GRANT Aerona 3 R32 Smart Controller Kit

Specifications

  • Product Name: Grant Aerona Smart Heat Pump System Controller
  • Model: Aerona
  • Country of Manufacture: United Kingdom
  • Serial Number Format: Ten-digit numerical code (e.g., 1006986828)

Product Information

The Grant Aerona Smart Heat Pump System Controller is designed for use with Grant Aerona air source heat pumps. It features a touchscreen display for easy operation and control of the heating system.

General Information

Installers should follow these instructions to correctly installand commission the Grant Aerona Smart Controller. Ensure the unit is not connected to mains power during installation.

Technical Data

The controller includes a wiring centre and a touchscreen display for user interaction.

Installation

Install the touchscreen display, wiring centre, temperature sensors, pumps, mixing valves, relays, smart flow sensor, room thermostat, and Wi-Fi Hub as per the provided instructions.

System Hydraulics
Connect the hydraulic components according to the installation pack summary and respective pack connections (Pack P, Pack Q, Pack R).

Electrical Connections
Connect the wiring centre, components, and ensure power supply reliability. Follow the layout for electrical connections based on the pack type.

System Configuration with Touchscreen Display
Configure the system using the touchscreen display, set up weather compensation, circuit control settings, and common settings.

Touchscreen Display Operation and Settings
Operate the Smart Controller through the touchscreen display, following the provided instructions for system control.

FAQs

Q: Where can I find the serial number of the Grant Aerona Smart Controller?
A: The serial number is a ten-digit numerical code located on a label attached to the wiring centre.

Q: Can the Grant Aerona Smart Controller be installed in wet or steamy conditions?
A: No, the controller must not be installed in steamy conditions or exposed to water, such as in a bath or shower room.

“`

Grant Aerona
Smart Heat Pump System Controller Installation & Operation Instructions
UK | DOC 0203 | Rev 1.0 | February 2024

IMPORTANT NOTE FOR INSTALLERS


These instructions are intended to guide installers on the installation and commissioning of the Grant Aerona Smart Controller intended for use with Grant Aerona air source heat pumps. After installing the unit, leave these instructions with the user.

SPECIAL TEXT FORMATS
The following special text formats are used in these instructions for the purposes listed below:


! WARNING !
Warning of possible human injury as a consequence of not following this instruction.

! CAUTION !
Electric device under voltage!
Before any action related to the power supply (cables connection, device installation etc.) Check to ensure the controller is not connected to the mains power. Installation should be done by a person with appropriate electrical qualifications. Improper cable connection could result in controller damage. The controller must not be installed in steamy conditions or exposed to water, such as bath or shower room

! CAUTION !
Caution concerning likely damage to equipment or tools as a consequence of not following this instruction.

! NOTE !
Used for emphasis or information not directly concerned with the surrounding text but of importance to the reader.

PRODUCT CODES AND SERIAL NUMBERS COVERED
The serial numbers used on Grant Aerona Smart Controller consist of a ten digit numerical code.


For example:
1006986828
This serial number can be found on a label attached to the wiring centre.

GRANT ENGINEERING (UK) LIMITED


Frankland Road, Blagrove Industrial Estate, Swindon, SN5 8YU Tel: +44 (0)1380 736920 Fax: +44 (0)1380 736991 Email: info@grantuk.com www.grantuk.com
This manual is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in the interests of continued product improvement. However, no responsibility of any kind for any injury, death, loss, damage or delay however caused resulting from the use of this manual can be accepted by Grant Engineering (UK) Limited, the author or others involved in its publication. All good sold are subject to our official Conditions of Sale, a copy of which may be obtained on application. © Grant Engineering (UK) Limited. No part of this manual may be reproduced by any means without prior written consent.

Contents

1 INTRODUCTION

4

1.1 General

4

1.2 Safety information

4

1.3 Information about documentation

4

1.4 Storage of documentation

4

1.5 Conditions of storage and

4

transport

1.6 Product contents

4

1.7 Additional components

4

1.8 Customer Support Hub

4

2 TECHNICAL DATA

5

2.1 Wiring centre

5

2.2 Touchscreen display

6

3 INSTALLATION

7

3.1 General

7

3.2 Regulations and Standards

7

3.3 Touchscreen display

7

3.4 Wiring centre

8

3.5 Temperature sensors

8

3.6 Connecting pumps

9

3.7 Connecting 3-port mixing valves

9

3.8 Connecting relays

9

3.9 Smart flow sensor

9

3.10 Room thermostat connection

9

3.11 Connecting the Wi-fi Hub

9

4 SYSTEM HYDRAULICS

10

4.1 Hydraulic Connections

10

4.2 Installation Pack Summary

10

4.3 Hydraulic controls

10

4.4 Hydraulic connections – Pack P

11

4.5 Hydraulic connections – Pack Q

12

4.6 Hydraulic connections – Pack R

13

5 ELECTRICAL CONNECTIONS

14

5.1 Connecting the wiring centre

14

5.2 Component connections

14

5.3 Power supply failure

14

5.4 Wiring centre LAYOUT

15

5.5 Electrical connections – Pack P

16

5.6 Electrical connections – Pack Q

17

5.7 Electrical connections – Pack R

18

6 SYSTEM CONFIGURATION

19

WITH TOUCHSCREEN DISPLAY

6.1 First switch-on

19

6.2 System configuration Creator

19

6.3 Weather compensation

21

6.4 Circuit control settings

22

6.5 Common Settings

22

7 TOUCHSCREEN DISPLAY

23

OPERATION AND SETTINGS

7.1 Touchscreen display

23

7.2 Smart Controller operation

24

7.3 Circuit settings

24

7.4 Legionella protection

26

7.5 Time schedules

26

7.6 Heat pump schematic

27

7.7 System schematic

27

7.8 Circuit control

28

7.9 User settings menu

29

7.10 Stored system settings

29

8 SERVICE SETTINGS – INSTALLER 30

8.1 Service Settings

31

9 HEAT PUMP PARAMETERS

33

INSTALLER

Contents

10 WI-FI HUB

35

10.1 General

35

10.2 Connection to wiring centre

35

10.3 Connection with internet

35

10.4 Econet24

36

11 SERVICING

37

11.1 Component replacement

37

11.2 Accessories & spare parts

37

12 EC DECLARATIONS

38

OF CONFORMITY

13 HEALTH AND SAFETY

39

INFORMATION

14 DISPOSAL AND RECYCLING

39

15 GUARANTEE

40

APPENDIX A- WIRED THERMOSTAT 42

A.1 General

42

A.2 Installation

42

A.3 Thermostat panel

42

A.4 Pairing

43

A.5 Changing setpoint temperature

43

A.6 Hotel mode

43

A.7 Error codes

43

APPENDIX B – WIRELESS

44

THERMOSTAT AND RECEIVER

B.1 General

44

B.2 Installing Wireless receiver

44

B.3 Wireless thermostat

44

B.4 Memory reset of the wireless receiver 45

B.5 Multiple Thermostat support

45

B.6 Thermostat Panel

45

B.7 Hotel Mode

45

B.8 Alarms

45

APPENDIX C – 3-PORT MIXER VALVE 46

C.1 General

46

C.2 Clockwise rotation

46

C.3 ANTI-Clockwise rotation

47

APPENDIX D – SMART

48

IMMERSION RELAY

D.1 General

48

D.2 Wiring

48

D.3 Smart Immersion functionality

48

APPENDIX E – SMART

49

FLOW SENSOR

E.1 General

49

E.2 Installation

49

E.3 Electrical

49

E.4 Sensor configuration

49

APPENDIX F – HOW TO VIDEOS

50

F.1 Icons Overview

50

F.2 Setting up the controller

50

F.3 Setting the Circuit temperature

50

F.4 Setting the hot water temperature

50

F.5 Setting the heating schedule

50

F.6 Setting the Hot water schedule

50

F.7 Adjusting the heating curve

50

F.8 Setting up Legionella protection

50

NOTES

51

Page 3

1 Introduction

1.1 GENERAL
The Grant Aerona Smart Controller is intended for controlling a central heating and domestic hot water with a Grant Aerona heat pump. The controller may be used in domestic and light commercial applications.
1.2 SAFETY INFORMATION
Requirements concerning safety are listed in particular Sections of this instruction manual. Apart from these it is necessary to fulfil the following requirements:
· The controller should be installed by qualified installer only and in accordance with current Standards and Regulations.
· Before starting the installation, repairs or maintenance and during the execution of any connection works, it is necessary to switch off the mains power supply and make sure that no terminals and electrical wires are live.
· Even after turning off wiring centre terminals it can still be under a dangerous level of voltage.
· The controller can be utilised only in accordance with its intended use.
· Additional measures should be used in order to protect the central heating and DHW system against the results of controller failure or software errors. Particularly control measures which reduce DHW temperature in order to protect users against burns.
· Parameters should be set in accordance to the heating system design.
· The controller is not an intrinsically safe device. It means that in case of failure it can be a source of sparks or high temperature which can cause fire or explosion.
· Modification of the programmed parameters should be made only by the installer.
· Use only in central heating system made in accordance with currently valid regulations.
· Electrical system including the controller should be 3-wired and protected with fuse selected in accordance with used loads.
· The controller components cannot be used with damaged housing.
· Never make any modifications in controller components structure.
· The controller consists of two key elements: Touchscreen display and wiring centre. Any replaced components must be compatible.
· Keep children away from the controller.
1.3 INFORMATION ABOUT DOCUMENTATION
This manual is divided into two parts: for user and installer. Both parts contain important information significant for safety issues, hence the user should read both parts of the manual.
Grant UK are not responsible for any damages caused by failure to follow these instructions.
1.4 STORAGE OF DOCUMENTATION
This installation and operation manual, as well as any other applicable documentation, should be stored in a safe place for future reference.

1.6 PRODUCT CONTENTS
This Grant Aerona Smart Controller is supplied for assembly on installation and is carefully packed with packing materials.

Table 1-1: Product contents

Quantity Item

1

Touchscreen display

1

Touchscreen display mounting plate

1

Touchscreen display cable (1m)

1

Controller wiring centre

1

Outdoor weather sensor

3

Water temperature sensors (2 x 2m, 1 x 4m)

1

Wi-Fi Hub Kit

– Wi-Fi Module

– Power Supply

– ecoLINK Cable

1

Smart Flow sensor kit (including 1m cable)

1

Accessory & Fixing Pack

– 6 x Wall plugs and screws – 6 x Cable clamps

– 12 x Cable clamp screws – 2 x 10 pin pluggable terminal blocks – 2 x 14 pin pluggable terminal blocks

– 2 x 4 pin pluggable terminal blocks – 2 x 2 pin pluggable terminal blocks

1

Heat Pump connection kit*

– 2 x Flexible Hoses & 90° Elbow

– 2 x Isolation Valves

* The Heat Pump connection kit will need to match the Heat pump model it is being installed with.

1.7 ADDITIONAL COMPONENTS
Grant UK offer a number of additional components compatible with the Aerona Smart Controller for consideration.

Table 1-2: Additional components

Part Code

Item

HPIDSMARTWRTR Wireless thermostat (with receiver)

HPIDSMARTWRT

Wireless thermostat (no receiver)

HPIDSMARTRECEIVER Wireless thermostat receiver

HPIDSMARTHRT

Wired thermostat

HPIDSMARTSEN2

Water temperature sensor with 2m cable

HPIDSMARTSEN4

Water temperature sensor with 4m cable

HPIDSMARTIMM

Immersion Heater Relay*

*supplied as part of Aerona Smart Controller installation packs

1.8 CUSTOMER SUPPORT HUB
Grant UK provides an online support centre for Heating Professionals and Homeowners to access post-installation care, advice and maintenance support for Grant products. Follow the QR codes below to access your relevant Customer Support Centre.

1.5 CONDITIONS OF STORAGE AND TRANSPORT
The controller cannot be exposed to direct effects of weather, i.e., rain and sunlight. During transport, the device cannot be exposed to vibrations greater than typical for normal road transport.

Page 4

Homeowner

Professional
Section 1: Introduction

2 Technical Data

2.1 WIRING CENTRE

Table 2-1: Technical Data Grant Aerona Smart Controller – Wiring Centre Power supply Controller current consumption

230V AC, 50Hz 0.4 A3

Maximum rate current Protection class Ambient Temperature Storage temperature

6 (6) A IP 204 0 to 50o C 0 to 65o C

Relative humidity Outdoor Weather Sensor working range Measurement accuracy: Water & Outdoor Weather Sensors

5 to 85% without water vapour condensation -40 to 110o C ±2o C

Wiring centre dimensions

234mm x 225mm x 64mm

Standards

EN 60730-2-9. EN 60730-1

Software class

A, according to EN 60730-1

Protection class

IP 20

Installation method

Wall mounted

3 Current consumed only by the controller. Overall current consumption depends on number of devices 4 After installing all cable clamps.

234 mm

225 mm 225 mm

I 0

Figure 2-1: Wiring centre dimensions

64 mm

Section 1: Introduction

Page 5

2.2 TOUCHSCREEN DISPLAY
Table 2-2: Technical Data – Touchscreen Display Grant Aerona Smart Controller – Touchscreen Display Power supply Touchscreen display current consumption Display Protection class Ambient temperature Relative humidity Touchscreen display dimensions Standards Software class Installation method

12V DC directly the Wiring centre 0.15A Touch screen, graphical 480px x 272px IP 20 0 to 50o C 0 to 65o C 144mm x 97mm x 20mm EN 60730-2-9, EN 60730-1 A, according to EN 60730-1 Wall mounted
144 mm

25,4°C

+

32 oC ,6 TEMPERATURE

Figure 2-2: Touchscreen display dimensions

98 mm

Page 6

Section 2: Technical Data

3 Installation

IMMEDIATE CONSIDERATION SHOULD BE GIVEN TO HYDRAULIC (REFER TO SECTION 4) AND ELECTRICAL (REFER TO SECTION 5) CONNECTIONS PRIOR TO
INSTALLATION FOR WIRING CENTRE POSITIONING.

3.1 GENERAL
This Section gives details of the installation process for the Grant Aerona Smart controller. These installation instructions must be read in conjunction with the Grant Aerona air source heat pump installation instructions (provided with the unit). Before starting to install the Grant Aerona Smart controller please read the Health and Safety information given in Section 13 of these installation instructions. Similarly, before staring any installation work on the Grant Aerona air source heat pump please read the Health and Safety information given in Section 14 of the Aerona³ installation instructions.
3.2 REGULATIONS AND STANDARDS
The installation of the Grant Aerona Smart controller and a Grant Aerona air source heat pump must be in accordance with the following recommendations, as applicable: · Building Regulations for England and Wales, and Building
Standards for Scotland · Local Bylaws (check with the Local Authority for the area) · Water Supply (Water Fittings) Regulations 1999 · MCS Installer Standards · MIS3005-D The heat pump Standard (Design) · MIS3005-I The heat pump Standard (Installation) · MCS020 MCS Planning Standard
The installation should also be in accordance with the latest edition of the following standards and Codes of Practice: · BS7671 and amendments · BS EN 12831

! NOTE !
When selecting the cable connecting the touchscreen display with the wiring centre, you must use a cable with single wire resistance lower than 8. Total cable length must not exceed 100m.
3.3.1 FITTING THE TOUCHSCREEN DISPLAY The touchscreen display installation should be done according to the following guidelines: 1. Detach the mounting plate from the back of the touchscreen
display. The plate is attached to the touchscreen with latches. Use a flat screwdriver to detach the plate. (See Figure 3-2) 2. Using a sharp tool cut out holes in four places of the cover for the screw terminals. (See Figure 3-3)
1
2
Figure 3-2: touchscreen display & back plate
3. Connect the cable to the screw terminal as described on the plate. Refer to Figure 3-4 The cable can be recessed in the wall or it can run over its surface – In this case the cable should be additionally placed in the cable channel.

