Instruction Manual for REVERSOMATIC models including: SL100ECM, SL100ECM Energy Recovery Ventilator, SL100ECM, Energy Recovery Ventilator, Recovery Ventilator, Ventilator

Samer

Kitchen Exhaust Fan BK100 XL Series - 176 CFM, 4.5 Sones, 0.10 S.P | C – Reversomatic


File Info : application/pdf, 10 Pages, 1.50MB

PDF preview unavailable. Download the PDF instead.

SL100ECM-manual c462bb64-0b8b-40cf-b002-824105b5dc1d ?v=1746460533
ERV INSTALLATION AND OPERATING INSTRUCTIONS

RERV-SL100ECM

790 Rowntree Dairy Road, Woodbridge, ON Canada L4L 5V3

Tel: 905.851.6701 Fax: 905.851.8376

Toll Free: 1.800.810.3473 (Canada) 1800.499.5073 (U.S.A.)

www.reversomatic.com

info@reversomatic.com

IMPORTANT SAFETY INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS

! WARNING !
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY, OBSERVE THE FOLLOWING: 1. Read all the instructions carefully before installation,
operation or maintenance of the unit. Failure to comply with instructions could result in personal injury and/or property damage. 2. Installation of the unit and the corresponding electrical wiring must be done by a qualified person and be in accordance with all municipal and national electrical codes and pertinent industry standards should be verified before installation. 3. Use this unit only in the manner intended by the manufacturer. 4. "To ensure quiet operation of the ENERGY STAR certified H/ERV, each product model must be installed using sound attenuation techniques appropriate for the installation."
5. "The way your heat/energy-recovery ventilator is installed can make a significant difference to the electrical energy you use. To minimize the electricity use of the heat/energy-recovery ventilator, a stand- alone fully ducted installation is recommended. If you choose a simplified installation that operates your furnace air handler for room-to room ventilation, an electrically efficient furnace that has an electronically commutated
6. (EC) variable speed blower motor will minimize your electrical energy consumption and operating cost."
7. "Installation of a user-accessible control with your product model will improve comfort and may significantly reduce the product model's energy use."
8. Moving Parts, Disconnect Power supply before opening. ensure that all the nuts and screws are securely fastened before restarting the unit.
9. Before servicing or cleaning the unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device,
10. To reduce the risk of fire, use only metal ductwork. 11. For residential use only. The unit must be grounded. 12. Do not install in a cooking area. 13. This unit is not designed to exhaust combustion and/or
dilution air for fuel burning appliances

PACKAGING INSPECTION
Open the box and check to make sure all the parts and accessories are present and in good condition. If you find any parts missing or any shipping damage please contact factory or our distributor immediately.

CONTENTS

Parts List

1

Wiring Diagram

· Control Board

2

· Furnace / Fan-Coil / Heat Pump Interlock

3

(For a furnace connected to a cooling system)

- Standard Furnace Interlock Wiring

3

- Alternate Furnace Interlock Wiring

3

HRV and ERV Typical Installations

· For High Rise Condominium

- Fully Ducted System - With Fan-Coil System

4

· Drain Connection

4

Air Flow Balancing

· Balancing Procedure

5

· Pitot Tube Air Flow Balancing

5

Maintenance

· Regular Maintenance

6

· Annual Maintenance

7

Troubleshooting

7

Climate Zone

8

! CAUTION !
1. Turn the unit OFF during construction or repair to avoid filter blockage.
2. Exhaust air outside - Do not intake / exhaust air in spaces within walls, crawl spaces, garage, or into attics.
3. When leaving house for a long period of time (more th two weeks), a responsible person should check if unit operates adequately.

Parts List
1 19
2
5

3

11

4

6

9

19 20
12 13
18 5
17
16 15

RERV-SL100ECM 1
*Optional Parts:
21 *
14
*
22
23 *
24 *

Reference
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21* 22* 23* 24*

10

7

8

Description
HRV/ERV -lid, Pan Assembly Polypropylene collar 6' Dia. Filter 8" x 12" (MERV -4 )
Enthalpy Core 5" Polypropylene Backdraft Damper
Motor - Exhaust/Supply(ECM) CF Adjustable Door Latch Drain Spout Assembly Core Locking Bracket Nut Safety Switch Electrical Box Cover
Main Control Board (ECM) Main Control Board Bracket
Defrost Motor Temperature Sensor Defrost Damper Assembly (6' dia.)
Door Hinges Extension Box Cover Mounting Brackets
"T" Connector Webbing/Brackets/Ladder Locks Electronic Timer Switch (TC100)
Drain Pipe

