330 | |
| (D) Depth | 220 | 222 | 220 | 222 | 175 | 200 | 260 | 260 | 262 | 242 | 310 | 335 | 333 | 333 | |
| Air Cooling [mm] | (I) Air space in inlet | 100 | 100 | 100 | 100 | 100 | 100 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 225 |
| (O) Air space outlet | 100 | 100 | 100 | 100 | 100 | 100 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 225 | |
| [kg] Weight | 4.9 | 5.3 | 6 | 7 | 9.7 | 14.2 | 23 | 27 | 12 | 23.5 | 45 | 64 | 35 | 50
|
|
MODEL SELECTION GUIDE

DEV200P2K2T5E20H2BGXX
- Please be aware that not all combinations are possible. Get help to configure your AC drive using the online configurator
- All VFDs are with LCP installed
- All VFDs comes with standard cable entry
- All VFDs comes with No Adaptation option
- All VFDs comes with latest released standard software
- LCP standard lanugage package including English, German, French, Spanish, Danish, Italian and Finnish; Contact factory for other language options
- All VFDs comes without any fieldbus option – select fieldbus module separately as per requirement.
- All VFDs comes without any funtional extension – select functional module separately as per requirement.
| DEV200 Fieldbus Options | |
| Part Number | Description |
| 200B1235 | DEV200 ProfiNet RT MCA 120 |
| 200B1219 | DEV200 EtherNet/IP MCA 121 |
| 200B1296 | DEV200 Modbus TCP MCA122 |
| 200B5646 | DEV200 EtherCAT MCA 124 |
| 200B1200 | DEV200 Profibus-DP MCA 101 |
| DEV200 Functional Extension | |
| Part Number | Description |
| 200B1212 | DEV200 General Purpose I/O MCB 101 |
| 200B1203 | DEV200 Encoder Input MCB 102 |
| 200B1210 | DEV200 Relay Option MCB 105 |
| DEV200 IP21/NEMA 1 Kits | |
| Part Number | Description |
| 200B1122 | DEV200, A2 Frame, IP21/NEMA1 Kits |
| 200B1123 | DEV200, A3 Frame, IP21/NEMA1 Kits |
| 200B1187 | DEV200, B3 Frame, IP21/NEMA1 Kits |
| 200B1189 | DEV200, B4 Frame, IP21/NEMA1 Kits |
| 200B1191 | DEV200, C3 Frame, IP21/NEMA1 Kits |
| 200B1193 | DEV200, C4 Frame, IP21/NEMA1 Kits |
For more information
- To learn more about Honeywell’s products, visit www.process.honeywell.com or contact your Honeywell account manager.
Honeywell Process Solutions - 2101, CityWest Boulevard
- Houston, TX 77042.
- Honeywell House, Arlington Business Park, Bracknell, Berkshire, England RG12 1EB UK.
- Shanghai City Centre, 100 Zunyi Road, Shanghai, China 200051. www.process.honeywell.com
VFDDOC-XX21-en-100B | Rev 2| February 2025 © 2025 Honeywell International Sàrl
Documents / Resources
![]() |
HONEYWELL DEV200 Variable Frequency Drive [pdf] Owner's Manual DEV200 P1K1, DEV200 P2K2, DEV200 P4K0, DEV200 P7K5, DEV200 P15K, DEV200 P30K, DEV200 P45K, DEV200 P75K, DEV200 Variable Frequency Drive, DEV200, Variable Frequency Drive, Frequency Drive, Drive |