3.3 TOUCHSCREEN DISPLAY
The touchscreen display is designed to be wall mounted. It must not be installed in steamy conditions such as a bath or shower room. The touchscreen display should be mounted at a height allowing comforTable operation, typically 1.5m above the floor. Refer to Figure 3.1.

1 3

1.5m

0,2m
Figure 3-3: Mounting plate cutaway
4. Drill holes in the wall and use screws to fix the mounting plate in the chosen place of the wall, maintaining its proper position (Refer to Figure 3-4)
5. Attach the panel to the mounting plate using latches.w

Figure 3-1: Touchscreen positioning To reduce measurement disturbances avoid locations exposed to strong sunlight, with poor air circulation, near heating equipment, and directly at the door and windows, typically 200mm from the edge of the door.
Section 3: Installation

! NOTE !
The touchscreen display connection cable can not be ducted with other electrical cables that are part of the building mains and should not be routed near devices that emit a strong Electromagnetic field
Page 7

117

1

UP

5-12V GND
5 D+ D-
4 6

65

3

1

2

4 23

Figure 3-6: Circuit temperature sensor fitting

190mm 185mm

Figure 3-4: Mounting plate wiring

Table 3-1: Touchscreen display & mounting plate

No

Description

1

Touchscreen display mounting plate

2

Touchscreen display

3

Mounting plate cut-away

4

Screw terminal

5

Terminal connection guide

6

Cable Channel

3.4 WIRING CENTRE
The wiring centre should be located in a suitable and neutral position to avoid damage and tampering.

3.4.1 FITTING THE WIRING CENTRE
The wiring centre should be mounted on to a flat surface, e.g., wall. 1. Drill and fit 2 mounting points for the mounting holes provided
on the upper Section of the back of the wiring centre. (See Figure 3-5).

2. Slot the wiring centre in place ensuring it is fully down.
3. Remove wiring centre lower front cover (via 2 screws) and mark position of lower 2 holes. (See Figure 3-5)

4. Remove wiring centre, drill and fit wall plugs
5. Set wiring centre back in position and fix controller with lower holes to secure in final position.
6. Ensure the wiring centre is securely in place and replace lower controller case front.

35mm

180mm

3mm

Table 3-2: Temperature Sensor installation

No

Description

1

Flow Pipe

2

Zip tie

3

Thermal insulation

4

Water Temperature sensor

3.5 TEMPERATURE SENSORS
The Smart Controller should be used only with the Grant supplied Outdoor and Water temperature sensors. At least one Water temperature sensor is necessary to activate the controller.

3.5.1 WATER TEMPERATURE SENSORS
The water temperature sensors should be installed in an area of the system relevant to their function. For heating circuits the most suitable location would be after controlled valves on the circuit flow to give the most accurate reading for the circuit.
Insulate the sensors affixed to the external surface of the pipe using thermal insulation covering the sensor together with the pipe. (Refer to Figure 3-6)

3.5.1 OUTDOOR WEATHER SENSOR
The Outdoor weather sensor is the only external sensor to be used with the Grant Aerona Smart Controller. It should:
· Be fixed to a coldest wall in the building, usually a north wall under the roof.
· Not be exposed to direct solar radiation or rain.
· Be fixed on a minimum height of 2m above the ground and in a distance of at least 1.5m from windows, chimneys and other heat sources which could interrupt the temperature measurement.
· Use a connecting cable with a cross section of at least 0.5 mm2 and length of 25m. Polarity of wires is not important.

To fasten the external sensor to the wall.
1. Remove the front of the sensor housing. (Refer to Figure 3-7).
2. Position the rear part of the housing against the wall, mark and drill fixing holes.
3. Insert the supplied wall plugs, place the housing back into position and secure in place with the screws.

Screw holes

Screw 2 pcs

142 mm

3mm

Figure 3-5: Wiring centre fixing centres

! NOTE !
Ensure to leave adequate access to the ON/OFF switch if the left side of the wiring centre is close to a side wall.
Page 8

Cable 2×0.05mm² Max. Length 25m Ø cable 3-6.5mm
Figure 3-7: Outdoor weather sensor
Section 3: Installation

3.5.3 TEMPERATURE SENSOR RESISTANCE
The accuracy of the temperature sensors can be checked by measuring their resistance at a given temperature. In case of significant differences between measured resistance value and values in Table below, the sensor should be replaced. (See Table 3-3)

Table 3-3: Temperature/Resistance chart

Water and Outdoor Weather sensors (10k NTC)

Temp (oC)

Nom ()

-30

175200

-20

96358

-10

55046

0

32554

10

19872

20

12488

30

8059

40

5330

50

3605

60

2490

70

1753

80

1256

90

915.4

100

677,3

110

508,30

120

386,60

3.6 CONNECTING PUMPS
Electrical connections from the circuit pumps to the controller should be according to the electrical schematics. See Section 4.

3.10.1 ROOM THERMOSTAT WIRING
The Grant Aerona Smart controller can support multiple wired room thermostats (including the touchscreen display). You will need to ensure the correct polarity of the connections are respected when wiring the room thermostats/touchscreen display in parallel to the wiring centre. (Refer to Figure 3-8).
With the connections made you will need to pair and assign the room thermostats with their own address.
See Appendix A for installation and operation guidance.

! CAUTION !

Maximum length of wires should not exceed 30m. This length may be longer if the wires used have cross-Section exceeding 0.5 mm2.

Wireless Receiver

Wiring Centre G1 Socket

Wired Thermostat

+12V GND D+ D-

P LED D- D+

GND +12V

DD+ GND +12V

+12V GND D+
D-

3.7 CONNECTING 3-PORT MIXING VALVES
The Grant Aerona Smart Controller should only be used with valve actuators equipped with limit switches and the 3-Port mixing valves can only be fitted as part of an adjustable circuit. Refer to Appendix C for further details on 3-Port mixing valves.
A water temperature sensor will also need to be installed after the mixing valve to measure the mixed water flow temperature for the circuit.
3.8 CONNECTING RELAYS
A relay for supplementary heating from a Buffer, Volumiser, Low Loss header and/or DHW cylinder can be used in conjunction with the Grant Aerona Smart controller.
They are to be connected via H1 (Buffer, Volumiser or Low Loss header) or H2 (DHW Cylinder) as the terminals are preset to the functions within the Smart Controller software.
Grant UK supply the Grant Smart Immersion relay as part of our installation packs. See Appendix D for further guidance on wiring specifics.
3.9 SMART FLOW SENSOR
The Grant smart flow sensor monitors the return flow rate to the heat pump. Refer to Appendix E for installation and configuration requirements.
3.10 ROOM THERMOSTAT CONNECTION
For optimum operation of the Grant Aerona Smart Controller each circuit within the system should have an individual thermostat assigned to it.
The room thermostats connect to the wiring centre and can utilise the weather compensation function to automatically adjust the flow temperature within the circuit to provide a consistent room temperature. The required temperature is set on the room thermostat of the circuit concerned.
It is recommended to use the touchscreen as a room thermostat.

Touchscreen display
Figure 3-8: Wired and Wireless wiring schematic
3.10.2 WIRELESS ROOM THERMOSTAT Connecting a wireless room thermostat requires connecting the wireless receiver to the G1 socket in the same fashion as the wired thermostat and pairing between the wireless receiver and thermostat. The wireless receiver can support up to 3 wireless thermostats. See Appendix B for Installation and operation guidance.
! NOTE !
Close attention must be paid to the 4 connections (+12V, GND, D+ and D-). Ensure they match to corresponding wires from touchscreen display. (+12V is also referenced as VCC).
3.11 CONNECTING THE WI-FI HUB
The Wi-Fi hub should be connected between the USB socket and the G3 socket of the wiring centre using the ecoLINK cable supplied. Refer to Section 10 for installation and user guidance.

Section 3: Installation

Page 9

4 System Hydraulics

4.1 HYDRAULIC CONNECTIONS
The Grant Aerona Smart controller can be utilised in a number of ways via the Smart controller configuration creator and settings configuration. The enclosed hydraulic schematics demonstrate typical setups associated with the Grant renewables price list installation packs available from the Grant UK website. Refer to the Grant Aerona Heat pump manual provided for further information regarding sealed system & DHW considerations. Refer to Section 5.4, 5.5 and 5.6 for corresponding electrical connection drawings.
4.2 INSTALLATION PACK SUMMARY
4.2.1 INSTALLATION PACK P
Installation Pack P – Direct S-Plan with non pre-plumbed cylinder.
Table 4-1: Installation Pack P
Order code: HPIDR32PACKP Flexi_Foot Kit
Mag One Filter
18L System Kit
32A Isolator
Grant Smart Immersion Relay

4.3 HYDRAULIC CONTROLS
4.3.1 THERMOSTATIC PUMP BLOCKADE Thermostatic pump blockade is a hydraulic control feature within a heating circuits setting that enables the Grant Aerona Smart controller to either switch a circuit pump/valve OFF (Pump blockade ON) or keep the circuit active (Pump blockade OFF) based on the status of the thermostat monitoring the circuit.
Refer to Section 7.8 for further details on how to activate and use this function.
4.3.2 CIRCUIT STOP FROM PRESET TEMP ‘Circuit stop from Preset temp’ is a hydraulic control feature within a mixing heating circuits setting that enables the Grant Aerona Smart controller to either switch a circuit pump/valve OFF (Circuit stop on Preset temp ON) or keep the circuit active (Circuit stop on Preset temp OFF) based on the status of the water temperature sensor on the flow in the circuit. Refer to Section 7.8 for further details on how to activate and use this function.

Refer to Section 4.4 for Hydraulic schematic.

4.2.2 INSTALLATION PACK Q Installation Pack Q – Open Loop Direct using 3-Port Diverter and
Mixing Valve with non pre-plumbed cylinder. Table 4-2: Installation Pack Q Order code: HPIDR32PACKQ Flexi-Foot Kit Mag One Filter 18L System Kit 32A Isolator Grant Smart Immersion Relay 28mm 3 Port Diverter Valve 22mm 3 Port Mixing Valve
Refer to Section 4.5 for Hydraulic schematic.

4.2.3 INSTALLATION PACK R Installation Pack R – Open Loop Direct using 3 Port Diverter
Valve with non pre-plumbed cylinder. Table 4-3: Installation Pack R Order code: HPIDR32PACKR Flexi-Foot Kit Mag One Filter 18L System Kit 32A Isolator Grant Smart Immersion relay 28mm 3 Port Diverter Valve
Refer to Section 4-6 for Hydraulic schematic.

Page 10

Section 4: System Hydraulics

4.4 HYDRAULIC CONNECTIONS – PACK P
Grant UK Drawing Number: HPCS-P001S

Section 4: System Hydraulics

Item
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29

Description
Aerona³ ASHP Flexible hose¹ Isolation valve¹ Grant External Volumiser² Anti-Vibration Mounts² Flow sensor¹ Grant Mag One magnetic filter kit² Wiring Centre Smart Controls¹ Touch Screen Display¹ Room thermostat – HPIDSMARTHRT (optional) Motorized 2-Port valve (DHW) Automatic air vent Cylinder immersion heater DHW cylinder Immersion heater relay² Drain point² Removable filling loop² Double check valve² Pressure gauge² Expansion vessel² Tundish² Pressure relief valve² Automatic bypass² Thermostatic Radiator valve Motorized 2-Port valve (Radiator circuit) Motorized 2-Port valve (UFH circuit) Thermostatic mixing valve UFH mixing set pump UFH manifold

*Outputs available: 6, 10, 13 & 17 kW Supplied with the HPIDR32SMART* Smart Controller Kit Supplied with HPIDR32PACKP

! NOTE !
***30L external volumiser or low loss header are available as an optional component where there is insufficient system volume or where hydraulic separation is required (HPIDVOLEXT30/HPIDSYSLLHKIT).
IMPORTANT The below diagram shows the Flow (outlet) and Return (inlet) connection positions for HPID6R32 models ONLY.

8
14 12 11
13

3 23
**
1 4
5
**Compression elbow c/w air vent (supplied with HPIDVOL30EXT6)

R
F5

23
1
*4**

2

3

6 7

IMPORTANT For positions of the Flow (outlet) and Return (inlet) connections on HPID10R32, HPID13R32 and HPID17R32 models, see above.

15

23

19

22

21 20

16

17 18

Grant Sealed System Kit

The siting of room thermostats is critical to ensure satisfactory performance of the heating system. Refer to the Aerona³ heat pump installation instructions for more information.
10 24
25

28
27 3
26
Close couple tees to be situated as close together as possible and no more than 4 pipe diameters.

9 3

29

Automatic bypass required unless there is an open radiator on the radiator circuit (such as a towel rail).

Page 11

! NOTE !
Please refer to the Aerona³ ASHP installation instructions for details of the flow and return connections at the heat pump.

! NOTE !
This system schematic should be read in conjunction with the Grant Aerona Smart Control installation instructions and wiring diagram HPCS-P001E.

4.5 HYDRAULIC CONNECTIONS – PACK Q
Grant UK Drawing Number: HPCS-Q001S

Page 12

Item Description

1

Aerona ASHP

2

Flexible hose¹

3

Isolation valve¹

4

Grant External Volumiser***

5

Anti-Vibration Mounts²

6

Flow sensor¹

7

Grant Mag One magnetic filter kit²

8

Wiring Centre Smart Controls¹

9

Touch Screen Display¹

10 Room thermostat

11 Automatic air vent

12 Cylinder immersion heater

13 DHW cylinder

14 Immersion heater relay²

15 Drain point²

16 Removable filling loop²

17 Double check valve²

18 Pressure gauge²

19 Expansion vessel²

20 Tundish²

21 Pressure relief valve²

22 Automatic system bypass²

23 Circulating pump

24 UFH manifold

25 3-Port diverted valve²

26 Thermostatic radiator valve

27 3-Port mixing valve²

28 Water sensor¹

*Outputs available: 6, 10, 13 & 17 kW

¹Supplied with the HPIDR32SMART* Smart Controller Kit

²Supplied with HPIDR32PACKQ

! NOTE !
***30L external volumiser or low loss header are available as an optional component where there is insufficient system volume or where hydraulic separation is required (HPIDVOLEXT30/HPIDSYSLLHKIT).

8
13 11
12

IMPORTANT The below diagram shows the Flow (outlet) and Return (inlet) connection positions for HPID6R32 models ONLY.

Port A 25

Port B

3

23

1

**

4 5

**Compression elbow c/w air vent (supplied with HPIDVOL30EXT6)

R
F5

23
1
**4*

2

3

6 7

IMPORTANT For positions of the Flow (outlet) and Return (inlet) connections on HPID10R32, HPID13R32 and HPID17R32 models, see above.

14

10

The siting of room thermostats is critical to ensure satisfactory performance of the heating system. Refer to the Aerona³ heat pump installation instructions for more information.

26 28

9

24

28 23

+

I

II

27 B

22

18

21

19

20

Automatic bypass required unless there is an open radiator on the radiator circuit (such as a towel rail).

15

16 17

Grant Sealed System Kit

! NOTE !
+The 3 port mixing valve mounted on the right hand side of the heating system will have the valve body scale plate indicating 0-10 in clockwise direction as well as the black scale plate for the actuator. Refer to the Smart Controller Installation instructions manual for more detail.

Section 4: System Hydraulics

! NOTE !
Please refer to the Aerona ASHP installation instructions for details of the flow and return connections at the heat pump.

! NOTE !
This system schematic should be read in conjunction with the Grant Aerona Smart Control installation instructions and wiring diagram HPCS-Q001E.