Part No.
9315 PBD6C 9358SL 9314SL 14043 9317SL 9319 9320 9321 14016 9322 9323 9361-ECM (DIP) B 9355 9325 9326 9327SL 9328 9329 011135 9330 9332 9349 9331

RERV-D100SA QTY 1 2 2 1 2 2 1 2 1 1 1 1 1 2 1 1 1 1 Set 1 4 1 2 Sets 1 1

Wiring Diagram : Superior ECM with & without DIP Switch

2

Wiring Diagram : Superior ECM with & without DIP Switch

2

Optional Accessories (Not Supplied)
a) Timer Switch (TC100-5V) (old/new) b) Wall Switch c) Dehumidistat d) Time Delay Switch (TC100-120 & TC100-120P) e) Master On/Off Switch for HRV/ERV f) Light g) Intermittent Switch (old/new) (IC100-5V)

a)
YEL RED GRN

c)

b)

Hi

DC connection

Low FAN

FAN

Exhaust

Supply

BLACK WHITE RED

Note:
Up to 4 Timer Switches (TC 100-5V) and one intermittent switch (IC 100-5V) can be connected to control board of HRV/ERV by using three 24 AWG (min.) standard Copper wires as shown. Maximum total wire length 75ft. (see option 2)

Option 2:
g)

to Control Board
+5 DAT GND

YEL RED

Intermittent

GRN OR Timer

Switch 1

RED WHIT E BLAC K

120 Vac / 1 / 60Hz Power Supply

Light / Switch Option

b)

f)

Light On / Off

HRV/ ERV Hi / Low
+ -
120 Vac / 1 / 60Hz Power Supply Ext. Interlock

or
b) +
Hi

4 - Speed Controller for Manual Balancing and Air Flow Adjustment
(Turn the Knob clockwise to increase speed)

Ground

Exhaus t Fan Speed

Supply Fan Speed

LINE LINE

DAMP NO DAMP NC

Low

High

Low

High

Speed Contact

Low Voltage (Dry contact)
ON DIP 1 2 3 4

Please do not touch DIP setting

NEUT

WHITE BLUE YELLOW YELLOW BLUE WHITE

NEUT LINE NEUT

(Also available without OFF mode)
Low Voltage

YEL

RED

Timer

GRN

Switch

2

GND DAT 5V

YEL

RED

Timer

GRN

Switch

3

Interloc k

Temp Sensor

NC C NO

(These connections must be done inside the electrical box)

YEL

RED

Timer

GRN

Switch

4

(TC100-5V)

Furnace, Fan Coil, Heat Pump Interlock
PCB with DIP Switch
(Newer Version)

BLACK WHITE

Damper motor

For external damper connection (single stack motor)

YELLOW ORANGE YELLOW ORANGE

Damper motor

For built-in internal damper connection (forward / reverse motor)

to Control Board

New Intermittent Switch (TC150-5V)

+5 DAT GND
NEW DAT Intermittent
+5V
OR Timer
GND
Switch 1

RED WHIT E BLAC K

NEW

DAT

+5V

Timer

GND

Switch

2

New Timer Switch (TC100-5V)

NEW

DAT

+5V

Timer

GND

Switch

3

EXHAUST
BLK
LINE NEUT
WHT

Remote

e)

ON/OFF

(HV-High Voltage)

On OR

NEW

DAT

Timer

+5V

Switch

GND

4

(TC100-5V)

LINE SW

SUPPLY

WHT

Low

d) TC100-120

BLACK

BLACK RED

GREEN BROWN BLUE

+
120 Vac / 1 / 60Hz

BLACK

RED

Power Supply -

WHITE

Ground

FAN Supply

FAN Exhaust

AC connection

Note: Same power source can be used for wall switch,Time delay switch

Door Safety switch

(TC100-120 & TC100-120P) and HRV / ERV

TC100-120P

+ -
120 VAC / 1 / 60Hz

Power Supply

GREEN BROWN BLUE
WHITE

RED

Off

Remote 0n/0ff
HV

Jumper

(remove jumper to install master ON/OFF switch)

Note:

Make sure, the Line must be connected to Line and Neutral connected to Neutral. Unit will not function if not connected correctly.

Wiring Diagram (cont'd)

3

Furnace / Fan-Coil / Heat Pump Interlock:

! WAR N I NG !
Never connect a 120 volt AC circuit to the terminals of the furnace/fan-coil/heatpump interlock (Standard Wiring). Only use the low voltage class 2 circuit.

