GRANT-logo

GRANT DOC32 REV05 High Level Balanced Flue Boilers Kit

GRANT-DOC32-REV05-High-Level-Balanced-Flue-Boilers-Kit-product

THIS SUPPLEMENT SUPERCEDES THE FITTING THIS SUPPLEMENT SHOULD BE READ IN CONJUNCTION WITH THE INSTINCTIONS IN THE INSTALLATION MANUALTION MANUAL SUPPLIED WITH THE BOILERS SUPPLIED WITH THE BOILER

GENERAL
The High level Balanced flue kit is supplied in 5 sections. For the purpose of clarity in these instructions, the sections have been designated (A),(B),(C),(D),(E) and (F). The flue pipe seals are factory fitted and must be lubricated with the lubricant supplied. The standard flue kit adjusts vertically from the top of the boiler and horizontally from the 90° bend to the end of the terminal. The length of the kit may be increased using extensions on the vertical and/or horizontal up to a total maximum length of 10 meters*. Four extensions are available from Grant UK (see Figure 1 below).

NOTE: The overall flue length assembled should not exceed 10 metres* from the top of the boiler to the end of the terminal. Outer diameter of flue: HLK01 – 150mm, HLK02 – 180mm.
FLUE SECTIONS CANNOT BE CUT.

  • Applies to condensing boilers only.

GRANT-DOC32-REV05-High-Level-Balanced-Flue-Boilers-Kit-fig-1

FITTING INSTRUCTIONS

  • Two types of locking bands are supplied with the kit. One for sections that butt together and one for adjustable sections. The locking bands for the adjustable sections are labelled for easy identification.
  • For short flue, heights section (C) and (D) may be omitted and the 90Obend fitted directly to section (B). The height of the flue kit may be increased using extensions. The charts (see page 3) may be used as a guide when ordering extra extensions.
  • Terminal section (F) slides telescopically over 90O bend section (E), see Figures 3 and 4.
  • Extensions may be added between the 90O bend (E) and the terminal section (F).
    • Note: An adjustable extension cannot be used to connect directly to the terminal section (F).
  • The distance of the boiler flue outlet centreline from the inner wall varies from model to model.
  • For the boiler flue outlet centre line dimension see the boiler installation manual. All dimensions given are ±5mmGRANT-DOC32-REV05-High-Level-Balanced-Flue-Boilers-Kit-fig-2 GRANT-DOC32-REV05-High-Level-Balanced-Flue-Boilers-Kit-fig-3

The following charts can be used as a guide when ordering extensions to increase the horizontal length.

HIGH LEVEL BALANCED FLUE – HORIZONTAL LENGTH
Dimensions show the horizontal length measured from the centre line of the boiler flue outlet to the face of the outside wall with the boiler against the internal wall.  

EXTENSIONS REQUIRED

BOILER MODEL BOILER OUTPUT LENGTH STANDARD KIT 225 450 450+225 950 950 + 225
Rear Side Rear Side Rear Side Rear Side Rear Side Rear Side
 

 

ALL MODELS

 

26kW

Min 300 200(N/A) 525 425(340) 750 650(565) 975 875(790) 1250 1150(1065) 1475 1375(1290)
Max 550 450(365) 775 675(590) 1000 900(815) 1225 1125(1040) 1500 1400(1315) 1725 1625(1540)
SEE NOTE 3                        
26-70kW Min 315 215(150) 540 440(375) 765 665(600) 990 890(825) 1265 1165(1100) 1490 1390(1325)
Max 550 450(385) 775 675(610) 1000 900(835) 1225 1125(1060) 1500 1375(1310) 1725 1625(1560)
SEE NOTES 1 & 2                      
HIGH LEVEL BALANCED FLUE – HORIZONTAL LENGTH
Dimensions show the horizontal length measured from the centre line of the boiler flue outlet to the face of the outside wall with the boiler against the internal wall.  