4.6 HYDRAULIC CONNECTIONS – PACK R
Grant UK Drawing Number: HPCS-R001S

Section 4: System Hydraulics

Item Description

1

Aerona ASHP

2

Flexible hose¹

3

Isolation valve¹

4

Grant External Volumiser***

5

Anti-Vibration Mounts²

6

Flow Sensor¹

7

Grant Mag One magnetic filter²

8

Wiring Centre¹

9

Touch Screen Display¹

10 Room thermostat

11 Automatic air vent

12 Cylinder immersion heater

13 DHW cylinder

14 Immersion heater relay²

15 Drain point²

16 Removable filling loop²

17 Double check valve²

18 Pressure gauge²

19 Expansion vessel²

20 Tundish²

21 Pressure relief valve² 22 Automatic system bypass

23 Motorized 2-Port valve (Upstairs – Radiators)

24 Thermostatic Radiator Valve

25 3-Port diverter valve²

26 Motorized 2-Port valve (UFH – Downstairs)

27 Thermostatic Mixing Valve
28 UFH Pump 29 UFH Manifold 30 Isolation valve

* Outputs available: 6, 10, 13 & 17 kW

¹ Supplied with the HPIDR32SMART* Smart Controller Kit

² Supplied with HPIDR32PACKR

! NOTE !
***30L external volumiser or low loss header are available as an optional component where there is insufficient system volume or where hydraulic separation is required (HPIDVOLEXT30/HPIDSYSLLHKIT).
IMPORTANT The below diagram shows the Flow (outlet) and Return (inlet) connection positions for HPID6R32 models ONLY.

8

14

13 11
12

25 Port A

Port B

3

23

1

**

4 5

**Compression elbow c/w air vent (supplied with HPIDVOL30EXT6)

R
F5

23
1
**4*

2

3

6 7

IMPORTANT For positions of the Flow (outlet) and Return (inlet) connections on HPID10R32, HPID13R32 and HPID17R32 models, see above.

22

18

21

20 19

15

16 17

Grant Sealed System Kit

10

The siting of room thermostats is critical to ensure satisfactory performance of the heating system. Refer to the Aerona³ heat pump installation instructions for more information.

24 23

9

29

28

27 30 30 26

Close couple tees to be situated as close together as possible and no more than 4 pipe diameters.

Automatic bypass required unless there is an open radiator on the radiator circuit (such as a towel rail).

Page 13

! NOTE !
Please refer to the Aerona ASHP installation instructions for details of the flow and return connections at the heat pump.

! NOTE !
This system schematic should be read in conjunction with the Grant Aerona Smart Control installation instructions and wiring diagram HPCS-R001E.

5 Electrical Connections

5.1 CONNECTING THE WIRING CENTRE

The wiring centre is to be powered with 230V AC/50 Hz voltage. The electrical installation should be:

·

Fused at 3A and earthed,

·

Cable size to be 0.75mm2 – 1mm2.

·

In accordance with current regulations,

must be protected with a residual current protection

device (RCD) with a rating In=30mA.

! WARNING !
All electrical scheme components should be connected only by qualified persons in accordance with applicable regulations. Follow safety precautions to prevent electrocution.
! WARNING !
After the wiring centre is turned off dangerous voltage on terminals may still be present. Before removing cover, disconnect the main power supply and use a Multimeter to check for voltage on terminals and leads.
For safety reasons, the wiring centre must be connected to a fused 230V AC power supply, with the sequence of connecting the live (L) and neutral (N) wires. Make sure that the L and N conductors are not crossed within the building’s electrical system, e.g., in an electrical socket or junction box.
5.1.1 ELECTRICAL CONNECTIONS All wiring connections should be made to the corresponding terminals on the pluggable terminal blocks supplied in the accessory and fixing pack. 1. Remove the terminal cover from the wiring centre housing.
Refer to Figure 5-3
! NOTE !
Isolate any incoming voltages on connections before removing the wiring centre cover beginning to connect to the wiring centre.

Figure 5-2: Wiring centre terminals cover
3. Connect the earth wire to the earth terminal strip inside the wiring centre housing.
4. Arrange the wires to prevent damaging the insulation by cutting it with cover edges or screws securing the cover.
5. Secure wire with cable clamp to prevent loosening from potential mechanical stress.
! WARNING !
The maximum length of the exposed wires extending from the outer cable sheath should not exceed 50mm. Connection cables should not be on contact with surfaces that exceed nominal operating temperature of 50°C.
! CAUTION !
All cable clamps must be fitted even if not all clamps are needed to maintain IP20.
! NOTE !
The wiring centre cover should always be in place before connecting the electrical supply.
5.2 COMPONENT CONNECTIONS
Electrical components of the planned system are to be connected to the wiring centre of the Grant Aerona smart controller. Refer to Section 5.4 for wiring centre layout. With the adjustable circuits, mixing needs a water temperature sensor connected to monitor the mixed water entering the circuit to adjust accoridngly. Table 5-1 displays the relation between the individual heating circuit and its associated component terminals.

I 0

Figure 5-1: Power switch
2. Connect L & N wires of the supply to Terminals 1 & 2. Refer to Figure 5-3 for wiring centre terminal diagram.

Table 5-1: Circuit component connections

Heating Circuit Pump/Valve

Mixer

1

H1-P

None

2

H2-P

H2-M

3

H3-P

H3-M

Water sensor None H2-S H3-S

Refer to 5.5, 5.6 & 5.7 for example pack wiring schematics. For any further guidance on device connections or schematic drawings, please contact Grant UK.

5.3 POWER SUPPLY FAILURE
In case of power supply failure, the controller returns to the work mode in which it was working previously when the power supply is restored.

Page 14

Section 5: Electrical Connections

5.4 WIRING CENTRE LAYOUT
230V AC / 50Hz
13 14 15 16 17 18 19 20 21 22

F1
L N 1 2

F3

F2

LN LN LN

M

M

M

1

2

3

H1-P H2-P H3-P H1

H2

PE PE PE

3 4 5 6 7 8 9 10 11 12

F4
LN L LN L N L

ON OFF
2 H2-M
PE

ON OFF

3
H3-M
PE

ON OFF
Z-P/Z3D C-P
PE PE

15V

37 38 39 40 41 42 43 44 45 46 47 48 49 50

G4

G3

GND

D+ D-

+5V

T1
ecoNET

23 H2-S H3-S HDW BT BB WS

23 24 25 26 27 28 29 30 31 32 33 34 35 36

G1

G2

GND GND GND IN GND IN GND

HEMS T2
LOCK

FLOW LE

D+

M-BUS B

ISM

D-

+12V GND D+ D-

L N PE
230V~

RT2

RT1

Figure 5-3: Wiring centre – Terminals

Table 5-2: Wiring Centre Terminals

Label 230V ~ H2-M H3-M Z-P/Z3D C-P

Terminal Numbers 1 & 2 3, 4 & 5 6, 7 & 8 9 & 10 11 & 12

Flow

31 & 32

LE

33 & 34

G1

Terminal Set

G2

M-BUS

G3 G4 H1-P H2-P H3-P

G3 Socket Terminal Set 13 & 14 15 & 16 17 & 18

H1

19 & 20

H2

21 & 22

H2-S

39 & 40

H3-S

41 & 42

HDW

43 & 44

BT

45 & 46

BB

47 & 48

WS

49 & 50

T1

37 & 38

T2

26 & 27

LOCK

23 & 24

HEMS

25 & 26

Section 5: Electrical Connections

Description Mains Live and Neutral Circuit 2 Mixing valve – 2 x 230V Lives (ON and OFF) and Neutral Circuit 3 Mixing Valve – 2 x 230V Lives (ON and OFF) and Neutral DHW Pump/3-Port Diverter Valve Secondary Circulation Pump Flow sensor I/O & Ground Electricity Meter Touchscreen & Thermostat connection terminals (RT1, RT2, RT3) Modbus connection to the Aerona Heat pump. Connection port for ecoNET cable +12V, Ground, D+, DCircuit 1 230V Switched Live and Neutral Circuit 2 230V Switched Live and Neutral Circuit 3 230V Switched Live and Neutral Switch for Immersion Relay (Buffer) Switch for Immersion Relay (DHW Cylinder) Circuit 2 Water temperature sensor Circuit 3 Water temperature sensor DHW Cylinder Water temperature sensor Buffer Upper Water temperature sensor Buffer Lower/Low Loss Header temperature sensor Outdoor Weather sensor External Volt-free switch for Circuit 2 External Volt-free switch for Circuit 3 Not used Not used

RT3
Page 15

5.5 ELECTRICAL CONNECTIONS – PACK P
Grant UK Drawing Number: HPCS-P001E

Notes: Some Neutral and Earth connections have been excluded for clarity. Grant Smart Immersion relay to house 2 live connections. Ensure both are isolated prior to opening housing.

UFH Circulator
28
L NE

Brown Blue
G/Y

Motor

HTG

Grey Orange

26

2-Port Zone Valve – UFH circuit –

Terminal Block 1 2 3 4 Place inside Smart
Controller Wiring Centre

Brown Blue G/Y

HTG Motor

25

Grey Orange

2-Port Zone Valve – Radiators circuit –

Aerona³ Heat Pump

1

24

8

25

9

26

10 27

11

28

12

29

13

30

14

31

15

32

16

ASHP Terminals

8 Smart Controls Wiring Centre 230 VAC

15VDC

G4 G3

13 14 15 16 17 18 19 20 21 22

37 38 39 40 41 42 43 44 45 46 47 48 49 50 G1

ecoNET

DHW Sensor Outdoor Sensor +12V GND D+ D-
+5V D+ DGND

Double Pole Isolator
13A

12

3 4 5 6 7 8 9 10 11 12

DW

WS

G1 G2

23 24 25 26 27 28 29 30 31 32 33 34 35 36 G1

+12V GND
D+ DD+ D-

M-BUS B/C

Brown Blue*
G/Y

Black Blue Brown

20A Minature Circuit Breaker

Dual Voltage

A1

A2

N

1 15

2

Brown Blue* G/Y

LN 13
Cylinder Immersion
Heater 5A
L N E
230V 50HZ

6 Flow sensor

+12V GND D+
D- 10
Wired Thermostat or Wireless Receiver -Radiator circuit-

+12V GND
D+ D-

9
Touch Screen Display -UFH Thermostat –

Brown Blue
G/Y

Motor

HTG

Grey Orange

11

2-Port Zone Valve – DHW –

Page 16

! NOTE !
*Please ensure that neutrals are derived from the same supply to prevent spurious trips.

! NOTE !
This wiring diagram should be read in conjunction with the Grant Aerona Smart Controls installation instructions and system schematic HPCS-P001S.

Section 5: Electrical Connections

5.6 ELECTRICAL CONNECTIONS – PACK Q
Grant UK Drawing Number: HPCS-Q001E
Notes: Some Neutral and Earth connections have been excluded for clarity. Grant Smart Immersion relay to house 2 live connections. Ensure both are isolated prior to opening housing.
! NOTE !
**If the 3 port valve is mounted on the left side of the heating system, the actuator has to be mounted in reverse, hence the white wire will be connected to terminal 8, and the brown wire will be connected to terminal 6. Blue wire will remain in the same terminal.
UFH circuit Circulating Pump
23
L NE

Aerona³ 1 Heat Pump

24

8

25

9

26

10 27

11

28

12

29

13

30

14

31

15

32

16

ASHP Terminals

Double Pole Isolator
13A

8 Smart Controls Wiring Centre 230 VAC

15VDC

G4 G3
G3

13 14 15 16 17 18 19 20 21 22

37 38 39 40 41 42 43 44 45 46 47 48 49 50
ecoNET G4

Sensor Z2 Sensor Z3 DHW Sensor
Outdoor Sensor +12V GND D+ D-
+5V D+ DGND

12

3 4 5 6 7 8 9 10 11 12

28

2

H2-S H3-S HDW

WS

23 24 25 26 27 28 29 30 31 32 33 34 35 36

G1

G2

M-BUS B/C

+12V GND
D+ DD+ D-

Brown Blue*
G/Y

White** Blue Brown**

Dual Voltage Immersion Relay

A1

A2 N

20A

Minature

1 14

2

Circuit

Breaker

1 2 3

27
Motorised Rotary Actuator for 3-Port Mixing Valve**

Brown Blue* G/Y

LN 12
Cylinder Immersion
Heater

Hot water cylinder port A (port A normally closed) Heating circuit port B (port B normally open)

G/Y

V4044C Diverter Valve

Blue* Brown

5A

A

25

B

L N E AB
230V 50HZ

Black Blue Brown
+12V GND
D+ D-

+12V GND D+
D- 10 Wired Thermostat/ Wireless Receiver
-UFH Upstairs-
FLow sensor
9 Touch Screen Display
-UFH Downstairs –

! NOTE !
*Please ensure that neutrals are derived from the same supply to prevent spurious trips.
Section 5: Electrical Connections

! NOTE !
This wiring diagram should be read in conjunction with the Grant Aerona Smart Controls installation instructions and system schematic HPCS-Q001S.

Page 17

5.7 ELECTRICAL CONNECTIONS – PACK R
Grant UK Drawing Number: HPCS-R001E

Notes: Some Neutral and Earth connections have been excluded for clarity. Grant Smart Immersion relay to house 2 live connections. Ensure both are isolated prior to opening housing.

UFH Circulator
28
L NE

Brown Blue
G/Y

Motor

HTG

Grey Orange

26

2-Port Zone Valve – UFH circuit –

Terminal Block 1 2 3 4 Place inside Smart
Controller Wiring Centre

Brown Blue G/Y

HTG Motor

Grey Orange

23

2-Port Zone Valve – Radiators circuit –

Aerona³ Heat Pump

1

24

8

25

9

26

10

27

11

28

12

29

13

30

14

31

15

32

16

ASHP Terminals

8 Smart Controls Wiring Centre 230 VAC

15VDC

G4 G3
G3

13 14 15 16 17 18 19 20 21 22

37 38 39 40 41 42 43 44 45 46 47 48 49 50 G4

ecoNET

DHW Sensor Outdoor Sensor +12V GND D+ D-
+5V D+ DGND

Double Pole Isolator
13A

12

3 4 5 6 7 8 9 10 11 12

G1 G2 23 24 25 26 27 28 29 30 31 32 33 34 35 36
M-BUS B/C

+12V GND
D+ DD+ D-

Brown Blue*
G/Y

Minature Circuit Breaker
20A

Immersion

Heater

Relay

A1

A2

N

1 14

2

Hot water cylinder port A
(port A normally closed)
Heating circuit port B
(port B normally open)

V4044C Diverter Valve

G/Y Blue* Brown

A

25

B

AB

Brown Blue* G/Y

LN 12
Cylinder Immersion
Heater 5A
L N E
230V 50HZ

Black Blue Brown

6 Flow sensor

+12V GND D+
D- 10
Wired Thermostat/ Wireless Receiver -Radiator Upstairs-

+12V GND
D+ D-

9
Touch Screen Display -UFH Downstairs –

! NOTE !
*Please ensure that neutrals are derived from the same supply to prevent spurious trips.
Page 18

! NOTE !
This wiring diagram should be read in conjunction with the Grant Aerona Smart Controls installation instructions and system schematic HPCS-R001S.
Section 5: Electrical Connections

6 System Configuration with Touchscreen display

6.1 FIRST SWITCH-ON
With installation completed, the Grant Aerona Smart controller will need to be configured:
1. Turn on the Grant Aerona Smart controller via the wiring centre power switch (Refer to Figure 5-1) and allow the software to cycle to the language selection panel. (Refer to Figure 6-1).

System configuration creator Would you like to start configuration?

Language

Figure 6-4: Configuration creator
6. If you tap X the controller will take you to the home screen and display ‘No circuits defined’. Refer to Figure 6-5.