Standard Interlock Wiring

FOUR WIRE
TW OWIRE heating only

THERMOSTAT TERMINALS

W

R

G

Y

W R G C Y

TW OWIRE

Cooling System

Furnace, Fan Coil, Heat Pump Interlock
GND DAT 5V

Ex Su

Temp Sensor

NC

C

NO

ORANGE BLUE

(These connections must be done inside the electrical box)
SUPERIOR ECM CONTROLBOARD
Note: These Connections must be done inside the electrical box

For a furnace connected to a cooling system:
On some older thermostats, energizing the R and G terminals at the furnace has the effect of energizing Y at the thermostat and thereby turning on the cooling system. If you identify this type of thermostat, you must use the "Alternate Interlock Wiring".

FOUR WIRE TW OWIRE heating only
W R G C Y

THERMOSTAT TERMINALS

W

R

G

Y

Furnace, Fan Coil, Heat Pump Interlock
GND DAT 5V

Temp
Ex Su Sensor

YELLOW ORANGE
BLU E

NC C NO
(These connections must be done inside the electrical box)

TW OWIRE

SUPERIOR ECM CONTROLBOARD

Cooling System

Note: These Connections must be done inside the electrical box

HRV and ERV Typical Installations

4

Installation Options for High-Rise Condominium Fully Ducted System

With Fan-Coil ·Fresh air from outside should be installed on

System

Fan-coil supply side (HRV/ERV station #2) and HRV/ERV should be interlocked with

Fan-coil unit.

Balancing Box (recommended air filter for auto balancing unit to prevent dust build-up on air flow sensors)
FRESH AIR EXHAUSTED AIR

Mounting Brackets

Insulated ductwork

Filter box FB-100

Note:
· All Exhaust Vents must be installed
min. 5 ft away from sidewalls.

Drywall Bulkhead

Access door

Minimum 24" x 12" access door required for filter cleaning & replacement

Note: All HRV / ERV must be balanced in the field.
Drain Connection During defrost cycle the HRV unit may produce some condensation and the water should flow into a nearby drain.

The HRV cabinet has pre-punched holes(two on side and one on the door) for the drain, in order to keep the drain pan intact, hand tighten the plastic drain spout to the unit using the gasket and nuts.

For Vertical installation

Cut two sections of ½" drain pipe and connect the other ends to the drain spout then connect to "T" connector. Connect a drain line and create a P-trap to prevent the unit from unpleasant odours from drain source. Tape or fasten base to avoid any bends.

(For vertical installation)

Drain Pan
Drain Spout ½" I.D.
Drain Pipe " T " Connector

Drain Pan "P" Trap

Drain Spout Assembly

Plastic Drain Pan

Rubber washer

HRV/ERV Steel Housing

Lid

Steel washer

Zip Tie

Nut

to Drain

Drain Spout

Note: For Horizontal installation, connect only 1 drain spout assembly on lid / door.
cut one ½'' drain pipe and connect one end to the drain spout and the other end to the drain line. Don't forget to create a P-trap as shown above.

Use this drain for horizontal installation

! CAUTION !
The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point or freeze protection must be provided.

Air Flow Balancing

5

For units without built-in true Automatic Electronic Air-balancing and for cross verification only
Balancing Procedure
It is required to have balanced air flows in an HRV/ERV. The volume of air brought in from the outside must equal the volume of air exhausted by the unit while running at normal speed. If the air flows are not properly balanced, then:

· The HRV/ERV may not function at its maximum efficiency · A negative or positive air pressure may occur in the house or condo
· The unit may not defrost properly

Prior to balancing, ensure that:

1. All the HRV/ERV's components are in place and functioning properly.

2. All sealing of the ductwork system has been completed.

3. Set the unit to normal speed.

4. 5.

Air flows in branch to specific areas of the house should be adjusted first prior to balancing the unit. After taking reading of both the stale air to the HRV/ERV duct and fresh air to the house duct, the duct with

the lowerCFM reading should be left alone while the duct with the higher airflow should be slower down to

6. match the lower reading by adjusting dial/speed controller on control board(see board layout on page-4).

Return unit to appropriate fan speed for normal operation.