EXTENSIONS REQUIRED

BOILER MODEL BOILER OUTPUT LENGTH 950 + 450 950 + 450 +225 950 +950 950 + 950 +225 950 + 950 + 450 950 + 950 + 450 + 225
Rear Side Rear Side Rear Side Rear Side Rear Side Rear Side
 

 

ALL MODELS

Up to 26kW Min 1700 1600(1515) 1925 1825(1740) 2200 2100(2015) 2425 2325(2240) 2650 2550(2465) 2875 2775(2690)
Max 1950 1850(1765) 2175 2075(1990) 2450 2350(2265) 2675 2575(2490) 2900 2800(2715) 3125 3025(2940)
SEE NOTE 3                        
 

26-70kW

Min 1715 1615(1550) 1940 1840(1775) 2215 2115(1950) 2440 2340(2275) 2665 2565(2500) 2890 2790(2725)
Max 1950 1850(1785) 2175 2075(2010) 2450 2350(2285) 2675 2575(2510) 2900 2800(2735) 3125 3125(3060)
SEE NOTES 1 & 2                      

FOR HORIZONTAL LENGTHS

  • NOTE1: For Vortex 46/70 models subtract 50mm from overall length (for rear exit flues only)
  • NOTE 2: Vortex 46/70 dimensions in brackets.
  • NOTE 3: Combi 21, 26 and 36 dimensions in brackets.

The following chart can be used as a guide when ordering extensions to increase the vertical height.

HIGH LEVEL BALANCED FLUE – VERTICAL HEIGHT
Dimensions show the vertical height of the flue measured from the top of the boiler water jacket flue outlet

to the centre line of the hole through the wall.

 

EXTENSIONS REQUIRED

BOILER MODEL BOILER OUTPUT HEIGHT FROM TOP OF BOILER STANDARD KIT 225 450 450 + 225 950 950 + 225 950 + 450 950 + 450

+ 225

950 + 950 950 + 950

+ 225

950 + 950

+ 450

950 + 950

450 + 225

                       
 

ALL MODELS

Up to 26kW Min 1025 1250 1475 1700 1975 2200 2425 2650 2925 3150 3375 3600
Max 1425 1650 1875 2100 2375 2600 2825 3050 3325 3550 3775
                         
 

26-70kW

Min 1005 1230 1455 1680 1955 2180 2405 2630 2905 3130 3355 3580
Max 1325 1550 1775 2000 2275 2500 2725 2950 3225 3450 3675
                         

45ºelbows are also available. Each elbow has an equivalent length of 1 metre, which must be deducted from the maximum length of 10 metres. Only six elbows should be used per system. The elbows may be connected together or used individually to connect to extra extensions to form offsets as shown. The 90º elbow may also be connected to a 45º elbow (and extension) as shown.

GRANT-DOC32-REV05-High-Level-Balanced-Flue-Boilers-Kit-fig-4 GRANT-DOC32-REV05-High-Level-Balanced-Flue-Boilers-Kit-fig-5 GRANT-DOC32-REV05-High-Level-Balanced-Flue-Boilers-Kit-fig-6 GRANT-DOC32-REV05-High-Level-Balanced-Flue-Boilers-Kit-fig-7

FITTING THE FLUE (Standard kit)
Unpack the flue kit. Remove the boiler top panel or panels, depending on model being installed. Decide upon the position of the boiler and determine exactly where the flue will pass through the wall. GRANT-DOC32-REV05-High-Level-Balanced-Flue-Boilers-Kit-fig-8

 

 

Model

Dimensions (mm)
A

Dia

B C min D min D max E
 

Vortex Pro 15/26

 

175

 

115

 

1215

 

1715

 

2115

 

N/A

Vortex Eco 15/21 & 21/26 175 115 1215 1715 2115 N/A
Vortex Pro 26/46 200 115 1280 1700 2020 N/A
Vortex Eco 26/35 200 115 1280 1700 2020 N/A
Vortex Pro 46/70 200 112 1595 2015 2335 N/A
Vortex Pro Combi 21e &26e 175 115 1215 1715 2115 N/A
Vortex Pro Combi 36e 200 105 1280 1700 2020 N/A
Vortex Eco Wall Hung 16/21 175 112 H+1207 H+1707 H+2107 220
H = height (mm) from the floor to the underside of boiler casing

Check that there are no obstructions in the way and that the terminal position complies with the dimensions given in figure 14.

  • HLK01 50/90, cut clearance holes of 175mm diameter through the wall.
  • HLK02 90/200, cut clearance holes of 200mm diameter through the wall.