Figure 6-1: Language selection 2. Select required language preference and confirm with >.
Date

No Circuits Defined

2023 10 02

Figure 6-5: No circuits defined
7. To access the system configuration creator you need to access the settings menu / service settings menu. See Section 7 Table 7-1. The service settings password is 0000.

Figure 6-2: Setting date 3. Set the date. Tap the & to amend the values for year ,
day and month. Confirm with >. Refer to Figure 6-2.
Time

6.2 SYSTEM CONFIGURATION CREATOR
The Grant Aerona Smart Controller integrated system configuration creator will aid with the setup of the space heating and DHW system within the software of the touchscreen display.
The steps in the configuration creator should reflect the system you have designed and electrically connected to the wiring centre.
You must only configure components you have connected (Refer to Section 5 Figure 5-3 for wiring centre layout).

! NOTE !

14 06

Ensure you pay close attention to the devices you connect to the wiring centre and confirm for correct operation.
Using the system you have planned you can follow the system confirguration creator steps to configure it within the Grant Aerona Smart controller. (Refer to Figure 6-6 for System configuration map).

Figure 6-3: Setting time
4. Set the time. Tap the & to amend the time & confirm with >. Refer to Figure 6-3.
5. The touchscreen will progress to ask if you wish to start a configuration. Tap ü to start the configuration creator. Refer to Figure 6-4 and Section 6.2.

Section 6: System Configuration with Touchscreen Display

Page 19

Section 6: System Configuration with Touchscreen Display

Page 20

Would you like to start configuration?
ü

How it Heat transferred from source?

LLH Buffer Direct

>

>

>

Number of

Sensors

12 >

Is DHW in

the system?

X

ü

Is a (Secondary) Circulation pump for DHW required? X
ü

Is there an outdoor

weather sensor?

ü

X

Select Outdoor Temperature sensor

EcoMulti >

X Do you want to configure Circuit 1?
ü
Circuit 1 Name
>
Choose Circuit 1 Mode

Radiators
(Unmixed) >

Fan-coil
(Unmixed) >

Choose Circuit Control Method

Fixed >

Weather >

Fixed Set Water Temperature >

Heating Curve Edit >

Decreasing Set Water Temperature >

Decreasing Set point Temperature
>

Circuit 1 Thermostat Choice >

Circuit 1

Summary

>

Radiators >

X Do you want to configure Circuit 2?
ü
Circuit 2 Name >
Choose Circuit 2 Mode

Do you want to configure Circuit 3?
ü
Options Mirror Circuit 2

Fan-coil >

Underfloor
Heating >

Is the Circuit Mixer

Controlled?

X

ü

Valve Opening Time >

Choose Circuit Control Method

Fixed >

Weather >

Fixed Set Water
Temperature >

Heating Curve
Edit >

Decreasing Set Water
Temperature >

Decreasing Set
point Temperature >

Circuit 2 Thermostat Choice >

Circuit 2

Summary

>

Figure 6-6: System Configuration Map

Do you want to check configured system?

X

ü

Manual Control >

Configuration Summary >

Setup Complete

! NOTE !
X – Confirm option is not required and proceed. ü – Confirm option is required and proceed. > – Confirm configurable option and proceed. < – Return to previous step in configuration.

· Would you like to start configuration?

· Circuit Summary

If a system has already been Configured you will be

The circuit summary displays the parameters you have

prompted to confirm you wish to overwrite the previous

defined. The circuit structure displays as a pump but is a

setup.

230V switched live output (labelled on the wiring centre as

H1-P, terminals 13 and 14). This could be connected to a

· How is heat transferred from the source?

2-Port motorised valve as is common in the UK. (Refer to

Confirm if you are using a Buffer/Volumiser, Low Loss

Section 5, Figure 5-3).

Header that the Grant Aerona Smart controller will manage or

if heat is transferred directly to the primary circuit.

·

Do you want to check configured system? Confirming will activate the manual control function (Refer

· Is DHW in the system?

to Section 8 and Figure 8-2) on the touchscreen display.

The Grant Aerona Smart controller will manage the DHW

The components that you have configured via the creator

cylinder as well as prioritize DHW on a demand.

will be shown on the screen. There will be both an icon on

· Is Circulation pump for DHW in system? This would be enabled if you require the Grant Aerona Smart controller to manage a secondary circulation pump.

the operational button area and the terminal block numbers to which they should be wired to on. Refer to Section 5 for the terminal blocks and associated devices that they control. Tapping the icon will switch the internal relay and send a

· Is Outdoor temperature sensor in the system?

relevant voltage to activate.

This will enable the weather control features of the Grant

Aerona Smart controller.

6.3 WEATHER COMPENSATION

· Source of Outdoor temperature sensor Assign an Outdoor temperature sensor. The ‘ecoMULTI’ is

6.3.1 HEATING CURVE

the outdoor weather sensor supplied with your Grant Aerona Weather compensation can be enabled if an Outdoor Weather

Smart Controller kit and should be the only option you

sensor is connected. The Outdoor Weather sensor should be

choose. Refer to Section 3.4.1.

enabled and select Regulation method as ‘Weather’.

· Do you want to Configure circuit 1, 2 or 3? Configuration of Heating circuits. Circuit 1 is non-mixing and this is indicated with a note that Circuit 1 can not have a mixer.
· Circuit Name To amend the name of a circuit e.g., ‘Ground Floor’ tap the change name button which will open a qwerty keyboard. To finish tap the enter key.

The circuit water target temperature is calculated based on the ambient temperature outside the building. The colder it is outside, the higher the water temperature in the circuit will be. The heating curve is configured per circuit either during system configuration or via the service menu of the controller.
Heating curve selection

· Choose circuit mode Assign the heating emitter type for the circuit. This could be ‘Radiators’ or ‘Underfloor heating’.

Heating Set point

Curve

Shift

· Choose circuit control method

60

Assign a control method from either ‘fixed’ or ‘weather’ control. Individual circuits can be assigned differing methods and can be amended later via the Circuit settings within the
system settings menu.

45 30 15 22°C

33°C 28°C

37°C 41°C

44°C

0.5

2

· Fixed Set point water temperature (Fixed Control)
The circuit will operate on a fixed flow temperature. This is the default day flow temperature.

20 10

0 -10 -20 -30
External temperature

· Decreasing set point water temperature (Fixed Control) This is the temperature the system flow will drop by on scheduled night/unattended periods.
· Heating curve edit (Weather Control) Configure the heating curve for the calculative weather control adjustments for set-point temperatures. Refer to 6.4 for further information on editing the heating curve.
· Decreasing set point temperature (Weather Control) This is the temperature the system flow will drop by on scheduled night/unattended periods.
· Will circuit be controlled with a Mixer? Confirm if the circuit will be controlled by a motorised mixing valve. (Not applicable to Circuit 1)

Figure 6-7: Heating curve adjustment

The heating curve selection will provide the line graph representing required target water temperature against outdoor air temperature (Refer to Figure 6-7).
1. Tap or of ‘Curve’ to align the curve to set a 45°C @ -5°C ‘External temperature’ as a starting point. Refer to Table 6-1 for recommended heating curve settings.
2. To further adjust should the temperature points not be satisfactory, Tap or of ‘Shift’ to move the set curve up or down.

Table 6-1: Recommended Heating Curve

Heat Emitter

Initial Curve Setting

· Mixing valve opening time

Fan-Coil

1.2 – 1.6

Configure the valve opening time to allow the software to be able to calculate the opening times for correct temperature

Radiators

1.2 – 1.6

mixing. (Refer to Appendix C for further information on the

Undefloor

0.2 – 0.6

mixing valve).

Refer to Section 6.3.2 for advice on how to further alter the

· Circuit thermostat choice

heating curve.

Configure a thermostat to a circuit. A circuit could be uncontrolled, use the touchscreen display or a wired/wireless thermostat. If a wired/wireless is chosen, the touchscreen display will begin the pairing wizard to be followed to pair the
individual thermostat to this circuit. Refer to Section 7.3.1.4.

The Grant Aerona Smart Controller can increase or decrease the
Heat pump target flow temperature, calculated in accordance with the heating curve, if it exceeds the temperature range for the
given circuit set in controller service menu.

We recommend at least one circuit be controlled by the

supplied touchscreen display.

Section 6: System Configuration with Touchscreen

Page 21

6.3.2 HEATING CURVE ADJUSTMENT The heating curve is adjustable and should be reviewed to ensure both comfort and economy.
The heating curve is set as part of the initial system configuration when configuring ‘Weather’ control but can be edited after the system configuration has been completed. Refer to Section 7.3.1.3 to access the heating curve setting adjustment, Figure 6-7 and Appendix F.7 for a QR code link to a how to video on adjusting the circuit heating curve.
Guidelines for adjusting a heating curve
· If the outdoor temperature drops, and the room temperature increases, the selected heating curve value is too high.
· If the outdoor temperature drops, and the room temperature drops as well, the selected heating curve value is too low.
· If during frosty weather the room temperature is comfortable, but when it gets warmer the room is too cold, it is recommended to increase the Heating curve shift and to select a lower heating curve.
· If during frosty weather the room temperature is too cold, and when it gets warmer the room is too hot, it is recommended to decrease the Heating curve shift and to select a higher heating curve.
Poorly insulated buildings or the use of traditional steel radiators require setting higher heating curves. Well insulated buildings and/or low temperature heat emitters e.g. Undefloor heating, heating curves will have a lower value.
6.4 CIRCUIT CONTROL SETTINGS
6.4.1 FIXED CIRCUIT CONTROL
(Not weather compensated) If the heat emitter size is known, set the required water temperature in the circuit using parameter ‘Fixed preset water temperature’, e.g., at a value of 50 °C. The value should allow the room to reach the required temperature.
After connecting the room thermostat, it is necessary to set a value of decrease in the Decreasing fixed water temperature parameter, e.g., to 3 °C. This value should be selected by trial and error. Upon activation of the room thermostat, the target circuit temperature will be decreased, which, if proper decrease value is selected will stop rise of temperature in the heated room.
6.4.2 WEATHER COMPENSATED CIRCUITS
(Not Fixed) The Outdoor weather sensor must be installed and configured to be able to use weather control. Using Heating curve shift, set target room temperature following the formula: Preset room temperature = 20°C + heating curve shift.
In this setup, it is possible to connect a room thermostat which will equalise the inaccuracy of set heating curve, if the selected heating curve value is too high. In such case, it is necessary to set the value of parameter Decreasing fixed water temperature, e.g., to 2 °C.
When the target temperature of the room thermostat is achieved, the Heat pump target flow temperature will be decreased, when pump blockade for that circuit is off. If pump blockade is on, the circuit pump/valve will close (if installed).

6.5 COMMON SETTINGS
After the system has been configured, check and if needed amend some common settings within the Heat pump parameters menu via the touchscreen display (Refer to Table 6-2). To access the Heat pump parameters menu: 1. Tap the Settings menu and select ‘Service settings’ and enter
the password: 1234. Refer to Table 7-1 and Section 9 for full Heat pump parameters listing.

User settings
Service settings

Figure 6-8: Settings menu

Table 6-2: Heat Pump parameters

Parameter No. Parameter Title

Heat pump Set points

21 00

Weather Comp

Frost protection

43 10

Frost Ambient Temp

43 11

Start Temp

43 12

Hys of Ambient Temp

43 20

Frost Flow Temp

43 21

Start Temp

43 22

Hys of Flow Temp

Relay output settings

51 07

DHW Cylinder Sensor

51 09

Amb Temp Ext Sensor

51 11

Buffer Temp Sensor

51 15

Modbus

Setting Value
Off
Frost Ambient Temp on 4°C 3°C ON 4°C 3°C
Off Off Off On

Page 22

Section 6: System Configuration with Touchscreen Display

7 Touchscreen Display Operation and Settings

7.1 TOUCHSCREEN DISPLAY
The display is a capacitive touch screen and parameters are edited by touching the selected symbol or area on the display screen.

1

5

7

8

9

10

!

NET

20.5°C

2 3

15
21 °C 16 .7 6

14
A
4

13
19.0°C

11 Ground Floor

12

Table 7-1: Touch screen

Number

Symbol

1

Figure 7-1: Display home screen example
Description Tap to access Heating circuit controls. Refer to Section 7.3.1.1

2

Tap to access DHW system controls. Refer to Section 7.3.2.1

3

Tap to access Schedule settings for Heating circuit(s), DHW cylinder and Heat Pump. Refer to Section 7.5.

4

Tap to access to Settings menu. Refer to Section 7.9

5

Tap to view Heat pump schematic. Refer to Section 7.6

6

Tap to access active system schematic.Refer to Section 7.7.

7

!

Indicates there are active alarms on the Smart controller.

8

NET

Indicates active connection to EcoNet24 external server.

9

Outdoor temperature value (If outdoor weather sensor support is enabled in the service menu). Tap to view and amend Smart Controller work mode. Refer to Section 7.3.3.

10

Indicates an active heat demand.

11

Ground Floor Circuit title/name

12

Circuit panes available (if more than 1 installed).

13

Circuit user set value.

14

A

Current circuit work mode. Tap to quick access the circuit work mode screen. Refer to 7.3.1.2 & 7.3.2.2

15

21.7°C

Current circuit temperature. Tap to access Circuit settings. Refer to 7.3.1 & 7.3.2.

16

Tap to move between multiple circuits (if installed) – The touchscreen can also be swiped to change circuits.

Section 7: Touchscreen Display Operation and Settings

Page 23

7.2 SMART CONTROLLER OPERATION
7.2.1 MAIN HEAT SOURCE The Grant Aerona Smart controller manages the operation of the heat pump by activating or deactivating it according to demand for DHW or the space heating circuits.

20,5°C

7.2.2 HEAT CIRCUITS The Grant Aerona Smart controller can manage the operation of one non-adjustable and up to two adjustable heat circuits. Water temperature in circuits can set as a fixed flow temperature or by weather, i.e., water temperature in the circuit is calculated in accordance with a temperature from the external temperature sensor. Despite varying outdoor temperature, a room temperature in heated rooms is kept on a set level. · Dependent circuits ­ A thermostat assigned for many circuits.
For example, temperature readings on a installed panel affect operation of both radiator and underfloor circuits. Commonly one Thermostat in a central location.
· Independent circuit ­ Connecting thermostats to measure room temperature independently and affecting assigned circuits. It is the way to obtain independency of the circuits, e.g., in case when one part of the building is used for the whole year and the second part is used periodically, e.g., for rent.
If multiple circuits are being controlled you can navigate between them with a swipe of the screen either to the left or the right.
7.2.3 DOMESTIC HOT WATER The Smart Controller manages the operation of the Heat Pump and heating of a DHW cylinder up to a user set temperature. DHW operation can be programmed in time intervals with a minimum operation for disinfection mandatory. While the Smart Controller can also control a DHW secondary circulating pump, their use is not recommended to minimise wasted energy and running costs.
20,5°C
53°C ,6
53°C
DHW temperature
Figure 7-2: DHW temperature display example
! NOTE !
The change of the colour under the current value of the temperature of the circulation and DHW cylinder indicates whether the temperature is below (blue), above (red) or the same (green) as the target temperature. Grey indicates the DHW function is Off.

A Auto
First Floor

40°C

Figure 7-3: Thermostatically uncontrolled circuit display
! NOTE !
The circuit is not controlled by a thermostat if a heat emitter icon is displayed on the circuit temperature display screen.
7.3 CIRCUIT SETTINGS
Tapping the screen on the displayed information of the DHW or a heating circuit you are viewing (if more than 1 heat circuit installed) will open the circuit settings panel. This will display various options that can be edited. Refer to Figure 7-4.

