Haswill STC-1000 Temperature Controller User Manual

Haswill-logo

Haswill STC-1000 Temperature Controller

Haswill-STC-1000-Temperature-Controller-product

Product Information

STC-1000 Thermostat

  • Manufacturer: Haswill Electronics
  • Product Name: STC-1000 Thermostat

Product Interface & Operation

The STC-1000 temperature controller is designed to regulate temperature by turning on/off the power status of the connected load. This unit is equipped with dual individually relays which can connect two loads simultaneously: one for refrigeration and another for heating. The heating and refrigeration controlling modes auto switch according to the room sensor temperature. The front panel of the STC-1000 thermostat displays icons that indicate its operation mode. The unit is designed to switch between heating and refrigeration modes automatically, making it an all-purpose temperature controller.

Product Package Contents

  • Controller – 1 PCS
  • Clips – 2 PCS
  • Sensor – 1 PCS
  • Manual – 1 PCS
  • Waterproof Cover – 1 PCS

Product Specification

  • Input Power: Maximum current 10A (Default) under 220V AC
  • Sensor: IP65 to the front panel

Product Usage Instructions

STC-1000 ThermostatTo use the STC-1000 thermostat, follow these steps:

  1. Connect the controller to the power source and the load you wish to regulate temperature for.
  2. Place the sensor in the room where you want to monitor the temperature.
  3. The controller will automatically switch between heating and refrigeration modes based on the room sensor temperature.
  4. To check the temperature set-point, press the F1 key. To check the Hysteresis value, press the F2 key.
  5. To power off/on, hold the key for 3 seconds.

STC-1000 temperature controller regulates the temperature by turn on/off the power status of the connected load. Within dual individual relays, this unit could connect two loads simultaneously, one for refrigeration, another for heating, and the heating and the refrigeration controlling modes auto switch according to the room sensor temperature; that’s why it was called the “All-Purpose Temperature Controller.”

Package

  • Controller: 1 PCS
  • Clips: 2 PCS
  • Sensor: 1 PCS
  • Manual: 1 PCS
  • Waterproof Cover: 1 PCS

Specification

  • Input Power: 220V AC ± 10% 50/60HZ; (12/24/48/110V Option)
  • Maximum current: 10A (Default) under 220V AC
  • Sensor: NTC Sensor (NTC), 25°C /10 KΩ, the sensor cable 200cm
  • Protection Class: IP65 to the front panel
  • Storage: -10°C ~ 60°C, RH<90%, without condensation
  • Measuring Range: -50.0°C ~ 120°C
  • Controlling Range: -50.0°C ~ 99.9°C
  • Resolution: 0.1°C
  • Accuracy: ± 1°C
  • Power Consumption: ≤ 3W

Haswill-STC-1000-Temperature-Controller-fig-1Environmental Information

  • Package: The package’s material is 100% recyclable. Just dispose of it through specialized recyclers.
  • Product: The electro components can be recycled or reused if it is disassembled for specialized companies.
  • Disposal: Please do not burn or throw the controllers in domestic garbage. Observe the respective law in your region concerning the environmentally responsible manner of disposing of its devices.

Interface & Operation

Front Panel & Icon

Haswill-STC-1000-Temperature-Controller-fig-2

Under normal status

  • Press theHaswill-STC-1000-Temperature-Controller-fig-3 key to check the temperature set-point F1;
  • Press theHaswill-STC-1000-Temperature-Controller-fig-4 key to check the Hysteresis value F2F2;
  • Hold the Haswill-STC-1000-Temperature-Controller-fig-5key for 3s to power off / on;
  • Hold theHaswill-STC-1000-Temperature-Controller-fig-6 key and theHaswill-STC-1000-Temperature-Controller-fig-7 key at the same time for 5s to restore factory settings

Indicators / Characters

Indicator Meaning Light on Light off Light Flashing
Cool Refrigerating Working Stop Delay
Heat Heater status Working Stop N/A
Set Setting status On Set Non-setting N/A

Dimensions & Installation

Haswill-STC-1000-Temperature-Controller-fig-8

  • Suggested amount dimension: 71 * 29 * 85 + mm (W*H*D)
  • Detach the slide fasteners, put the controller into the hole, wiring follow the diagram
  • Install the fasteners, and install the waterproof cover
  • Please avoid installing in the below environments:
    • Relative humidity > 90%, have condensation.
    • The places that temperature <-10°C or >60°C.
    • The places that have inflammable and explosives.
    • Strong vibration or struck.
    • Exposed to the continuous water mist spraying.
    • Exposed to the dust.
    • Exposure to corrosive and pollution gas (gas, smoke, or salt fog that contains sulfur or ammonia.
    • Wireless electromagnetic interference or strong magnetic fields (near to transmitting antenna or switch board room);

Wiring Diagram

Haswill-STC-1000-Temperature-Controller-fig-9

  • Need not to distinguish + or – when wiring the NTC sensor’s cable or the Input power.
    • Wiring the 5 to the live wire and terminal 6 to a heater, or the opposite.
    • Wiring the 7 to the live wire and terminal 8 to a refrigerator, or opposite.
    • The heating and cooling mode will switch automatically.
  • The input voltage must be within the voltage value marked in the diagram ±10% value.
  • Suggest Load Power ≤ (The voltage of Load * Max current of Relay)/Factor
    • The factor for Inductive Load like compressor, heating pump, usually be 5~8;
    • The factor for Resistive Load like Electric heating rod, Electric blanket usually is 1.5 ~ 2;
    • The factor for an Incandescent lamp usually is 15.