Note: When the boiler is installed with the back panel against the wall, the throat of the bend could enter the inner wall opening. Cut away the underside of the hole in the inner wall to accept the throat of the bend. Take the 90O bend (E) and fit the black seal to the swage in the outer flue pipe. Ensure the factory-fitted inner seal is in position. Lubricate the inner and outer seal using the lubricant supplied.

Note: Two black seals are supplied with the kit. The thicker black seal should be used on a standard kit. If an extension is fitted between the elbow and the terminal, the thinner black seal should be used between the extension and the terminal. Discard the thicker black seal. Measure the distance from the boiler flue outlet centre line and the outer surface of the outer wall. Take the terminal section (F) and 90° bend assembly (E) and push fit until the required length is achieved.

Note: The min/max marks on the terminal. It is easier to push these sections together using a twisting motion. Ensure that lubricant is applied to both sides of the black lipped seal. Do not dry fit flue parts with seals fitted as removal will prove very difficult.
When using additional extensions on the horizontal section use the locking band supplied with the extension to connect to the horizontal part of the flue elbow assembly. Place the inner wall dress plate over the end of the terminal assembly and slide it down to the throat of the bend. From inside the building, place the terminal assembly (E and F) through the wall. Ensure that the flue terminal protrudes the correct distance from the surface of the outer wall. The air inlet slots in the terminal must not be obstructed. The terminal is marked to show the minimum and maximum projection allowable (see figure 12).

Grant Vortex Condensing Models only: Clamp the boiler connector (A) to the neoprene gasket fitted to the boiler flue outlet using the stainless steel bolt supplied with the boiler.GRANT-DOC32-REV05-High-Level-Balanced-Flue-Boilers-Kit-fig-9

 

Ref

 

Location of outlet

Minimum distance (mm)
Pressure jet Condensing
A Directly below an opening, air brick opening, opening window, etc. 600 1,000 **
B Horizontally to an opening, air brick opening, opening window, etc. 600 1,000 **
C Below a gutter, eaves or balcony with protection 75 * 1,000 **
D Below a gutter, eaves or balcony without protection 600 1,000 **
E From vertical sanitary pipework 300
F From an internal or external corner 300
G Above ground or balcony level 300
H From a surface or boundary facing the terminal 600 2,500 **
J From a terminal facing the terminal 1,200
K Vertically from a terminal on the same wall 1,500
L Horizontally from a terminal on the same wall 750
M Above the highest point of an intersection with the roof 600
N From a vertical structure to the side of the terminal 750
O Above a vertical structure less than 750 mm from the side of the terminal 600
P From a ridge terminal to a vertical structure on the roof 1,500
Q Above or to the side of any opening on a flat or sloping roof 300
R Below any opening on a sloping roof 1,000
S From oil storage tank (Class 1) 1,800 ***
  • A heat shield at least 750 mm wide must be fitted to provide protection of combustible material.
  • Clearances required by BS 5410-1:2019 to alleviate the effect of plume nuisance. If a risk assessment shows that there will be no impact from plumbing, then the ‘pressure jet’ figure could apply – seek confirmation from Local Authority Building Control.
  • Seek guidance from OFTEC Book 3 (Oil Storage and Supply).

NOTES

  1. Appliances burning class D fuel have additional restrictions. Refer to BS 5410-1:2019.
  2. Vertical structure in N, O and P includes tank or lift rooms, parapets, dormers, etc.
  3. Terminating positions A to L are only permitted for appliances that have been approved for low level flue discharge when tested in accordance with BS EN 303-1, OFS A100 or OFS A101.
  4. Terminating positions should be at least 1.8 metres from an oil storage tank (Class 1) unless a wall with at least 30 minutes fire resistance and extending 300 mm higher and wider than the tank is provided between the tank and the terminating position.
  5. Where a flue is terminated less than 600 mm away from a projection above it, and the projection consists of plastics or has a combustible or painted surface, then a heat shield of at least 750 mm wide should be fitted to protect these surfaces.
  6. If the lowest part of the terminal is less than 2 metres above the ground, balcony, flat roof or other place to which any person has access, the terminal should be protected by a guard.
  7. Notwithstanding the dimensions given above, a terminal should not be sited closer than 300 mm to combustible material. In the case of a thatched roof, double this separation distance should be provided. It is also advisable to treat the thatch with a fire retardant material and close wire in the immediate vicinity of the flue.
  8. A flue or chimney should not pass through the roof within the shaded area delineated by dimensions Q and R.
  9. Where protection is provided for plastics components, such as guttering, this should be to the standard specified by the manufacturer of the plastics components.
  10. Terminals must not be sited under carports.
  11. Terminals at low levels (terminals under 2.1 metres) have more restrictive recommendations and should not be positioned near public footways, frequently used access routes, car parking spaces less than 2.5 metres from the terminal or patios (hard surface area).