20,5°C
53°C

On

55.0°C

DHW temperature

Figure 7-4: Circuit settings access on touch-screen
7.3.1.1 HEAT CIRCUIT SETTINGS Entering Heat circuit settings will display options the used can edit for the heating circuit. Refer to Figure 7-5.
Preset day temperature
+
21°C .5 –
Heating zone 1

Figure 7-5: Heating circuit settings example

Page 24

Section 7: Touchscreen Display Operation and Settings

Table 7-2: Heating circuit settings

Button

Function description

Navigate back to previous screen.

Tap to amend Circuit work mode

Tap to view & amend circuit details

Tap to amend circuit thermostat choice

+

Increase required circuit temperature

Decrease required circuit temperature

7.3.2.1 DHW SETTINGS
As per Figure 7-4 when on the DHW (if installed) you will navigate to the DHW settings.

Table 7-5: DHW settings panel

Button

Function description

Navigate back to previous screen.

Tap to amend DHW work mode

Tap to access DHW additional settings

+

Increase required circuit temperature

Decrease required circuit temperature

7.3.1.2 CIRCUIT WORK MODE The Circuit work mode sets the circuit to operate as per the consumer preference.

Table 7-3: Heating circuit work modes

Button

Function description

Auto – Day/Night temperatures based on user schedule

Off – Circuit will not be heated

Day Mode – Circuit set to preset day temperature

Night Mode – Circuit set to preset night temperature

7.3.2.2 DHW WORK MODE
DHW work modes give selectable modes as per the consumer preference but also have a optional boost function should the consumer wish (in the event of an expected increase in system demand).

Table 7-6: DHW work modes

Button

Function description

Navigate back to previous screen.

Boost – Tap to create a temporary DHW demand.

1

Cylinder wil be raised to user set value and then

stop.

On – DHW demand on temperature fall by hysteresis (Refer to Section 7.3.2.3)

7.3.1.3 HEATING CIRCUIT DETAILS
The heating circuit details panel will display settings of the circuit which you are viewing/editing. Refer to Figure 7-5.
· Circuit name ­ Name of the circuit, e.g., “Ground Floor”.
· Hysteresis ­ The value between when a thermostat switches off and back on. The parameter is only available when a thermostat is assigned to the circuit.
· Preset day temperature ­ The target air temperature for when the circuit is set to/scheduled to be in day mode (occupied). The parameter is available for editing only when a thermostat is assigned to the circuit.
· Preset night temperature (Setback temperature) ­ The target air temperature for when the circuit is set to/scheduled to be in night mode (overnight/unoccupied). The parameter is available for editing only when a thermostat is assigned to the circuit. The setback temperature should be configured to the ideal comfort level minus the temperature value shown in Table 7.4 below (based on heat emitters configured).

Table 7.4: Recommended setback air temperatures

Heat Emitter

Night mode setback value(°C)

Fan-Coil

3

Off – Cylinder will not be heated
Schedule – On/Off based on User schedule
Tapping ‘Boost’ will create a temporary DHW demand. The icon colour will change and remain blue until the cylinder reaches user set temperature. If you wish to stop this, Tap the boost icon again. The icon will change to grey to indicate it is off. If the cylinder is within its optimum temperature range the boost function will not activate
7.3.2.3 DHW ADDITIONAL SETTINGS DHW additional settings provides a sub menu for the DHW cylinder hysteresis parameters & Legionella protection (If additional heater is configured – Refer to Section 7.4). DHW Hysteresis is the amount of temperature drop from the user set temperature in the cylinder before the system will demand more heat in a scheduled ON time period. If the hystersis setting is too low this can cause potential cycling of the heat demand in an scheduled ON period. Too high can cause the cylinder to not reach desired temperature and higher energy useage.

Radiators

3

Underfloor Heating

1

· Heating curve ­ Adjust the heating curve and shift. Refer to Section 6.3.

7.3.3 CONTROLLER WORK MODE
The Grant Aerona Smart Controller work mode of the controller is selected by tapping the currently displayed symbol on the main screen in the place where the value of the outdoor temperature is displayed. (Refer to Table 7.1).

7.3.1.4 HEATING CIRCUIT THERMOSTAT CHOICE
Circuit thermostat choice will allow a circuit thermostat to be reassigned. You will be prompted to confirm you wish to overwrite any existing thermostats installed. The options are: None, Control panel, Wired thermostat, Wireless thermostat.
· None: No Thermostat assigned

Table 7-7: Controller work mode

Mode

Description

AUTO

Automatically switches on or off the heatingcooling mode (Cooling not available with Aerona
R32 heat pump range), depending on the external
temperature.

· Control Panel: Thermostat within Touchscreen display.
· Wired Thermostat: Wired thermostat (See Appendix A).
· Wireless Thermostat: Paired Wireless Thermostat (See Appendix B).

SUMMER WINTER

Adjustable circuit performs the cooling function. (Cooling not available with Aerona R32 heat pump range)
Adjustable circuit performs the heating function.

Section 7: Touchscreen Display Operation and Settings

Page 25

7.4 LEGIONELLA PROTECTION
The Grant Aerona Smart controller has the function to provide protection against legionella by executing a scheduled temperature increase. This is executed on a weekly basis from within the Grant Aerona Smart controller settings.
For protection against legionella the DHW cylinder needs to be periodically raised to a minimum of 60°C to ensure it is sterilised of any present legionella bacteria.
Care must be given to vulnerable people who may be exposed to potentially life-threatening legionella. This group of people include the elderly, pregnant women, young children and those with breathing difficulties. Where legionella disinfection is required more frequently than once a week, this must be provided by other means.
It is important that this decision is based on the welfare of the occupants and not on energy saving measures.

7.5 TIME SCHEDULES
The Grant Aerona Smart Controller allows for programmable time schedules for the Heating Circuit(s), DHW and the Heat pump itself.
In the situation when the consumer is not at home or at night, the controller can decrease the amount of supplied heat which affects electric consumption.
Time schedules can be set separately for each day of the week or copied across multiple days. If the space is unoccupied Monday to Friday for the same time periods the user could set the hours for Monday and then apply to multiple days.

Schedule

12:00 Mon.14.11.2022 Monday

! WARNING !

If the hot water stored in the cylinder has not been used

0

for a prolonged period of time (e.g., a few days) and has

not been stored at 60°C, then it is important that the

temperature is raised to at least 60°C for a period of one

hour before using the hot water.

12

24

11:30-12:00

7.4.1 ENABLING DHW HEATER SUPPORT ‘DHW heater’ support must be enabled within the system settings menu of the controller for ‘disinfection’ to be available.
1. Tap the Settings Menu button.
2. Tap ‘Service settings’ and input the password: ‘0000’. Tap ‘Enter’ to confirm.
3. Tap ‘Installation controller’.
4. Swipe the touchscreen to move down and tap ‘Heaters’
5. Tap the button next to ‘DHW Heater’ to enable heater support.
6. Tap and set ‘DHW Delay’ to ’75mins’ and confirm. (To prevent the Immersion heater from operating during a scheduled DHW demand period).
7. Tap ‘<‘ to navigate back.

Figure 7-6: Heating time schedule interface
! NOTE !
The ON/OFF time schedule is defined separately for the heat pump and DHW cylinder.

Schedule

12:00 Mon.14.11.2022 Monday

7.4.2 CONFIGURING LEGIONELLA SETTINGS Once DHW heater support has been enabled: 1. Navigate to the DHW circuit screen. 2. Tap the displayed temperature for the cylinder to enter the
DHW circuit settings. 3. Tap ‘DHW additional settings’ (Refer to Table 7-5). 4. Tap the button next to ‘disinfection’. This will expand the
display for the individual settings for legionella protection for configuration. · ‘Day’ – Day to execute Legionella protection. · ‘Start Hour’ – Time to start. · ‘Preset temp’ – Temperature for DHW cylinder to heat to.
(Should not exceed 60°C).
! NOTE !
Legionella protection works independently of the DHW cylinder schedule and will start even if DHW cylinder is scheduled off.
7.4.3 LEGIONELLA DISINFECTION SCHEDULING Legionella disinfection should be scheduled in a window that is a minimum of 1 hour after a DHW demand and in a setback heating demand period e.g. Overnight. This is to avoid the least amount of loss in the heating circuits. The Legionella protection can not be run twice in a week should the schedule be changed within the settings.

0

12

24

11:30-12:00

ON OFF

Figure 7-7: DHW/Heat pump time schedule interface

Table 7-8: Time schedule controls

Button

Function description

Navigation Arrows – Weekday selection and time period selection. Navigate the required day or move selected time period in the specified direction.

Copy to – Copy the currently set schedule to one or multiple days

Preset Night mode (Setback Temperature) – Target night temperature for circuits will be applied if a thermostat is assigned to the circuit. If not, the decrease will be set to the value of the Water temperature decrease.
Preset Day mode – Target day temperature setting for circuits will be applied, if a thermostat is assigned to the circuit.

ON OFF

Option is Configured ‘ON’ Option is Configured ‘OFF’

Page 26

Section 7: Touchscreen Display Operation and Settings

7.5.1 HEATING CIRCUIT SCHEDULE The schedule for the heating circuit(s) controls the specific time period at which the target day and night temperatures are applied.
To amend a heating schedule:
1. Tap the time schedule menu (Refer to Figure and Table 7-1). The schedule icon is available regardless of which circuit or device you are currently viewing.
2. Tap the heating circuit you wish to amend from the options.
3. Modify the day if different to current by tapping navigation arrow. Refer to Figure 7-6.
4. Tap the night mode function and use the navigation buttons to move to the first time period you wish to change (if more than one).
5. Tap day mode and use the right navigational button to alter the time periods. Switch between day and night mode for unoccupied portions of the day.
6. After defining the required time schedule it can be applied to multiple days. Tap ‘Copy to’ and tap the days required. Refer to Table 7-8. Confirm with ü.

7.6 HEAT PUMP SCHEMATIC
The heat pump schematic gives a visual preview of the basic operating functions of the heat pump such as working status, Flow/return temperatures as well as being able to configure the operating mode of the heat pump in relation to the system installed.

20,5°C

OFF 39ºC

OFF 0rpm
On

OFF

39ºC

0Hz

Pump heating

Heat Pump

7.5.2 DHW SCHEDULE The schedule for the DHW cylinder will turn the cylinder heating function from the heat pump on or off on the selected time period. If the cylinder temperature falls below hysteresis value in an off time period the heat pump will not activate.
To amend the DHW schedule:
1. Tap the time schedule menu (Refer to Figure and Table 7-1). The schedule icon is available regardless of which circuit or device you are currently viewing.
2. Tap ‘DHW’.
3. Modify the day if different to current by tapping navigation arrow. Refer to Figure 7-7.
4. Tap the ‘OFF’ function and use the navigation button to move to the first time period you wish to change. (if more than one).
5. Tap ‘ON’ and use the right navigational button to alter the time periods. Switch between ‘ON and ‘OFF’ to create multiple intervals based on end-user requirements
6. After defining the required time schedule it can be applied to multiple days. Tap ‘Copy to’ and tap the days required. Confirm with ü. Refer to Table 7-8.
We recommend to schedule up to 4 x 1 hour on periods in a day with a minimum gap of 1 hour between each.
7.5.3 HEAT PUMP SCHEDULE The schedule for the heat pump will disable the heat pump from activating in the off periods To amend the Hheat pump schedule:
1. Tap the time schedule menu (Refer to Figure and Table 7-1). The schedule icon is available regardless of which circuit or device you are currently viewing.
2. Tap ‘Heat source’.
3. Modify the day if different to current by tapping navigation arrow. Refer to Figure 7-7.
4. Tap the ‘OFF’ function and use the navigation button to move to the first time period you wish to change. (if more than one).
5. Tap ‘ON’ and use the right navigational button to alter the time periods. Switch between ‘ON and ‘OFF’ to create multiple intervals based on end-user requirements
6. After defining the required time schedule it can be applied to multiple days. Tap ‘Copy to’ and tap the days required. Confirm with ü. Refer to Table 7-8.
We recommend you leave the Heat pump enabled ‘ON’ at all times. This does not mean the heat pump will be running continually.
! NOTE !
The heat pump schedule will override all other schedules and could cause unwanted heat loss within the space heating or DHW circuits.

Figure 7-8: Heat pump scheme interface
The heat pump operating modes are accessed by tapping the heat pump scheme icon. Refer to Table 7-9 and Figure 7-8.
Table 7-9: Heat Pump Status The heat pump is turned on.

ON OFF SCHEDULE

The heat pump is turned off regardless of the conditions in the system.
The heat pump is switched on and off according to the set time schedule for the heat pump.

7.7 SYSTEM SCHEMATIC
The system scheme display shows the scheme of the installed and configured system. Icons will change from white to green to indicate they are active such as a motorised valve or the Heat pump. Refer to Figure 7-9 for system schematic example.
Installed diverter valves will indicate via the symbol which direction it is causing the heat to travel. Mixer valves will display a % figure to show their open status.
The system schematic also displays water temperatures from installed sensors (DHW Cylinder, Buffer, Low-Loss Header, Water temperature sensors on adjustable circuits).

1

2

3

Figure 7-9: System schematic display
! NOTE !
The view of the system schematic depends on the enabled support for the individual circuits, DHW cylinder or buffer installed.

Section 7: Touchscreen Display Operation and Settings

Page 27

7.8 CIRCUIT CONTROL
The 3 available heating circuits in the Grant Aerona Smart controller are connected and controlled via the following terminals within the wiring centre (Refer to section 5).
Table 7-10: Circuit terminals

Installation controller DHW settings Circulation settings

Heating circuit 1 2

230V Pump/Valve Terminals 13(L) & 14(N) 15(L) & 16(N)

Circuit 1 Circuit 2

3

17(L) & 18(N)

Circuit 3

Each heating circuit can either have a circulation pump or motorised valve connected to it.

Heaters

In a conventional system the thermostat (or sensor) will stop the pump or close valve when the actual circuit air temp reaches the target circuit air temp.
7.8.1 THERMOSTATIC PUMP BLOCKADE

Figure 7-11: Installation controller menu
4. Swiping the touchscreen display scroll down to ‘Thermostatic pump blockade’. Tap the icon to switch on. (Refer to Figure 7-12)

If a thermostat has been installed on any heating circuit, you have the following choices in how to control that circuit:

Circuit 1

1. With pump blockade ‘ON’ – Each heating circuit thermostat will control the circuits circulation pump or motorised valve (whichever is installed) for that circuit based on the air temperature the sensor/thermostat is monitoring.

Fixed preset water temperature

40°C

Decreasing fixed water temperature 4.0°C

2. With pump blockade ‘OFF’ – The heating circuit will continue to have circulation pump or motorised valve enabled (whichever is installed) but the smart controller will drive down the flow temperature to the minimum value to maintain the target air temperature within the circuit i.e the circuit remains active. This option would be best suited for open loop room optimisation.

Thermostat

ecoTOUCH: 100

Room temperature correction

4.0

Thermostat pump blockade

7.8.1.1 ENABLE THERMOSTATIC PUMP BLOCKADE To enable Thermostatic pump blockade for a circuit: 1. Tap the Settings menu and then ‘Service settings’. Enter
the password: 0000 on the keypad provided and tap ‘Enter’. Refer to Table 7-1 and Section 8 for full Service settings parameters listing.

User settings
Service settings

Figure 7-12: Edit Circuit 1 settings
Tap the < button to navigate backwards to the home screen.
7.8.2 CIRCUIT STOP FROM PRESET TEMP If a water temperature sensor has been installed on a mixing circuit, you have the ability to control that circuit based on the circuit flow temperature value. 1. With Circuit stop from preset Temp ‘ON’ – The water
temperature sensor will monitor the water temperature of the flow into the circuit from the heat pump and directly control the circuits circulation pump or motorised valve closed when the target water temperature is achieved.
2. With Circuit stop from preset Temp ‘OFF’ – The heating circuit will continue to have circulation pump or motorised valve enabled (whichever is installed) but the smart controller will drive down the flow temperature to the minimum value to maintain the target water temperature within the circuit i.e the circuit remains active. This option would be best suited for open loop room optimisation.

