AN412930943622en-000201
Installation Guide
iC7 Series Pre-charging Unit
for AFE and GC Modules
1 Overview
1.1 Pre-charging Unit
The pre-charging unit is used for pre-charging the system modules that are connected to the same DC bus. There are 3 electrical sizes, and an IEC and a UL variant of the unit. · Pre-charging unit 10, IEC/UL · Pre-charging unit 20, IEC/UL · Pre-charging unit 30, IEC/UL The pre-charging unit is available as an accessory.
5

e30bj917.11

1

Illustration 1: The Pre-charging Unit

1

Charging resistors

2

Fuse switch

3

Contactor

4 3 2

4

Terminal blocks

5

Rectifier and snubber capacitor

Danfoss A/S © 2023.02

AN412930943622en-000201 / 172F8128 | 1

iC7 Series Pre-charging Unit Installation Guide

Mechanical Installation

2 Mechanical Installation
2.1 Safety Information
DANGER
DISCHARGE TIME The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning indicator lights are off. Failure to wait the specified time after power has been removed before performing service or repair work could result in death or serious injury.
- Stop the motor. - Disconnect AC mains, permanent magnet type motors, and DC-link connections to other drives. - Wait for the capacitors to discharge fully before performing any service or repair work. The discharge time is 5 minutes. - Use a measuring device to make sure that there is no voltage, before opening the drive or performing any work on the ca-
bles.
WARNING
SHOCK HAZARD FROM THE COMPONENTS The components of the drive are live when the drive is connected to mains.
- Do not make changes in the AC drive when it is connected to mains.
2.2 Installation Requirements
The products that are described in this guide have the protection rating IP00/UL Open Type. Install them in a cabinet or other enclosure that has a correct level of protection against the ambient conditions in the installation area. Make sure that the cabinet gives protection against water, humidity, dust, and other contaminations. The maximum temperature of the air inside the cabinet for the pre-charging unit is +60 °C (140 °F). The cabinet must also be sufficiently strong for the weight of the system module and other devices. The protection rating of the cabinet must be at least IP21/UL Type 1. When preparing the installation, obey the local regulations.
2.3 Installing the Pre-charging Unit into the Cabinet
Install the pre-charging unit into the cabinet in a horizontal position.
Procedure 1. Attach the pre-charging unit to the cabinet using the mounting holes.
Use M5 screws. In industrial installations, use a minimum of 4 screws. In marine installations, use 8 screws. To make the installation secure, use the outermost mounting holes.

2 | Danfoss A/S © 2023.02

AN412930943622en-000201 / 172F8128

iC7 Series Pre-charging Unit Installation Guide

2121

1212

Mechanical Installation

e30bk014.10

2121

1212

Illustration 2: Mounting Holes of the Pre-charging Unit

1

Preferred mounting holes

2

Alternative mounting holes

2.4 Cooling Requirements
The maximum ambient temperature of the pre-charging unit is 60 °C (140 °F). The product is cooled with natural convection. Make sure that the installation position provides conditions for natural convection. A minimum of 50 mm (2 in) free space at top and bottom is necessary for sufficient cooling air flow.
CAUTION
BURN HAZARD The pre-charging resistor will be very hot during the pre-charging sequence and the following cooling down period.
- Do not install the pre-charging unit on a combustible surface. - Do not touch when hot.

2.5 UL 98 Requirements
Minimum distances are required from the fuse switch of the pre-charging unit to the enclosure walls. · 165 mm (6.50 in) from the top and bottom of the fuse switch terminals · 13 mm (0.52 in) from the left side of the fuse switch These distance requirements are for the size of the enclosure, not for electrical spacings.