Further guidance can be obtained from BS 5410-1:2019, OFTEC Book 4 (Installation), and Approved Document J. Grant UK flue products are fully compliant with the CE (European Community) standards, having undergone rigorous product testing. Locate the boiler connector (A) centrally into the gasket on the top of the boiler. Tighten the bolt to fix it n place to the flue outlet. (see figure 16). Ensure the red seal in the swage in the boiler connector is fitted. (see Figure 17). Take the starter section (B) of the vertical flue pipe and check that the factory-fitted seal is in position as shown. (see Figure 15) in the swaged recess in the inner flue pipe. Lubricate the lip of the red seal in the boiler connector. Push fit the starter section (B) of the flue pipe into the boiler connector. Ensure that the test point screw is orientated for easy access for flue gas analysis and combustion testing. Remove the test point screw. Connect the flexible air inlet tube to the air inlet spigot on the first section and secure it with the hose clamp supplied.GRANT-DOC32-REV05-High-Level-Balanced-Flue-Boilers-Kit-fig-12

Refit the boiler casing top panel or panels. Ensure the red seal is fitted into the swage in the inner pipe of the starter section (B). Lubricate the seal. Take the lower section of the vertical flue pipe (C) and push fit it into the starter section (B) using a twisting motion. Fit a fixed section locking band to join the outer pipes. Ensure the red seal is fitted into the swage in the inner pipe of the lower section (C). Lubricate the seal. Take the upper section (D) of the vertical flue pipe and push fit it into the lower section (C), using a twisting motion, ensuring the outer pipes overlap by a minimum of 35mm.GRANT-DOC32-REV05-High-Level-Balanced-Flue-Boilers-Kit-fig-10

Place both an adjustable and fixed locking bands over the fitted sections of the flue and rest on the top of the boiler. Holding section(C) of flue in position, extend the vertical flue pipe (D) to the required length using a twisting motion. Locate the top end of the pipe into the 90O elbow ensuring that the inner pipe engages the red seal in the top of the vertical section(C). Take a fixed section flue pipe locking band and clamp the flue assembly together. Note the flue elbow locking band locates into the recess on the outer pipe and elbow assembly. Drill 3 x 2.5mm dia. holes through the outer flue pipes of the adjustable length and fix into position using the 3 self tapping screws supplied. Fit the clamping band marked with a label for telescopic sections to the telescopic joint on the outer pipe (see Figure 18). Ensure that an airtight seal is made.GRANT-DOC32-REV05-High-Level-Balanced-Flue-Boilers-Kit-fig-11

Ensure that the terminal projects through the wall, as shown (see Figure 12). Fit the inner and outer wall dress plate using a suitable mastic sealant.

Grant Engineering (UK) Limited
Frankland road, Blagrove, Swindon, Wiltshire SN5 8YG Telephone: (01380) 736920 Fax: (01380) 736991 email: info@grantuk.com website: www.grantuk.com

This manual is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests of continued product improvement. All goods sold are subject to our official Conditions of Sale, a copy of which may be obtained on application. © Grant Engineering (UK) Limited 2008. No part of this manual may be reproduced by any means without prior written consent.

FAQs

Q: Can the flue sections be cut?
A: Flue sections cannot be cut. Ensure proper measurements and use extensions if needed.

Q: What is the maximum total length of the flue kit?
A: The overall flue length assembled should not exceed 10 meters from the top of the boiler to the end of the terminal.

Documents / Resources

GRANT DOC32 REV05 High Level Balanced Flue Boilers Kit [pdf] Installation Guide
DOC32 REV05, DOC32 REV05 High Level Balanced Flue Boilers Kit, High Level Balanced Flue Boilers Kit, Balanced Flue Boilers Kit, Flue Boilers Kit, Boilers Kit

References

Leave a comment

Your email address will not be published. Required fields are marked *