Variable Frequency Drive DEV200 Specifications
The table below has the basic unit specifications without any extensions

Main supply (L1, L2, L3) DEV200
Power range 380-500 V AC 1.1-75 kW / 1.5-100 hp
Supply frequency 50/60 Hz
Displacement power factor (cos φ) near unity > 0.98
Switching on input supply L1, L2, L3 1-2 times/min.
Output data (U, V, W)
Output voltage 0-100% of supply voltage
Output frequency 0-590 Hz (0-300 Hz in FluxMode)
Output frequency (OL) 0-590 Hz
Switching on output Unlimited
Motor control and supported motor types
Ramp times 0.01-3600 s
EMC and motor cable length
Cable length – screened/unscreened 150/300 m
Functional Safety
Safety function Safe Torque Off (STO – EN 61800-5-2) standard
Digital inputs
Programmable digital inputs 6
Changeable to digital output 2 (terminal 27, 29)
Logic PNP or NPN
Voltage level 0-24 V DC
Maximum voltage on input 28 V DC
Input resistance, Ri Approx. 4 k
Scan interval 1 ms
Analog inputs
Analog inputs 2
Modes Voltage or current
Voltage level -10 to +10 V (scaleable)
Current level 0/4 to 20 mA (scaleable)
Accuracy of analog inputs Max. error: 0.5% of full scale
Pulse inputs / Encoder inputs
Programmable pulse inputs 2
Voltage level 0-24 V DC (PNP positive logic)
Pulse input accuracy (0.1-1 kHz) Max. error: 0.1% of full scale
* Two of the digital inputs can be used for pulse inputs.
Digital outputs
Programmable digital/pulse outputs 2
Voltage level at digital/frequency output 0-24 V DC
Max. output current (sink or source) 40 mA
Maximum output frequency at frequency output 32 kHz
Accuracy on frequency output Max. error: 0.1% of full scale
Analog outputs
Programmable analog outputs 1
Current range at analog output 0/4-20 mA
Max. load to common at analog output (clamp 30) 500
Accuracy on analog output Max. error: 0.5 % of full scale
Relay outputs
Programmable relay outputs 2
Max. terminal load (AC) on 1-3 (NC), 1-2 (NO), 4-6 (NC) power card 240 V AC, 2 A
Max. terminal load (AC -1) on 4-5 (NO) power card 400 V AC, 2 A
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO) power

card

24 V DC 10 mA, 24 V AC 20 mA
Control card
USB interface 1.1 (Full Speed)
USB plug Type “B”
RS485 interface Up to 115 kBaud
Max. load (10 V) 15 mA
Max. load (24 V) 200 mA
Surroundings/external
Ingress protection class IP: 20, 21 & 55

UL Type: Chassis, Type 1 & Type 12

Vibration test 0.7 g
Max. relative humidity 5-95% (IEC 721-3-3); Class 3K3

(non-condensing) during operation

Ambient temperature Max. 50 °C without derating, – Operating temperature range is -10 °C to 50 °C without derating Max 55 °C with derating
Galvanic isolation of all I/O supplies according to PELV
Aggressive environment Designed for 3C2 (IEC 60721-3-3)
Fieldbus communication
Standard built-in: Protocol Modbus RTU Optional with separate Fieldbus communication card:
  • PROFIBUS DP V1
  • PROFINET
  • EtherNet/IP
  • Modbus TCP
  • EtherCAT
Inbuilt protection
– Electronic motor thermal protection against overload
– Protection against overtemperature
– The AC drive is protected against short circuits on motor terminals U, V, W
– The AC drive is protected against ground faults on motor terminals U, V, W
– Protection against mains phase loss

Electrical Data for A, B, and C Enclosures

[T5] 3 x 380-500 V AC – high overload

High overload (160% 1 min/10 min) Enclosure size
Type code Output current Typical shaft output power Continuous input current Estimated power loss Protection rating [IEC/UL]
(3 x 380-440 V) (3 x 441-500 V) IP20/21 IP55
 

DEV200

 

Con. IN

Inter. IMAX (60

s)

 

Con. IN

Inter. IMAX (60 s) kW @ 400 V hp @ 460 V [A] @ 400 V  

[W]

 

Chassis

 

Type 12

P1K1 3 4.8 2.7 4.3 1.1 1.5 2.7 58 A2 A4
P2K2 6 9.0 5 8 2 3 5 88 A2 A4
P4K0 10 16.0 8.2 13.1 4.0 5.0 9.0 124 A2 A4
P7K5 16 25.6 15 23 8 10 14 255 A3 A5
P15K 32 51.2 27.0 43.2 15.0 20.0 29.0 379 B3 B1
P30K 61 91.5 52 78 30 40 55 570 B4 C1
P45K 90 135.0 80.0 120.0 45.0 60.0 82.0 891 C3 C1
P75K 147 221.0 130 195 75 100 133 1232 C4 C2

[ T5] 3 x 380-500 V AC – normal overload

Normal overload (110% 1 min/10 min) Enclosure size
Type code Output current Typical shaft output power Continuous input current Estimated power loss Protection rating [IEC/UL]
(3 x 380-440 V) (3 x 441-500 V) IP20/21 IP55
DEV200 Con. IN Inter.