Danfoss A/S © 2023.02

AN412930943622en-000201 / 172F8128 | 3

iC7 Series Pre-charging Unit Installation Guide

13 (0.52)

165 97.5 (6.50) (3.84)

e30bk550.10

Mechanical Installation

e30bj821.11

165 81.5 (6.50) (3.21)

Illustration 3: Keep-out-area Around the Pre-charge Unit 10­30 UL Types, UL 98

2.6 Dimensions of the Pre-charging Unit, IEC

15 (0.59)

30 (1.18)

60 (2.36)

292 (11.5) 240 (9.45)
Ø6 (0.24)

60 (2.36)

239 (9.41)

118 (4.64) 240 (9.45)

263 (10.35)

18 (0.71)

230 (9.05)
Illustration 4: Dimensions of the Pre-charging Unit in mm (in), IEC 4 | Danfoss A/S © 2023.02

AN412930943622en-000201 / 172F8128

iC7 Series Pre-charging Unit Installation Guide

2.7 Dimensions of the Pre-charging Unit, UL

15 (0.59)

30 (1.18)

60 (2.36)

292 (11.5) 240 (9.45)
Ø6 (0.24)

60 (2.36)

112 (4.41) 240 (9.45)

263 (10.35)

115 (4.53) 156 (6.14)

Illustration 5: Dimensions of the Pre-charging Unit in mm (in), UL

Mechanical Installation
239 (9.41)

e30bj822.11

Danfoss A/S © 2023.02

AN412930943622en-000201 / 172F8128 | 5

iC7 Series Pre-charging Unit Installation Guide

Electrical Installation

3 Electrical Installation
3.1 Electrical Installation Safety
WARNING
OVERHEATED CABLES Overheated cables are a fire hazard.
- Because of several possible cable installations and environmental conditions, it is important to consider local regulations and
IEC/EN standards.

Route the main circuit and control circuit wires away from sharp edges, screw threads, burrs, fins, moving parts, drawers, and similar parts, which can abrade the wire insulation.
For the main circuit, use double insulated wires or protect the wires with, for example, a protective sleeve or wrap to minimize the risk of short circuit. Maintain separation between the main and control circuit wires.

3.2 Cable Requirements

Table 1: Mains Terminals Line 1, Line 3, Line 5

Item

Value

Terminal type

Screw terminal

Tool Wire size (Cu)

Flat head 4­10 mm2 (10­8 AWG), solid or stranded, with minimum insulation temperature rating of 75 °C.

Strip length

12 mm (0.47 in)

Torque per wire size

4­6 mm2: 3 Nm 10 mm2: 4 Nm 10 AWG: 30 in-lb 8 AWG: 35 in-lb

Table 2: DC Terminals DC+, DC-

Item

Value

Terminal type Wire size (Cu)

Spring terminal 4­10 mm2 (10­8 AWG), solid or stranded, with minimum insulation temperature rating of 75 °C.

Strip length

15 mm (0.59 in)

Table 3: Control Terminals A1, A2 Item Terminal type Tool Wire size Strip length Torque

Value Screw terminal Pozidriv 2 or flat head 5.5 mm (0.22 in) 1­2.5 mm2 (18­14 AWG) 10 mm (0.39 in) 1.2 Nm (11 in-lb)

A PE conductor is required if the pre-charging unit is not fixed to a grounded conductive structural part of the drive enclosure.

6 | Danfoss A/S © 2023.02

AN412930943622en-000201 / 172F8128

iC7 Series Pre-charging Unit Installation Guide

Electrical Installation

Table 4: Grounding Terminal PE Item Terminal type
Wire size (Cu)

Value
Ring or fork terminal, size M8 Reference terminal type (UL): · P8-38R-Q (AWG 8, Panduit) · P10-38R-L (AWG 10, Panduit)
4­10 mm2 (10­8 AWG)

3.3 Fuses
Use only these fuse types in the fuse switch of the pre-charge unit. Table 5:
Standard Fuse In [A] Fuse Un [V AC] Fuse type

IEC

40

690

NH gG size 000

UL

40

600

Class J, Time-delay, 2­3/8 x 1­1/16 in (60x27 mm)