Configurations

Code and Function Menu

  • Hold the S button for 3s to enter the menu list.
Code Function Min Max Default Unit
F1 Temperature Setpoint -50.0 99.9 10.0 °C
F2 Temperature Hysteresis / Return Difference 0.3 10.0 0.5 °C
F3 Protection Delay Time for Refrigerator 1 10 3 Min
F4 Temperature Calibration -10.0 10.0 0 Hour
  • F1: Temperature Setpoint
    • It is the room temperature value users wish to keep around.
  • F2: Temperature Hysteresis / Return Difference Value
    • A. Switch to heating mode once found
      • Measured Temperature ≤ Temp Set-point – Return Difference
    • B. Switch to Refrigeration mode once found
      • Measured Temperature ≥ Temp Set-point + Return Difference
      • But the compressor will not start up until the compressor’s delay time is over.
  • F3: Compressor Delay Time: The purpose of this value is to protect the compressor.
  • F4: Temperature Calibration
    • F4 = Real Temperature – Measured Temperature
How to Set Parameters?
  • Step 1: Hold the for 3s to enter the menu list; the display shows the code F1
  • Step 2: Press the or to select the code you want to update;
  • Step 3: Press the to check the current value.
    • Hold the and press or key to change the value;
  • Step 4: Release keys to back to function menu list.
    • Repeat operation from Step 2 / 3 / 4 to adjust other parameters;
  • Step 5: After configuring all values, remember to press the for saving data, and back to normal monitor status, the display shows the room sensor temperature.
    • The modified value will be discarded and back to normal status if without operation in 8 seconds.

When Will is the Load Works/Stops?

Loads Startup Condition Stop Condition
Refrigeration Room Temp ≥ F1 + F2 and

The instant period passed the delay time (F3)

Room Temp ≤ F1
Heating Room Temp ≤ F1 – F2 Room Temp ≥ F1
  • Room Temp: Measured temperature value by the controller’s sensor.
  • F 22: Return difference Hysteresis.
  • The instant period is counts from load stops last moment to the instant time; Means, the time should be later than the compressor’s last stops moment + delay time.

Error & Solution

When an alarm occurred, the buzzer scream “di-di-di,” press any key to stop screaming; but the error code on display will not disappear until all the failures are resolved

Code Reason Troubleshooting
E1 The memory unit broken Press/key to restoring the default data or get factory reset.
EE Sensor error Ensure the sensor was installed firmly or replace a new sensor, display back to normal in 10 seconds once the

problem is fixed.

HH Room temp. > 99.9°C Check the room temperature and all loads, then stop the loads

from working manually if necessary.

  • Video on YouTube

Haswill Electronics

Copyright Haswill-Haswell All Rights Reserved

Haswill-STC-1000-Temperature-Controller-fig-10

Documents / Resources

PDF thumbnailSTC-1000 Temperature Controller
User Manual · STC-1000, STC-1000 Temperature Controller, Temperature Controller, Controller

References

Questions and answers

Helpful product questions tied to this manual. Each item links to the full Q&A page.

Browse all questions about this manual

Questions & Answers

Use this section to ask about setup, compatibility, troubleshooting, or anything missing from this manual.

  1. I have two STC 100 units that are correctly wired up, the temperature shows on both units but I am unable to set a temperature as the Fi button does not work. I hold Set and F1 but the screen does not change from showing F1. So I am unable to set up my controllers. The controllers are to switch cooling fans on and off

    Maurice Watkins asks I have two STC 100 units that are correctly wired up, the temperature shows on both units but I am unable to set a temperature as the Fi button does not work. I hold Set and F1 but the screen does not change from showing F1. So I am unable to set up my controllers. The controllers are to switch cooling fans on and off
    Manuals+ clarified question
    Question

    How do I change the temperature settings on the STC-1000 if the screen stays on F1?

    Answer

    To set the temperature on your Haswill STC-1000, you must use a specific combination of button presses. If you are seeing F1 on the screen, you have successfully entered the menu, but you need to follow these steps to change the value:

    • Step 1: Hold the S (Set) button for 3 seconds until F1 appears.
    • Step 2: While F1 is displayed, press and hold the S button.
    • Step 3: While continuing to hold the S button, press the Up or Down arrow keys to change the temperature value.
    • Step 4: Once you have reached your desired temperature, release all buttons and press the Power button (top right) once to save the settings and return to the main display.

    Note: If you do not press the Power button to save, or if you do not press any buttons for 8 seconds, the unit will exit the menu without saving your changes. The key is that the S button must be held down simultaneously while using the arrows to adjust the numbers.

  2. لقد قمت بمحاولة ضبط اعدادات stc1000 ولكن بعد عدة محاولات تم قفل جميع مفاتيح الجهاز فاصبحت لا تستجيب للضغط

    عيد asks لقد قمت بمحاولة ضبط اعدادات stc1000 ولكن بعد عدة محاولات تم قفل جميع مفاتيح الجهاز فاصبحت لا تستجيب للضغط
    Manuals+ clarified question
    Question

    How do I unlock the keys on the STC-1000 temperature controller if they are unresponsive after adjusting settings?

    Answer

    If the keys on your Haswill STC-1000 have become unresponsive after attempting to adjust settings, you should try to perform a factory reset to restore the device to its default state. According to the manual:

    • To restore factory settings: Under normal status, hold the Up arrow (▲) key and the Down arrow (▼) key at the same time for 5 seconds.

    Additionally, please note the following operational details that might cause confusion:

    • Saving Settings: After adjusting parameters, you must press the Power button (top right) to save the data. If no button is pressed for 8 seconds, the device will discard your changes and return to normal display mode.
    • Menu Access: To enter the menu, you must hold the S button for 3 seconds.
    • Error Codes: If the screen displays E1, it indicates a memory unit failure. In this case, try pressing any key to restore default data or perform the factory reset mentioned above.

Ask a Question