Figure 7-10: Service Settings menu
2. Tap ‘Installation controller’ 3. Swiping the Touchscreen display scroll down to the desired
circuit and select by tapping. (Refer to Figure 7-11).

7.8.2.1 ENABLE CIRCUIT STOP FROM PRESET TEMP

To enable Circuit stop from preset temp for a circuit:

1.

Tap the Settings menu and then ‘Service settings’. Enter

the password: 0000 on the keypad provided and tap

‘Enter’. Refer to Table 7-1 and Section 8 for full Service

settings parameters listing.

2.

Tap ‘Installation controller’

3.

Swiping the Touchscreen display scroll down to the

desired circuit and select by tapping. (Refer to Figure

7-11).

4.

Swiping the touchscreen display scroll down to

‘Circuit stop from Preset temp’. Tap the icon to switch

on. (Refer to Figure 7-13).

! NOTE !
‘Pump only’ will need to be enabled. If a mixer is installed, ‘Circuit stop from preset temp’ will not be available.

Page 28

Section 7: Touchscreen Display Operation and Settings

Circuit 2 Circuit Support

Circuit Name

Upstairs Rads

Circuit type

Radiators

Pump Only

Circuit stop from preset temp

Heating circuit

Figure 7-13: Edit Circuit 2 settings
Tap the < button to navigate backwards to the home screen.
Irrespective of whether pipe sensors are used or not, the space heating performance can be adjusted based on user comfort levels using either the Smart controller or via ecoNET24. (Refer to Section 6.3.2 for Heating curve adjustment guidance)

7.9 USER SETTINGS MENU
User settings can be accessed via the settings menu from the touchscreen display. (Refer to Figure and Table 7-1 and Figure 7-14).

Time

User settings

Date Panel address

04.10.2024 100

Tapping the radio icon symbol (Refer to Figure 7-14): · ecoNET configuration wizard – Wizard configuration of the
Wi-Fi Hub. · ecoNET status – LAN – connection status of Wi-Fi and
ecoNET web services · Wi-Fi settings – configuration of connection with Wi-Fi Hub.
Connection of Wi-Fi and its configuration is described in this manual. Parameters that should be set by the user: SSID, Security type and network access password.
i Tapping the symbol (Refer to Figure 7-14):
· Displays diagnostic information about the operation of the controller, Alarms list, Firmware version and updating (e.g., serial number) UID and ISM .
7.10 STORED SYSTEM SETTINGS
The Grant Aerona Smart controller can store and recall a default system setting scheme within its memory. Once the system has been installed and commissioned the applied settings (including demand schedules and Legionella protection) can be stored within the Grant Aerona Smart controller. This can be recalled if a setting is perhaps inadvertently changed causing issues with the system.
7.10.1 SAVE A SYSTEM DEFAULT To store the currently set system as a default you will need to: 1. Tap the Settings menu and tap ‘Service settings’. Input
the relevant password on the keypad and tap enter. (Password: 0000 – Refer to Section 8). 2. Tap ‘Installation controller’. 3. Swipe the screen to scroll down to the bottom and tap ‘Default settings’. 4. Tap ‘Save current settings as default’.

Language

7.10.2 RESTORE SYSTEM DEFAULT

Parental lock Screen brightness

100%

To restore the currently saved default to the Smart Controller:
1. Tap the Settings menu and tap ‘Service settings’. Input the relevant password on the keypad and tap enter. (Password: 0000 – Refer to Section 8).

Figure 7-14: User settings menu

2. Tap ‘Installation controller’.

3. Swipe the screen to scroll down to the bottom and tap

·

Time – Time will synchronise with paired thermostats.

‘Default settings’.

·

Date

4. Tap ‘Restore default’.

·

Panel Address

·

Language – Menu language selection.

Any paired thermostats will need to be re-paired after a system

·

Parental Lock – The lock will activate after 5 minutes of default has been restored. The memory will clear if unpowered for

inactivity. Unlocking the screen is possible after pressing an extended period of time.

down the screen for 5 seconds.

·

Screen Brightness

·

Screen saver – Choose screen saver display: None,

Empty, Time, Time and Temps.

·

Time to screen saver on

·

Brightness in screen saver.

·

Alarm sound – Enable/Disable Alarm sounds.

·

Key sound – Enable/Disable Key sounds.

·

Panel temperature correction.

! NOTE !

The temperature in the room should be measured with an additional temperature sensor and the difference between this measurement and the temperature value displayed by the Touchscreen display should be entered into the value of this parameter.

Section 7: Touchscreen Display Operation and Settings

Page 29

Section 8: Service Settings – Installer

Page 30

Service Settings (Password: 0000) Installation control System configuration creator Alarm list
Weather sensor External temp. sensor support Temp. sensor source SUMMER mode activation temperature WINTER mode activation temperature
Main heat source DHW temp. correction Circuit temp. Correction Set-point temp. correction ­ heating
Heaters Buffer heater DHW heater
Flow meter Flow meter Specific Heat capacity Time detect* Time alarm erase* No flow detection threshold* No flow detection hyst.* Pulse rate Pulse counting time* Too often alarm*

Installation control Manual control
Weather sensor Hydraulic scheme Main heat source Buffer settings* Low Loss Header settings* DHW settings Circulation settings* Circuit 1-3 Heaters Flow meter* Additional Modules Default settings

Buffer settings Buffer operation type Preset temperature Preset temperature hysteresis Heating installation start temp.
Low Loss Header settings Additional temp. sensor Water preset temperature Preset temperature hysteresis
DHW settings DHW support
Circulation settings Circulation support Circulation operation time Circulation pause time Start from temperature Pump start temperature
Default settings Restore default settings Save current settings as default

Circuit 1 Circuit support Circuit name Regulation method Work mode Heating circuit Fixed preset water temperature Decreasing fixed water temperature Heating Curve Decrease water temperature Thermostat Room temperature correction Thermostat pump blockade*
Circuit 2&3 Circuit support Circuit name Circuit type Pump only Circuit stop from preset Temp. Heating circuit Regulation method Work mode Decrease water temperature Minimal Temp. Maximum Temp. Heating curve Thermostat Room temperature correction Thermostat pump blockade Valve Opening Time (UFH) Mixer deadband zone (UFH) Proportional range (UFH) Intergration time constant (UFH)

Figure 8-1: System settings menu map

! NOTE !
Items within the menu will change depending on configured system.

8 Service Settings – Installer

8.1 SERVICE SETTINGS

Parameter

Description

Installation control Top level menu function (See previous page)

System configuration The creator assists with the configuration of the parameters of the controller when it is started. Depending how you answer

creator

each question, subsequent questions about the parameters may differ. (Refer to Section 6)

Note: All parameters in the creator are available in the service menu.

Alarm list

Displays a list of alarms reported by the controller.

Manual control

The manual control menu enables activation of individual heating system components to conduct operation tests. Turning on or off particular selected device is done by tapping the symbol on the screen. Note: the controller does not check protection logic, so this menu should be used with awareness of starting outputs in order to avoid damaging the controller and devices connected to its terminals. Long and uncontrolled operation of devices (e.g., pumps) may result in damage.

Manual Control

MOD A

13 14 LN 230V 1

15 16 LN 230V 2

17 18 LN 230V 3

19 20 230V

21 22 NO

345

LN L

230V

ON

OFF

2

67 8

LN L

230V

ON

OFF

3

9 10
NL 230V

11 12 NO

Weather sensor
Hydraulic Scheme Main heat source
Buffer settings (if selected)
Low Loss Header settings (if selected)
DHW settings
Circulation settings (DHW) We do not recommend the use of Secondary circutlation in domestic installations.

Figure 8-2: Manual Control
The menu contains settings for an weather external sensor. · External temp. sensor support – enabling or disabling support for the external (weather) temperature sensor. · Temp. sensor source – selection of external temperature sensor depending on its connection: ecoMULTI, Heat pump. · Summer mode activation temperature – ambient temperature at which summer mode is activated. · Winter mode activation temperature – ambient temperature at which summer mode is deactivated.
Selection of a supported hydraulic system scheme for the heat pump. Options: Direct, Buffer, Low Loss Header.
This menu contains settings related to the heat pump. · DHW temp. correction – increase of the target DHW temperature in heating mode. · Circuit temp. correction – Adjustable Circuit temperature correction value. · Set-point temp correction ­ heating ­ increase of the target heat pump temperature in heating mode.
This menu contains settings for the heat buffer. · Buffer operation type – selection of the number of sensors with which the buffer will work. To choose from: One sensor,
Two sensors. · Preset temperature – Target buffer temperature value. · Preset temperature hysteresis – Temperature value drop from preset temperature at which the buffer is heated. · Heating installation start temp. – Temperature value at which the circuit pumps will be switched on.
This menu relates to settings for a Low Loss Header. · Additional temp. sensor ­ Enable Low Loss Header temperature sensor connected to the controller (lower buffer
temperature sensor). If the operation is switched off, the temperature value is measured on the return. · Preset temperature ­ Target temperature of water in the Low Loss Header. · Preset water hysteresis ­ Temperature value drop from preset temperature at which the Low Loss Header is heated.
This menu relates to settings for the DHW cylinder.
· DHW Cylinder ­ enable/disable DHW cylinder
This menu contains parameters related to the operation of a DHW secondary circulation pump. · Circulation support – turn on/off Secondary circulation support. · Circulation operation time – the DHW circulation pump operation time. It determines the working time after a break in the
circulation pump operation. The DHW circulation pump operates periodically. · Circulation pause time – the DHW circulation pump pause time. Defines the time interval between activations of the
circulation pump. The DHW circulation pump operates periodically. · Start from temperature – activation or deactivation of the circulation pump operation depending on the DHW cylinder
temperature. · Pump start temperature – in order to save energy, the circulation pump will be turned off when the temperature of the
DHW cylinder is lower than the Pump start temp.

! NOTE !
When configuring the system for the first time, it is recommended to use the system configuration creator.
Section 8: Service Settings – Installer

! NOTE !
During the initial setup the smart controller disables support for all heating circuits, DHW cylinder, buffer, and circulation pumps. Depending on the hydraulic system used, these circuits must be turned on.
Page 31

Parameter Circuit 1
Circuit 2 & 3 Heaters Flow meter Default Settings

Description
This menu contains parameters related to operating the non-adjustable circuit. The non-adjustable circuit 1 preset temperature will be automatically increased in order to guarantee heat for adjustable circuits 2 and 3.
· Circuit support – turn on or off circuit support. · Circuit name – name of the circuit set by user.
· Circuit type – This menu contains parameters related to selecting the type of a non-adjustable circuit. – Radiators – Fan-coil
· Regulation Method – Fixed – constant set temperature of water in the non-adjustable circuit is maintained.
– Weather – Water temperature is related to Outdoor weather sensor. Outdoor weather sensor required
· Work Mode
– OFF
– Day ­ setting higher target circuit temperature.
– Night ­ setting lower target circuit temperature.
– Schedule ­ Day or Night mode is set depending on the time schedule.
· Heating circuit – switching the Heating Circuit On/Off. · Fixed preset water temperature – Heat pump stops when fixed preset water temperature is reached. · Decreasing fixed water temperature – If Regulation method is fixed value of temperature decrease for night mode. · Heating Curve – View and adjust the heating curve for the circuit if the circuit is weather compensated
· Decrease water temperature – Flow temperature drop when in night mode if the circuit is weather compensated.
· Thermostat – Thermostat in control of circuit. Assignable options: None, Room panel, Wireless thermostat, Wired thermostat.
· Room temperature correction ­ with thermostat support enabled automatic correction of room temperature is carried out in accordance with the following formula:
– Target temperature with correction = Target temperature of the circuit + (Target temperature of the thermostat assigned to the circuit minus Current temperature of the thermostat assigned to the circuit) x Room temperature correction.
– By default, the Room temperature correction value is 4.0, and the value range is 0 – 10. It is necessary to find appropriate value of the Room temperature correction. The higher the coefficient, the greater the correction of target circuit temperature. If the setting is “0”, the target circuit temperature is not corrected. Note: setting a value of the room temperature coefficient too high may cause cyclical fluctuations of the room temperature.
· Thermostat Pump Blockade – Parameters for the circuit pump being disabled when a room thermostat is active for the circuit. Refer to Section 7.8. – OFF – When the target air temperature is met or exceeded, the circuit pump is not disabled. – ON – When the target air temperature is met or exceeded, the circuit pump is disabled.
Circuit 2 & 3 contain similar functions to Circuit 1 and are dynamic based on the configured system. Below are additional options for Circuit 2 and 3. · Circuit type – This menu contains parameters related to selecting the type of a adjustable circuit.
– Radiators – Fan-coil – Underfloor heating · Pump only – Enables or disables the mixing function on the circuit. – No ­ The circuit is mixer controlled. (Options for Mixer setup will be available in the Circuit menu) – Yes ­ The circuit is not mixer controlled. (Circuit stop from preset temp will become active). · Circuit stop from preset temp – Parameters for a circuit pump being disabled based on water temperature values. – No ­ When the target water temperature value is exceeded, the circuit pump/valve is not disabled. – Yes ­ when the target water temperature value is exceeded, the circuit pump/valve is disabled. · Minimum temperature – Minimum target water temperature in the adjustable circuit. · Maximum temperature – Maximum target water temperature in the adjustable circuit. If the Maximum temperature is greater than 60°C, the controller will take 60°C as a maximum value. · Valve opening time – The time between fully open and closed on installed mixing valve. · Mixer deadband zone – Temperature insensitivity of mixer adjustment. · Proportional Range – Mixer actuator proportional movement. · Integration time constant – Time for actuator reaction for temperature deviation.
This menu contains parameters related to the operation of the DHW heater and buffer heater support. · Buffer heater – enabling or disabling the buffer heater support. · Buffer heater (delay) – delay time for switching on the buffer heater after a heat pump demand. · DHW heater – enabling or disabling the DHW heater support. Output to Smart Immersion Relay. Refer to · DHW heater (delay) – delay time for DHW heater ON from DHW demand start. The options below apply to both buffer and/or DHW heater support when configured. · Outside temp to activate the heater – external temperature value beyond which the DHW heater will be activated. · Outside temp force the heater – external temperature value at which the heater support will be permanently switched on
during heat pump operation.
This menu contains parameters related to the operation of the flow meter operation and the detection of no flow. Refer to Appendix E. · Flow meter – Flow detection is performed by selected option. (Default/Pulse) · Default flow meter – default flow in the circuit, when exceeded, a no-flow alarm will be reported. · Specific Heat Capacity – Coefficient of liquid used to transfer heat. · Time detect – time after which the no-flow alarm will be reported. · Time alarm erase – time after which the no-flow alarm will be reset. The controller will not report an alarm. · No flow detection threshold – flow value below which the alarm “Flow error” will be reported. · No flow detection hysteresis – if the actual flow rises above the value of No flow detection threshold plus No flow detection
hysteresis, the “Flow error” alarm will be turned off. · Pulse rate – Flow sensor pulse rate to calculate flow. · Pulse counting time – Flow sensor pulse count time duration. · Too often alarm – too frequent no-flow alarm detection threshold. It allows to limit the frequent reporting of the no-flow
alarm.
This menu saves and recalls stored defaults applied by the consumer.
· Restore default settings – Recall and apply saved default settings.
· Save current settings as default – Saves the current setup of the Grant Aerona Smart controller to memory.