I

MAX (60 s)

Con. IN Inter. I AX

M

(60 s)

kW @ 400 V hp @ 460 V [A] @ 400 V [W] Chassis Type 12
P1K1 3 4.8 2.7 4.3 1.1 1.5 2.7 58 A2 A4
P2K2 6 9 5 8 2 3 5 88 A2 A4
P4K0 10 16.0 8.2 13.1 4.0 5.0 9.0 124 A2 A4
P7K5 16 26 15 23 8 10 14 255 A3 A5
P15K 38 41.3 34.0 37.4 18.5 25.0 34.0 465 B3 B1
P30K 73 80 65 72 37 50 66 698 B4 C1
P45K 106 117.0 105.0 116.0 55.0 75.0 96.0 1083 C3 C1
P75K 177 195 160 176 90 125 161 1474 C4 C2

Dimensions and Sizes for Enclosures A, B, and C

HONEYWELL -DEV200 -Variable -Frequency -Drive

Enclosure size A2 A3 A4 A5 B1 B2 B3 B4 C1 C2 C3 C4
 

Protection rating [IEC/UL]

IP20

Chassis

IP21

Type

1

IP20

Chassis

IP21

Type

1

 

IP55 / Type 12

 

IP55 / Type 12

 

IP20 / Chassis

 

IP55 / Type 12

 

IP20 / Chassis

 

 

 

 

[mm]

(H) Height of back plate 268 375 268 375 390 420 480 650 399 520 680 770 550 660
(H1) Height with decoupling plate

for fieldbus cables

374 374 420 595 630 800
(H2) Distance to Mounting holes 254 350 257 350 401 402 454 624 380 495 648 739 521 631
(W) Width 90 90 130 130 200 242 242 242 165 230 308 370 308 370
(W1) Distance to Mounting holes 70 70 110 110 171 215 210 210 140 200 272 334 270 330
(D) Depth 220 222 220 222 175 200 260 260 262 242 310 335 333 333
Air Cooling [mm] (I) Air space in inlet 100 100 100 100 100 100 200 200 200 200 200 200 200 225
(O) Air space outlet 100 100 100 100 100 100 200 200 200 200 200 200 200 225
[kg]          Weight 4.9 5.3 6 7 9.7 14.2 23 27 12 23.5 45 64 35 50

 

MODEL SELECTION GUIDE

HONEYWELL -DEV200 -Variable -Frequency -Drive-1

DEV200P2K2T5E20H2BGXX

  1. Please be aware that not all combinations are possible. Get help to configure your AC drive using the online configurator
  2. All VFDs are with LCP installed
  3. All VFDs comes with standard cable entry
  4. All VFDs comes with No Adaptation option
  5. All VFDs comes with latest released standard software
  6. LCP standard lanugage package including English, German, French, Spanish, Danish, Italian and Finnish; Contact factory for other language options
  7. All VFDs comes without any fieldbus option – select fieldbus module separately as per requirement.
  8. All VFDs comes without any funtional extension – select functional module separately as per requirement.
DEV200 Fieldbus Options
Part Number Description
200B1235 DEV200 ProfiNet RT MCA 120
200B1219 DEV200 EtherNet/IP MCA 121
200B1296 DEV200 Modbus TCP MCA122
200B5646 DEV200 EtherCAT MCA 124
200B1200 DEV200 Profibus-DP MCA 101
DEV200 Functional Extension
Part Number Description
200B1212 DEV200 General Purpose I/O MCB 101
200B1203 DEV200 Encoder Input MCB 102
200B1210 DEV200 Relay Option MCB 105
DEV200 IP21/NEMA 1 Kits
Part Number Description
200B1122 DEV200, A2 Frame, IP21/NEMA1 Kits
200B1123 DEV200, A3 Frame, IP21/NEMA1 Kits
200B1187 DEV200, B3 Frame, IP21/NEMA1 Kits
200B1189 DEV200, B4 Frame, IP21/NEMA1 Kits
200B1191 DEV200, C3 Frame, IP21/NEMA1 Kits
200B1193 DEV200, C4 Frame, IP21/NEMA1 Kits

For more information

  • To learn more about Honeywell’s products, visit www.process.honeywell.com or contact your Honeywell account manager.
    Honeywell Process Solutions
  • 2101, CityWest Boulevard
  • Houston, TX 77042.
  • Honeywell House, Arlington Business Park, Bracknell, Berkshire, England RG12 1EB UK.
  • Shanghai City Centre, 100 Zunyi Road, Shanghai, China 200051.  www.process.honeywell.com

VFDDOC-XX21-en-100B | Rev 2| February 2025 © 2025 Honeywell International Sàrl

Documents / Resources

HONEYWELL DEV200 Variable Frequency Drive [pdf] Owner's Manual
DEV200 P1K1, DEV200 P2K2, DEV200 P4K0, DEV200 P7K5, DEV200 P15K, DEV200 P30K, DEV200 P45K, DEV200 P75K, DEV200 Variable Frequency Drive, DEV200, Variable Frequency Drive, Frequency Drive, Drive

References

Leave a comment

Your email address will not be published. Required fields are marked *