Pitot Tube Airflow Balancing

The following is a method of field balancing an HRV/ERV using a Pitot tube advantageous in situations when flow stations are not installed in the ductwork. Procedure should be performed with the HRV/ERV on normal speed.
The first step is to operate all mechanical systems on most desire speed, which have an influence on the ventilation system, i.e.the forced air furnace or air handler if applicable. This will provide the maximum pressure that the HRV/ERV will need to overcome, and allow for a more accurate balancing of the unit.
Drill a small hole in the duct (about 3/16"), three feet downstream of any elbows or bends, and one foot upstream of any elbows or bends. These are recommended distances but the actual installation may limit the amount of straight duct.
The Pitot tube should be connected to a magnehelic gauge capable of reading from 0 to 0.25 in. (0-62 Pa) or other digital airflow meter. The tube coming out of the top of the pitot is connected to the high pressure side of the gauge/meter and the tube coming out of the side of the pitot is connected to the low pressure or reference side of the gauge/meter.

Pitot tube and gauge

Duct

AIR FLOW

High

Pressure

Pitot tube

Tap

Magnehelic

gauge

Low Pressure Tap
NOTE:
Place the magnehelic gauge on a level surface and adjust it to zero.

Insert the pitot tube into the duct; pointing the tip into the airflow. For general balancing it is sufficient to move the pitot tube around in the duct and take an average or typical reading. Repeat this procedure in the other duct.
Determine which duct has the highest airflow (highest reading on the gauge). Then slower down that motor speed
by adjusting dial/speed controller on control board to match the lower reading from the other duct. The flows should now be balanced. Actual airflow can be determined from the gauge/metre reading. The value read on the gauge is called the velocity pressure and on the flow meter is called air velocity(FPM). The Pitot tube comes with a chart that will give the air flow velocity based on the velocity pressure indicated by the gauge. This velocity will be in either feet per minute or metres per second. To determine the actual airflow, the velocity is multiplied by the cross sectional area of the duct being measured.

Air Flow Balancing (cont'd)

Note:(Option #2)
*For balancing, extension box cover plate is provided with 3 holes on supply side and 3 holes on exhaust side. *Do not use pitot tube to open holes in the insulation as it may block/damage the pitot tube. *Take 3 readings on each hole and average all 9 readings for supply and same for exhaust.
*After finish balancing, plug all six holes with plastic plugs provided with the unit.

DUCTDIAM. CROSSSECTIONAREA

5"

0.136sq.ft.

6"

0.196sq.ft.

Opening area: 0.136 sq.ft. (option #2)
.4 .5

Extension box cover plate

Min 3 ft straight duct

6

P" Ø5 Ø6 0.010 0.004 0.012 0.006 0.016 0.008 0.022 0.010 0.027 0.013 0.034 0.016
0.041 0.020
0.048 0.023
0.057 0.027

CFM
50 60 70 80 90 100 110 120 130

P"= Velocity Pressure in inch

Pitot tube

Pitot

tube

Magnehelic

gauge

(option #1)

Min 3 ft straight duct Opening area: 0.2196sq.ft.

Note: To take more accurate readings, use option #1(if possible).

CFM = Opening / Cross-sectional Area(sq.ft.) x velocity(FPM)

The accuracy of the flow reading will be affected by how close to any elbows or bends the readings are taken. Accuracy can be increased by taking an average of multiple readings as outlined in the literature with the Pitot tube.

Maintenance
Regular Maintenance
1. Turn the unit off and disconnect the power supply. 2. Unlatch the door and lift the door panel towards you, hold it firmly and slide it to the left. 3. Clean the inside of the door and drain pan with a damp cloth to remove dirt and debris
that may be present. 4. Clean the filters: (twice a year)
- Remove the filters. - Vacuum to remove most of the dust. - Wash with a mixture of warm water and mild soap. Rinse thoroughly and shake filters
to remove water and let dry. 5. Oil/grease defrost damper levers and hinges.
6. Check the exterior fresh air supply hood:
- Make sure there are no leaves, twigs, grass, ice or snow that could be drawn into the vent. Partial blocking of this air vent could cause the unit to malfunction.
7. Reassemble the components, Filters and Door (The door is secured when you hear a click.)
8. Reconnect the power and turn on the unit.

Maintenance (cont'd)

7

Annual Maintenance

Repeat steps 1 to 5 from the previous section and continue with the following steps:

1. Clean the HRV and ERV core: - Remove filters, Loosen the core locking bracket, Remove the core, carefully grip ends of core and pull evenly outward

-

HRV Core > remove dust using vacuum cleaner or

rinse with cold water

> Soak and rinse the HRV core in warm

soapy water

- ERV Core > remove dust using vacuum cleaner

2. Motors - Maintenance Free, permanently lubricated

! ATTENTION !
· Do not use cleaning solution for the HRV/ERV core · Do not use pressure washer on the HRV/ERV core · Do not place the HRV/ERV core in dishwasher · Do not use bleachor chlorine

3. Drain Tube and Drain Pipe - Inspect drain tube, drain pipe and "P" trap for blockage, mold or kinks. Flush with warm soapy water and replace if worn, bent or unable to clean.