Page 32

Section 8: Service Settings – Installer

9 Heat Pump Parameters – Installer

01 Read Only Values 00 Primary return temp 01 Compressor frequency 02 Discharge temp 03 Power input (Watts) 05 Defrost sensor 06 Ambient Air temp (HP) 08 Suction temp 09 Primary Flow temp 19 Low tariff and Night mode 32 Ambient temp (Ext) 33 Buffer/LLH temp
41 Heat Pump Settings 00 HP OnOff Based on 22 Delay Pump from Comp Off 23 Delay Comp from Pump on 30 Max Flow Temp 32 Attempts to Target Temp 33 Max Ambient Limits 34 Min Ambient limits 35 Flow Set Point Limit

Heat Pump Settings Service Settings (Password 1234) 01 Read Only Values 21 Heat Pump Set Points 31 DHW 41 Heat Pump Settings 42 Water Pump Settings 43 Frost Protection 46 Back-up Heater 51 Relay Output Settings

21 Heat Pump Set Points 00 Weather Comp On/Off 01 Max target Flow Temp 41 Off to On Hys (01 or 02)
31 DHW 01 DHW production type 21 Max time for DHW 22 Min time for heating
46 Back-up Heater 00 Back up Heater function 01 Manual Set Point 02 Hys Man Set Point 04 Heat Act Delay Time 05 Intergration Time 10 Condition For Heater 11 Amb For Heater – Dis Comp 12 Hys for 4611 13 Amb For Heater Supp Mode 14 Hys For 4613 20 Freeze Prot Func

42 Water Pump Settings 00 HP Water Pump 03 Pump off from Comp off 20 Ext. Pump Control

43 Frost Protection 00 Frost Room Temp 01 Start Temp 02 Hys of Room Temp 03 Water Temp 04 Delay Pump Off 10 Frost Ambient Temp 11 Start Temp 12 Hys of Ambient Temp 13 Back-up Heater Set Point 14 Hys of Flow Temp 20 Frost Flow Temp 21 Start Temp 22 Hys of Flow Temp 30 Frost Cylinder Temp 31 Start Temp 32 Hys of Cylinder Temp 40 Frost Secondary System

Figure 9-1: Heat pump parameters menu

Section 9: Heat Pump Parameters – Installer

51 Relay Output Settings 01 Remote Controller 04 3-Way Mixing Valve 07 DHW Cylinder Sensor 09 Amb Temp Ext Sensor 11 Buffer Temp Sensor 13 Mix Temp Sensor 15 Modbus 17 Humidity Sensor 19 DHW Remote Contact 20 SH Remote Contact 22 Dual Set Point 24 Heat/Cool Contact 26 Flow Switch 28 Night Mode 30 Low Tariff 41 Ext Heat Source 43 Heat/Cool Mode Output 45 Dehumidifier 46 DHW/Back-up Heater 47 Alarm Output 48 Pump 1 – Zone 1 49 Pump 2 – Zone 2 50 DHW 3-Port Valve

Page 33

Parameter 01 Read only Values 21 Heat Pump Set Points 31 DHW 41 Heat Pump Settings
42 Water Pump Settings 43 Frost Protection
46 Backup Heater
51 Relay Output settings

Description
Heat Pump operating conditions – Displayed information directly from the Heat pump.
21 00 – Enable/Disable Weather Compensation on Heat Pump (Do not enable) 21 01 – Setting for the Maximum Target Flow temperature (Smart controller adjusts automatically) 21 41 – Hysteresis set point to enable the Heat pump
31 01 – Heat pump priority on DHW demand 31 21 – Max time the Heat pump can run for a DHW demand 31 22 – Minimum time for a Space heating demand
41 00 – Heat Pump control based on selected set point 41 22 – Delay time for Pump off after compressor off 41 23 – Delay time for Compressor on after Pump on 41 30 – Maximum Flow temperature set point for Heating and DHW 41 32 – Set the max number of attempts for Heat pump to reach target temperature 41 33 – Maximum ambient temperature at which the Heat pump will operate 41 34 – Minimum Ambient temperature at which the Heat pump will operate 41 35 – Flow set point limits
42 00 – Operation settings of Water pump 42 03 – Delay time of Water pump OFF from Compressor OFF 42 20 – Operation settings for an external secondary Water pump
43 00 – Frost Detection based on room temperature 43 01 – Start Temperature set point for frost protection based on room temperature 43 02 – Hysteresis of room temperature to activate frost protection based on room temperature 43 03 – Temperature set point of circulated water 43 04 – Time delay for water pump to be deactivated on frost protection end 43 10 – Frost detection based on ambient temperature 43 11 – Start temperature for Frost protection on Ambient Temperature 43 12 – Hysteresis of Ambient temperature 43 13 – Temperature Set point for Back-Up Heater 43 14 – Flow Temperature Hysteresis 43 20 – Enable/Disable Frost protection on Outgoing flow temperature 43 21 – Start Temperature for 43 20 43 22 – Hysteresis of 43 20 43 30 – Enable/Disable Frost protection on DHW Cylinder temperature 43 31 – Start temperature for 43 30 43 32 – Hysteresis for 43 30 43 40 – Frost Secondary System – Frost Protection for a slave heat pump connected in cascade.
46 00 – Enable/Disable Back-up Heater 46 01 – Back-up Heater Temperature Set point 46 02 – Hysteresis for Back-up Heater cylinder 46 04 – Delay time for Back-up Heater activation 46 05 – Intergration time for starting the heater 46 10 – Power condition of Back-up Heater 46 11 – Ambient temperature for enabling Heater & Disable compressor 46 12 – Hysteresis for 46 11 46 13 – Ambient temperature to activate Heater Supplementary mode 46 14 – Hysteresis for 46-13 46 20 – Enable/Disable Freeze Protection Function
Enable/Disable Heat Pump terminal PCB relays as listed – Refer to Figure 9-1

Page 34

Section 9: Heat Pump Parameters – Installer

10 Wi-Fi Hub

10.1 GENERAL
The Wi-Fi hub enables the Grant Aerona Smart Controller to be accessed and operated remotely via the Internet or app. Users can monitor the operation of the Grant Aerona Smart controller and modify some operation parameters with the use of a computer, Tablet or mobile phone. Essential features of the module include:
· Communication with econet24.com external server provides access to Smart Controller via Internet.
· Support Wi-Fi wireless network access.
· Preview of the current operation parameters of the Smart Controller in readable and clear “tiles”.
· Visual diagrams indicating current operation of the installed hydraulic system.
· Preview and edit options of most user and service parameters of the controller.
· Registration of operation parameters and alarm conditions of the controller.
· E-mail notifications of alarm conditions of the main controller.
The mobile app is available from Google play or IOS store and can be downloaded using the QR codes below.

After the power is on, hub requires approx. 1 minute in order to load the operational system. The module will then indicate its condition via the LED. In a connection between hub with a main controller is active, a ” connection with controller” indicator lights up.
LED indicators
Power Connection to Controller WiFi Connection Connection with Server
Serial No.
Manufactured

ecoLINK2

WPS/RESET

ecoNET.apk (Android) ecoNET.app (IOS)
10.2 CONNECTION TO WIRING CENTRE
The hub has to be connected with G3 socket on the wiring centre with the use of ecoLINK interfacecable. The ecoLINK interface cable and adapter are a part of the Wi-Fi hub set within your Grant Aerona Smart controller kit.

Figure 10-3: Web Module

Table 10-1: LED description

LED

ON/OFF Condition

Status of Power.

Active connection to the Aerona Smart Controller.

3G WISP AP 3 G USB
+5V D+ D-
GND

WAN LAN

POWER

USB

ecoLINK

Power

Connection to Wireless Network Connection to ecoNET24 external server

Figure 10-1: ecoLink Cable connection
10.3 CONNECTION WITH INTERNET
Connect the power adapter plug to thr mini USB Port socket and 3G USB Port to the ecoLINK interface. A Ethernet cable will be required between the RJ45 Ethernet Port and ADSL router, switch and modem. The ethernet cable does not have to be used if connected via Wi-Fi wireless network access.
Mode Switch RJ45 Ethernet Port mini USB Port 3G USB Port

! NOTE !
The Wi-Fi hub requires active DHCP server connection. Manual IP assignment for the hub is not supported.
Wi-Fi access parameters will need to be entered into the touchscreen display via the User settings menu for the hub to be able to make a wireless connection. (Refer to Section 7.9)

3G WISP AP
3G USB

WAN LAN

POWER

Figure 10-2: Connection ports The Mode Switch can be set in any position.
Section 10: Wi-Fi Hub

Page 35

10.4 ECONET24
The Wi-Fi hub connects to ecoNET24 via an external server connection. This provides access to the controller via the Internet.
You will need an account to log into the the external server, visit www.econet24.com on a web browser to register.

3. Tap the information icon at the bottom. Refer to Figure 10-6.
User settings Diagnostic info

10.4.1 FIRST CONNECTION Ensure the Wi-Fi hub will need is connected to the Internet and connected with the external server (‘Server connection’ LED indicator is active). The device UID (which is obtained via User settings menu in Device Diagnostics) will be needed as part of the registration process. Refer to Section 10.4.2 for details. On a web browser visit www.econet24.com. When registering you will be prompted to validate the device UID. If the system correctly validates the UID number, the registration will progress. Complete the form with the data of the user. · Controller UID · Controller label ­ enter any name for the Smart Controller. · Remote access to the controller ­ enables remote access to
view and edit controller parameters. · Controller installation address ­ check that the Smart
Controller address is the same as residential address. · Alarm notifications ­ E-mail notifications of alarms can be
sent to a designated address.
! NOTE !
To use the app you will need to register via Website first.
For a reminder of a password for an existing account, select FORGOT PASSWORD and enter your email. A password reminder will be sent to your email account.

Alarm list Firmware version Firmware update
Figure 10-6: Controller information options. 4. Then tap ‘Firmware version’. Refer to Figure 10-7.
Firmware version
Panel S002.11 h1.0.0 C14.01.05 Controller S002.04 h2.3.0 Serial number 1234567890
UID 12ABCDEF456GHIJ78KL9MNP ISM
Figure 10-7 Firmware version and UID.

10.4.2 HOW TO OBTAIN THE UID Follow the steps to obtain the UID. 1. When the heating circuit control interface is shown (see
figure 7-1), tap settings menu. Refer to Table 7-1 and Figure 10-4.

User settings

10.4.3 RESTORING TO DEFAULT
If you should experience any issues during setup or the user forgets their details for logging in the Wi-Fi hub, it is possible to restore default data with the use of the WPS/Reset button on the hub housing.
· Push and hold WPS/RESET for at least 10 seconds.
· Release the WPS/RESET button. LED indicator above should flash several times.
· Wait for approx. 2 minutes.
· The hub will automatically start up and connect with the Internet using default username and password.

Service settings

! NOTE !
Default username: admin, password: admin

Figure 10-4: Settings selection. 2. Then tap the User settings. Refer to Figure 10-5.

Time

User settings

Date

Panel address

Language

Parental lock

Screen brightness

04.10.2024 100
100%

Figure 10-5: User settings menu.

Page 36

Section 10: Wi-Fi Hub

11 Servicing
11.1 COMPONENT REPLACEMENT
11.1.1 MAIN FUSE The main fuse is located under the wiring centre cover, next to the terminals on the high-voltage side. This is a 250V 5 x 20mm 6.3A ‘T’ type AC fuse. A spare fuse is located under the cover of the wiring centre on the low-voltage terminals side.

Fuse 5×20

Figure 11-1 Mains fuse replacement
In order to remove fuse lift fuse holder with flat-blade screwdriver and pull out the fuse. Refer to Figure 11-1.

11.1.2 TOUCHSCREEN DISPLAY REPLACEMENT
When replacing the touchscreen display make sure that its software is compatible with software in the wiring centre. The compatibility is kept if the first number of software in the touchscreen display and wiring centre are the same.

11.1.3 WIRING CENTRE REPLACEMENT Requirements are analogous to the control panel.

11.2 ACCESSORIES & SPARE PARTS
Grant UK offer the individual components to the Smart Controller system should the need arise.

Table 11-1: Accessories & Spare Parts List

Part Code

Item

HPIDSMARTWRTR Wireless thermostat (with receiver)

HPIDSMARTWRT

Wireless thermostat (no receiver)

HPIDSMARTRECEIVER Wireless thermostat receiver

HPIDSMARTHRT

Wired thermostat

HPIDSMARTSEN2

Water temperature sensor with 2m cable*

HPIDSMARTSEN4

Water temperature sensor with 4m cable*

HPIDSMARTWSEN Outdoor Weather Sensor*

HPIDSMARTFLO

Smart Flow sensor**

HPIDSMARTIMM

Immersion Heater Relay**

HPIDSMARTHUB

Smart Controller Wi-Fi Hub*

HPID120

3-Port Diverter valve

HPID122

3-Port Valve body**

HPID123

Motorised valve actuator**

* – supplied as part of Aerona Smart controller kit ** – supplied as part of a Aerona Smart controller installation pack

Section 11: Servicing

Page 37

12 EC Declarations of Conformity

UKCA – Safety Declaration of Conformity
This declaration is made under the sole responsibility of the following Manufacturer. The Manufacturer declares that the following product conforms to the requirements of the UK Legislation and Regulations as detailed below. The Technical Construction Files are retained at the Manufacturer’s location.
Product: Grant Smart Controls Model: GRANTSMARTCONKIT
In accordance with the following directive(s) or Regulation(s), provided that the products are installed and used in accordance with our instructions:
S.I. 2016/1101: Electrical Equipment (Safety) Regulations 2016 S.I. 2016/1091: Electromagnetic Compatibility Regulations 2016 S.I. 2012/3032: The Restriction of the Use of Certain Hazardous Substances in Electrical
and Electronic Equipment Regulations 2012

following the provisions of:
BS EN 60730-2-9:2010 BS EN 660730-1:2016-A1:2019 BS EN 50581: 2012
Place of Issue Date of issue

United Kingdom 13 December 2023

Technical File Compiler and Authorised Signatory

Page 38

Neil Sawers Commercial Technical Manager

Grant Engineering (UK) Ltd
Frankland Road | Blagrove | Swindon |SN5 8YG
+44(0)1380 736920 | info@grantuk.com |www.grantuk.com

REGISTERED IN ENGLAND No: 3196757. REGISTERED OFFICE: AS ABOVE

GUK13122023 UKCA DoC GSCK

Section 12: EC Declarations of Conformity

13 Health and Safety Information
13.1 GENERAL
The Health and Safety information given in this Section relates to the Grant Aerona smart controller only. For details of the Health and Safety Information for the heat pump, refer to Section 14 of the Aerona³ installation and servicing instructions supplied. For details of the Health and Safety Information for any other heating appliances being used, refer to the instructions supplied with the appliance. Under the Consumer Protection Act 1987 and Section 6 of the Health & Safety at Work Act 1974, we are required to provide information on substances hazardous to health (COSHH Regulations 1988).
14 Disposal and Recycling
14.1 DIRECTIVE WEEE 2012/19/EU
Purchased product is designed and made of materials of the highest quality. The product meets the requirements of the Directive 2012/19/ EU of 4 July 2012 on waste electrical and electronic equipment (WEEE), according to which it is marked by the symbol of crossed-out wheeled bin (like below), meaning that product is subjected to separate collection. Responsibilities after finishing a period of using product: · Dispose of the packaging and product at the end of their
period of use in an appropriate recycling facility, · Do not dispose of the product with other unsorted waste, · Do not burn the product. · By complying with the above obligations of controlled
disposal of waste electrical and electronic equipment, you avoid harmful impact on the natural environment and threats to human health.