Part number, Mersen Part number, Eaton

H000GG69V40

40NHG000B-690

AJT40

LPJ-40SP

3.4 Terminals

A1 A2

A1 A2

e30bj902.11

LINE 1 LINE 3 LINE 5 PE

DC+ DC-

Illustration 6: Terminals of the Pre-charging Unit

Left Right

Pre-charging unit 10/20 Pre-charging unit 30

Table 6: Pre-charging Unit Terminal Descriptions Terminal Description

Line 1 Line 3 Line 5

AC-supply connection point for pre-charging circuit

DC+

Pre-charging circuit, DC terminal connection point

LINE 1 LINE 3 LINE 5 PE

DC+

DC-

Danfoss A/S © 2023.02

AN412930943622en-000201 / 172F8128 | 7

iC7 Series Pre-charging Unit Installation Guide

Electrical Installation

Terminal DC-
A1 A2
PE

Description Pre-charging circuit, contactor coil terminal. Coil voltage range 100­250 V AC, 50/60 Hz. Grounding terminal for the pre-charging circuit

See the wiring diagrams in 3.6 Pre-charging Unit Wiring Diagram and 3.7 Control Wiring Diagram.
3.5 Installing the Power Cables
Procedure 1. Attach the mains cable to the mains terminals Line 1, Line 3, and Line 5 of the pre-charging unit. - a. Attach the grounding conductor of the mains cable to the PE terminal of the pre-charging unit. See the cable requirements in 3.2 Cable Requirements. See the location of the mains terminals in 3.4 Terminals. 2. Attach the DC cable to the DC terminals DC+ and DC- of the pre-charging unit. See the cable requirements in 3.2 Cable Requirements. See the location of the DC terminals in 3.4 Terminals.

3.6 Pre-charging Unit Wiring Diagram

8 | Danfoss A/S © 2023.02

AN412930943622en-000201 / 172F8128

iC7 Series Pre-charging Unit Installation Guide

L1

L1

L1

L1

L1

L1

L2

L2

L2

L2

L2

L2

L3

L3

L3

L3

L3

L3

1

1

-QB6

LINE 1 LINE 3 LINE 5

2

4

6

1

3

5

1

3

5

-QA6

2

4

6

-TB6 3 + -CA6 -

-QB6

LINE 1 LINE 3 LINE 5

2

4

6

1

3

5

1

3

5

-QA6

2

4

6

-TB6 3 + -CA6 -

Electrical Installation

e30bj903.11

L1

L1

L1

L2

L2

L2

L3

L3

L3

1

-QB6

LINE 1 LINE 3 LINE 5

2

4

6

1

3

5

1

3

5

-QA6

2

4

6

-TB6 3 + -CA6 -

-XD6 1 +

3-

-RA6.1 -RA6.2

-XD6 2 +

4-

-XD6 1 +

3-

-RA6.1 -RA6.3

-RA6.2 -RA6.4

-XD6 2 +

4-

-XD6 2 +

1+

5-

6-

-RA6.3 -RA6.1 -RA6.5

-RA6.2 -RA6.6

-RA6.4

-XD6 4 +

3+

7-

8-

1

1

1

DC+ DC-

DC+ DC-

DC+ DC-

DC+ DC-

DC+ DC-

DC+

DC+
DC+

DC-

DC-

10

20

30

Illustration 7: Main Circuits of the Pre-charging Units

1

Double-insulated cable

10

Pre-charging unit 10, IEC/UL

20

Pre-charging unit 20, IEC/UL

30

Pre-charging unit 30, IEC/UL

DC+ DC-
DC-

Danfoss A/S © 2023.02

AN412930943622en-000201 / 172F8128 | 9

iC7 Series Pre-charging Unit Installation Guide
3.7 Control Wiring Diagram
1
115... 230 VAC

-SF11

23 24

2

3

A1 -QA6
A2

A1 -QA3
A2

N

4

123 COM NO NC
X1

456 COM NO NC
X2

78 COM NO
X3

71 72 TI+ TI-
X51

Electrical Installation

e30bi270.11

Illustration 8: Pre-charging Control Wiring Diagram

1

Short-circuit protected

2

Pre-charging contactor control

3

Main input device control

4

Basic I/O of the control unit of the AFE module

Vacon Ltd, Member of the Danfoss Group Runsorintie 7 FIN-65380 Vaasa www.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogs, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.