4. Clean Duct Work if Required - Wipe and vacuum the duct once every year. The duct work running to and from HRV/ERVmay accumulate dirt. You may wish to contact a heating / ventilation company to do this.

5. Cleaning the Fans - Fans may accumulate dirt causing an imbalance and/or excessive vibration on the HRV/ERV. A reduction in

the air flow may also occur. In new construction this may result within the first year due to heavy dust and may occur periodically

after that over time depending on the outdoor conditions.

· open the servicedoor · remove the core

! WARNING !

· disconnect the fan motor wires · remove the screws securing fan assembly · pull the fan assembly out of unit · check for any accumulation on the blades

Electrical shock hazard. Can cause injury or death. Before attempting to perform any serviceor maintenance,

· clean with a small brush if necessary:

always disconnect the unit from its

- scrub individual fan blades until clean

power source.

- vacuum and wipe

· put the components back in place

· reconnect the power supply and turn the unit back on.

Troubleshooting
PROBLEMS
1. Air flow is low
2. Sensescold air from Supply
3. Waterin the bottom of HRV

POSSIBLE CAUSES
- HRV/ERV airflow improperly balanced (for units without built-in Automatic Electronic Air-balancing)
- filter clogged - core obstructed - exterior fresh air supply blocked - ductwork is restricting - power supply low (Low Voltage)
- Exhaust hood outside the house is blocked
- HRV/ERV airflow improperly balanced (for units without built-in Automatic Electronic Air-balancing)
- outdoor temperature is extremely cold
- drain pans, drain tube, drain pipe and "P" trap are clogged

SOLUTION
- have professional balancer or contractor balance the unit
- remove and clean filter - remove and clean core - removeand clean the blockage - inspect duct installation - switch off the unit immediately and
call the electrician to check the voltage
- remove the blockageand clean the hood
- have professional balancer or contractor balance the unit
- placement of furniture or closed doors is restricting the movement of air in the home
- install a duct heater - check for blockageand for kinks in
line - check connections - make sure water drains properly

Troubleshooting (cont'd)

PROBLEMS
4.Timer switch 20/40/60 minute / intermittent Switch light doesn't stay on
5. Unit is not defrosting properly
6.All 3 LEDs of timer switch blinks
7. LED's on the Main Control board and the remote wall mount Timer Switch will flash 0.5 sec On/0.5 sec Off/0.5 sec On then 2 sec Off, then repeat the cycle

POSSIBLE CAUSES
- loose connection - the switch may be defective - turn off the HRV/ERV bracker
- fresh air duct maybe frozen - HRV/ERV airflow improperly
balanced -Temp. sensor maybe defective - Control board reports error - lost communication with main
control board - Exhaust fan open circuit:
a) motor burned b) fan overheated
- damper obstructed

8. LED's on the Main Control board and the remote wall mount Timer Switch will flash 0.5 sec On/0.5 sec Off/0.5 sec On/0.5 sec Off/ 0.5 sec On/0.5 sec Off/0.5 sec On
then 2 seconds Off, then repeat the cycle

- exhaust fan jam / over-current - Supply fan open circuit:
a) motor burned b) fan overheated
- damper obstructed

- Supply Fan jam / over-current

9. LED's on the Main Control board and the remote wall mountTimer Switch willflash: 0.5 sec On/0.5 sec Off/ 0.5 sec On/0.5 sec Off/ 0.5 sec On/0.5 sec Off/ 0.5 sec On/0.5 sec Off/ ts off and 0.5 sec On, then 2 seconds Off, then repeat the cycle

- Temperature sensor failure (Supply shuts down and exhaust runs on low only)

Select ERV for your Climate Zone

HRVs are recommended for colder climates. ERVs are designed for warm-humid climates with long cooling seasons.

Severe Conditions Moderate Conditions Dry Climate

Pacific Conditions High Humidity

U.S. Department of Energy climate zones map

8
SOLUTION
- check connection - replace the timer switch - reset the main controller - check and remove the ice - have professional balancer or
contractor balance the unit - replace theTemp. sensor - refer to problem 4. - check all wire connections on timer
switch and main control board - replace motor - call technician (if possible replace
fan)
- check backdraft damper, no screw must interfere the function of the damper
- replace the fan
- replace motor - call technician (if possible replace
fan)
- check back-draft damper, no screw must interfere the function of the damper
- replace the fan
- replace temperature sensor



References

Adobe PDF Services