The AFDD (Arc Fault Detection Device) may only be installed, connected and ser-viced by a qualified electrician. Before mounting, the AFDD must be checked for external damage. If any damage or other defect is found, the device must not be mounted. The national regulations, safety regula-tions and installation standards BS 7671 must be observed.

Design and layout of the device

hager-ARM906U-MCB-with-Dangerous-Arc-Detection-FIG-1

  1. Test button
  2. LED status display
  3. Handle
  4. Yellow flag
  5. Mounting metal DIN rail clip

Function

MCB-AFD in 1 module ARMxxxU is a sin-gle device consisting of a miniature circuit breaker (MCB) unit with integrated Arc fault detection (AFD) unit (2 in 1).
The AFDD mitigates the risk of a fire in the final electrical circuits of a fixed installation due to arcing fault currents, which under certain conditions present a fire ignition risk due to dangerous arc Fault, complaint ac-cording to BS 7671 installation Standards.

Correct use
Mounting on DIN rail after TH 35 7.5- 15 according to IEC 60715:2017 / EN 60715:2017

Tools

hager-ARM906U-MCB-with-Dangerous-Arc-Detection-FIG-2

Installation and electricial connection

DANGER !
Electric shock when touching live parts! Electric shock can lead to death! Before working on the unit, disconnect the connecting cables and cover live parts in the vicinity!

Mount device

hager-ARM906U-MCB-with-Dangerous-Arc-Detection-FIG-3

  • Open the din rail clip.
  • Insert the AFDD until it is inked.
  • Put the AFDD on the rail.
  • Press the metal clamp down. The AFDD is fixed on the rail.

Connect device

hager-ARM906U-MCB-with-Dangerous-Arc-Detection-FIG-4

Wiring diagram

hager-ARM906U-MCB-with-Dangerous-Arc-Detection-FIG-5

Disassembly

hager-ARM906U-MCB-with-Dangerous-Arc-Detection-FIG-6

Testing
The test button T is used for testing the device. If the circuit is interruped, operate the handle provided for this purpose.

Test device

ATTENTION !
High voltage tests may damage this product! If the handle is OFF you dont have to disconnect the cable.

Notice

  • The AFDD function must be tested after installation. The supply voltage must be present.
  • The MCB- AFDD must trip within one second. If the device does not trip, it must be replaced by an experienced electrician.
  • Short press the test button only when the yellow flag is present. This ensures that the device has not been triggered by the user.

hager-ARM906U-MCB-with-Dangerous-Arc-Detection-FIG-7

Short press the test button T. The MCB-AFDD tripped, i.e. the cir- cuit must switch off.

Notice
If the AFDD does not trip, check the status of the LED (table 1).

LED status for troubleshooting

hager-ARM906U-MCB-with-Dangerous-Arc-Detection-FIG-8

The handle is in the OFF position. Short press the test button T to open the color code.

LED status display for a standard troubleshooting

Steady GREEN AFDD is ON
LED is OFF AFDD is OFF
Blinking RED/ GREEN + yellow flag absence AFDD

manual tripped

Blinking RED/ GREEN + yellow flag presence Overload or Short-Circuit
Blinking RED/ YELLOW Series arc fault
Blinking RED Parallel arc fault
Steady YELLOW Overvoltage
Blinking YELLOW Internal failure

Notice
In case of an internal Failure, re-place the AFDD and contact the Hager technical support.

Connection to mobilephone
A mobile phone ( iphone, operating with IOS14 or above, or Android, operating with Android 7 or above) is required to use those functions.

Notice
Using the connected functions with your mobile phone requires to activate network functions (Bluetooth, WiFi) and to accept the application terms of use & privacy notice. Only bluetooth 4.2 or above is supported.

  • Install the Hager Pilot mobile application on your mobilephone.
  • Follow further instructions on the mobile application.

LED status for Bluetooth® connection

hager-ARM906U-MCB-with-Dangerous-Arc-Detection-FIG-9

The handle is in the ON position. Press the test button T for 5 seconds to open the color code.

LED status display for Bluetooth® connection

Blinking BLUE Bluetooth enabled
Steady BLUE Bluetooth connected
Blinking RED/BLUE Update mode (only overload and short-circuit protection in this mode)
Blinking BLUE/ YELLOW Trace mode (use for technical Hager support)
Blinking (BLUE/ GREEN) Product localisation request

EU and UKCA Declaration

Hereby, Hager Electro SAS , declares that the AFDD products are in compliance with SI 2017/1206 Radio Equipment Regulations 2017 and with radio emission directive 2014/53/EU

Documents / Resources

hager ARM906U MCB with Dangerous Arc Detection [pdf] Instruction Manual
ARM906U MCB with Dangerous Arc Detection, ARM906U, MCB with Dangerous Arc Detection, Dangerous Arc Detection, Arc Detection, Detection
hager ARM906U MCB with Dangerous Arc Detection [pdf] Instruction Manual
ARM906U MCB with Dangerous Arc Detection, ARM906U, MCB with Dangerous Arc Detection, Dangerous Arc Detection, Arc Detection, MCB

References

Leave a comment

Your email address will not be published. Required fields are marked *