Section 13: Health and Safety Information and Section 14: Disposal and Recycling

Page 39

15 Guarantee

You are now the proud owner of an Aerona Smart Controller for use with the Grant Aerona Air Source Heat Pump which has been designed to give years of reliable, trouble free operation.
Grant Engineering (UK) Limited guarantees the manufacture of the Aerona Smart Controller including all electrical and mechanical components supplied with it for a period of twelve months from the date of installation, provided that the Smart Controller and the air source heat pump with which it is being used have been installed in full accordance with the installation and servicing instructions issued.
This will be extended to a total period of two years if the Smart Controller is registered with Grant Engineering (UK) Limited within thirty days of installation, and it is checked, along with the associated valves, sensors, etc. when the heat pump is serviced at twelve monthly intervals³. See main Terms and Conditions below.
Registering the product with Grant Engineering (UK) Limited
Please register your Smart Controller with Grant Engineering UK Limited within thirty days of installation. To do so visit www.grantuk.com and click the ‘Register Product’ link in the top right-hand corner of the home page, where you can register your Smart Controller for a further twelve months guarantee (giving two years from the date of installation). This does not affect your statutory rights¹.
If a fault or defect occurs within the manufacturer’s guarantee period
If your Smart Controller should fail within the guarantee period, you must contact Grant Engineering (UK) Limited, who will arrange for the repair under the terms of the guarantee, providing that the Smart Controller and the heat pump with which it is being used have been correctly installed, commissioned and serviced (if the appliance has been installed for more than twelve months) by a competent person and the fault is not due to tampering, system water contamination, misuse, trapped air or the failure of any external components not supplied by Grant Engineering (UK) Limited, e.g. pipework, etc.
This two-year guarantee only applies if the Smart Controller is registered with Grant Engineering (UK) Limited within thirty days of installation and is checked along with the associated valves, sensors, etc. when the heat pump is serviced after twelve months.
In the first instance Contact your installer or commissioning engineer to ensure that the fault does not lie with the system components, discharged batteries in wireless thermostats, or any incorrect settings of the Smart Controller that falls outside of the manufacturer’s guarantee otherwise a service charge could result. Grant Engineering (UK) Limited will not be liable for any charges arising from this process.
If a fault covered by the manufacturer’s guarantee is found
Ask your installer to contact Grant Engineering (UK) Limited, Service Department on +44 (0)1380 736920 who will arrange for a competent service engineer to attend to the fault.
Remember – before you contact Grant Engineering (UK) Limited
Ensure the Smart Controller and the air source heat pump with which it is being used have been installed, commissioned and serviced by a competent person in accordance with the installation and servicing instructions.
Ensure the problem is not being caused by the heating system, discharged batteries in wireless thermostats, or any incorrect settings of the controls.

Free of charge repairs
During the two year guarantee period no charge for parts of labour will be made, provided that the Smart Controller and the air source heat pump with which it is being used have been installed and commissioned correctly in accordance with the manufacturer’s installation and servicing instructions, it was registered with Grant Engineering (UK) Limited within thirty days of installation and, for Smart Controllers and air source heat pumps over twelve months old, details of annual service is available³.
The following documents must be made available to Grant Engineering (UK) Limited on request:
· Proof of purchase
· Commissioning Report Form
· Service documents
· System Design Criteria
Chargeable repairs
A charge may be made (if necessary following testing of parts) if the cause of the breakdown is due to any fault(s) caused by the plumbing or heating system, e.g. contamination of parts due to system contamination, sludge, scale, debris or trapped air. See ‘Extent of manufacturer’s guarantee’ below.
Extent of manufacturer’s guarantee:
The manufacturer’s guarantee does NOT cover the following:
· If the Smart Controller has been installed for over two years.
· If the Smart Controller and/or the air source heat pump with which it is being used have not been installed, commissioning, or serviced by a competent person in accordance with the installation and servicing instructions.
· The serial number has been removed or made illegible.
· Fault(s) due to accidental damage, tampering, unauthorized adjustment, neglect, misuse or operating the Smart Controller and/or the air source heat pump contrary to the manufacturer’s installation and servicing instructions.
· Damage due to external causes such us bad weather conditions (flood, storms, lightning), fire, explosion, accident or theft.
· Fault(s) due to incorrectly sized expansion vessel(s), incorrect vessel charge pressure or inadequate expansion on the system.
· Fault(s) caused by external electrics and external components not supplied by Grant Engineering (UK) Limited.
· Air source heat pump servicing, de-scaling or flushing.
· Checking and replenishing system pressure.
· Electrical cables and plugs, external controls not supplied by Grant Engineering (UK) Limited.
· Heating system components, such as radiators, pipes, fittings, pumps and valves not supplied by Grant Engineering (UK) Limited.
· Instances where the Smart Controller has been un-installed and re-installed in another location.
· Use of spare parts not authorised by Grant Engineering (UK) Limited.
· Consumable items including, but not limited to, batteries, antifreeze and biocide inhibitor.
· The replacement of batteries in wireless thermostat.
· The cost and provision of any specialist access equipment, or any associated costs, required to inspect, repair, service or replace any units not installed in accordance with these installation instructions, irrespective of whether the heat pump is deemed to be at fault or not.

Page 40

Section 15: Guarantee

Terms of manufacturer’s guarantee
The Company shall mean Grant Engineering (UK) Limited.
The Smart Controller and the heat pump with which it is being used must be installed by a competent installer and in full accordance with the relevant Codes of Practice, Regulations and Legislation in force at the time of installation.
The Smart Controller is guaranteed for two years from the date of installation, providing that after twelve months the annual service has been completed³ and the heat pump registered with the company withing thirty days of the installation date. Any work undertaken must be authorised by the Company and carried out by a competent service engineer.
Proof is provided that the system has been flushed or chemically cleaned where appropriate (refer to BS 7593) and that the required quantity of a suitable corrosion inhibitor added.
Proof of annual servicing (including the checking of any expansion vessels and pressure relief valves) must be provided if and when requested by the Company.
IMPORTANT Grant Engineering (UK) Limited strongly recommends that a Grant Mag-One in-line magnetic filter/s (or equivalent) is fitted in the heating system pipework. This should be installed and regularly serviced in accordance with the filter manufacturer’s instructions.
This guarantee does not cover breakdowns caused by incorrect installation, neglect, misuse, accident or failure to operate the Smart Controller and/or heat pump in accordance with the manufacturer’s installation and servicing instructions.
The Smart Controller is registered with the Company within thirty days of installation. Failure to do so does not affect your statutory rights¹.
The balance of the guarantee is transferable providing the installation is serviced prior to the dwelling’s new owners taking up residence. Grant Engineering (UK) Limited must be informed of the new owners’s details.
The company will endeavour to provide prompt service in the unlikely event of a problem occurring but cannot be held responsible for any consequences of delay however caused.
This guarantee applies to Grant Engineering (UK) Limited Smart Controllers purchased and installed on the UK mainland, Isle of Wight, Channel Islands and Scottish Isles only². Provision of inguarantee cover elsewhere in the UK is subject to agreement with the company.
All claims under this guarantee must be made to the Company prior to any work being undertaken. Invoices for call out/repair work by any third party will not be accepted unless previously authorised by the Company. Proof of purchase and date of installation, commissioning and service documents must be provided on request.
If a replacement Smart Controller is supplied under the guarantee (due to a manufacturing fault) the product guarantee continues from the installation date of the original Smart Controller and not from the installation date of the replacement.
· The replacement of a Smart Controller under this guarantee does not include any consequential costs.
Foot notes
1. Your statutory rights entitle you to a one-year guarantee period only.
2. The UK mainland consists of England, Scotland and Wales only. Please note that for the purposes of this definition, Northern Ireland, Isle of Man and Scilly Isles are not considered part of the UK mainland.
3. We recommend that your Smart Controller and the air source heat pump with which it is installed are serviced every twelve months (even when the guarantee has expired) to prolong the lifespan and ensure it is operating safely and efficiently.
4. The guarantee period will commence from the date of installation, unless the installation date is more than six months from the date of purchase, in which case the guarantee period will commence six months from the date of purchase.
5. As measured by gauss. The Mag One magnetic filter has a Gauss measurement of 12000.
Version 1.0 – December 2023
Section 15: Guarantee

Page 41

Appendix A Wired Thermostat

A.1 GENERAL
The Grant Wired thermostat is designed to provide individual circuit control via the Grant Aerona Smart Controller.
The thermostat is installed in a suitable location to monitor the circuit, e.g., Ground floor hallway, and is designed to maintain a target temperature.
The thermostat on the backlit LCD display shows information about the circuit temperature value, selected operating mode, current time with simultaneous clock synchronization with the main controller.
A.2 INSTALLATION
The thermostat is intended for installation only in a dry, habitable location and should be mounted to the wall. After choosing the place of installation, make sure that:
· The selected location is free of excessive humidity and the ambient temperature of the thermostat should be within the range of 0 to 40oC,
· The chosen location should ensure free air circulation and should be located away from heat-emitting sources, e.g., electronic equipment, fireplace, heater and direct sunlight.
· The thermostat should be mounted at a height enabling convenient operation, typically 1.5m above the floor. (Refer to Figure 3-1)
The thermostat should be screwed to the wall with mounting screws. Access to the screw holes is obtained by opening and removing the back cover of the thermostat. A flat screwdriver can be used to open the cover.

Before reattaching the cover, lead the wire connecting the thermostat with the wiring centre through the hole. The cable must be recessed into the wall. The cable can not be routed together with the electrical cables of the building. The cable should not run in the vicinity of devices emitting strong electromagnetic fields. Then attach the thermostat to the mounting frame using the clips. The VCC, GND, D+, D- terminals of the thermostat should be connected to the transmission socket of the main controller. Refer to Figure A-3.
! NOTE !
A 4-core cable with a cross-Section of min. 0.5 mm2.
VCC GND
D+ D-

Figure A-3: Wired Thermostat Wiring

! NOTE !
Close attention must be paid to the 4 connections for Voltage, Ground and Polarity. Ensure they match to corresponding wires from touchscreen panel

A.3 THERMOSTAT PANEL

Figure A-1: Wired thermostat back access

The cover is screwed to the selected location of the wall with the appropriate position (UP), as shown in the Figure below. The hole spacing can be determined by attaching the cover to the wall.
UP

12:00
21°c .5

Figure A-2: Wired thermostat wall fixing
Page 42

Figure A-4:Wired (& Wireless) thermostat panel LCD
Appendix A: Wired Thermostat

Table A-1: Wired (& Wireless) theromstat LCD symbols

Symbol

Symbol descirption

Alarm symbol

Schedule – Thermostat is schedule managed

Parameter editing

Heat demand

Radio signal (Wireless Thermostat only)

Low battery indicator (Wireless Thermostat only)

Decrease parameter

Confirm

Increase parameter

A.4 PAIRING
The wired thermostat should be connected as part of the Smart Controller configuration creator for the circuit that the thermostat will measure. To pair again you can follow this within the individual circuit settings to re-pair to the Grant Aerona Smart controller.
· Access the circuit you wish to pair with a wired thermostat panel from the Circuit settings within the System settings menu (Refer to Section 8) and select the Thermostat option from the menu and confirm you wish to overwrite if a thermostat is already present on the circuit.
· The pairing wizard will begin and will instruct you to set put the desired wired thermostat into pairing mode.
· Follow the on-screen prompts. Hold the up and down buttons simultaneously for 2 seconds. The screen will change to display you have entered the user menu where you then select parameter 03 in the user menu of the thermostat. “PAr” will be displayed on the screen. After accepting with button, the pairing will start (the word “PAr” begins to flash).
· Confirmation of the pairing will be confirmed by the message “END” and “Succ” on the thermostat.
· After pairing a room thermostat holding the tick down will return you first to the previous menu and then the back to the main screen in 2 second intervals.
A.5 CHANGING SETPOINT TEMPERATURE
Tapping the up or down arrows will prompt the thermostat into the check/editing of target temperature causing the current target saved temperature to flash. The first tap of the arrow will trigger the edit temperature function but will not change the value. Tapping the arrow again will then change the value either up or down. Tapping the tick will confirm, save and exit.
Not confirming a new target with 5 seconds of inactivity will cause the thermostat to exit the editing mode without changing the target temperature.
! NOTE !
Holding the up or down arrows for more than 2 seconds will cause a fast change to the parameter.

A.6 HOTEL MODE
Hotel mode can disable the wired thermostats ability to change the Smart Controller parameters and schedules. We recommend this be activated to avoid conflicting programmed settings between the wired thermostat and the Grant Aerona Smart controller.
1. To access the service menu press and hold the down arrow and the confirmation tick capacitive buttons for 2 seconds. After which you will need to enter the number sequence 1410 and confirm with the tick.
2. To enter the password you will need to cycle each of the 4 digits with the up or down arrow and confirm that digit with the tick. On the confirmation of the fourth digit you will continue to the service menu.
3. Navigate to parameter 2 and select Hotel mode with the tick. Default setting for hotel mode is off and the arrows will cycle through options. Ensure On is visible and confirm.
4. Holding the tick for 2 seconds will save and exit the menu back to the main screen.

A.7 ERROR CODES
The Grant Aerona Smart controller communicates alerts to the thermostat panels when present in the system. Refer to Table A-2 for determining the fault.

Table A-2: Theromstat alarm codes

Code Alert descirption

1

Outside temperature sensor error

2

1 – No communication with the controller

3

No compatibility of programs

4

3 – Panel temperature sensor error

5

DHW sensor error

6

Upper buffer temperature sensor error

7

6 – Lower buffer temperature sensor error

8

Circuit 2 temperature sensor error

9

Circuit 3 temperature sensor error

10

Anti-freeze active

12

No communication with the thermostat

13

No communication with thermostat circuit 1

14

No communication with thermostat circuit 2

15

No communication with thermostat circuit 3

16

15 – alarm from digital input

17

No flow detected

18

Too often no flow detected

20

19 – No communication with heat pump module

21

Circuit 4 temperature sensor error (not used)

22

Circuit 5 temperature sensor error (not used)

23

Circuit 6 temperature sensor error (not used)

24

Circuit 7 temperature sensor error (not used)

25

No communication with thermostat circuit 4 (not used)

26

No communication with thermostat circuit 5 (not used)

27

No communication with thermostat circuit 6 (not used)

28

No communication with thermostat circuit 7 (not used)

98

Service alarm

100-140 Alarms from heat pump

Appendix A: Wired Thermostat

Page 43

Appendix B Wireless Thermostat and Receiver

B.1 GENERAL
The Grant Wireless receiver & thermostat are designed to provide wireless circuit control via the Grant Aerona Smart controller.
The thermostat should be installed in a suitable location to monitor the circuit, e.g., First floor hallway, and is designed to maintain a target temperature. by sending a radio signal to the module connected to the wireless receiver.
The thermostat on the backlit LCD display shows information about thecircuit temperature value, selected operating mode, current time with simultaneous clock synchronization with the touchscreen display.

P LED D- D+

GND +12V

B.2 INSTALLING WIRELESS RECEIVER
The wireless receiver should be mounted on a wall near the installation location of the wiring centre. If the radio connection is poor, try placing the wireless receiver in other places. Moving the wireless receiver even by a few centimetres can affect the quality of the connection.
! NOTE !
Placing a wireless receiver in a metal casing, e.g. a mounting box, a metal boiler casing, etc. will block the radio signal and thus interfere with the operation.
The radio module should be screwed to the wall with mounting screws. Access to holes for screws is obtained after unscrewing the cover of this module. Refer to Figure B.1.
Screw Hole
Screw

4 x 0.5mm2 wire max length 30m
Figure B-2: Wireless receiver wiring
! NOTE !
Ensure the correct polarity of the connection of the D+, D- signals and the GND, +12V power supply between the thermostat and the wiring centre. Incorrect connection may lead to damage to the main controller or errors in its operation.
The maximum cable length depends on the cross-section of the wires. For a 0.5 mm² wire, it should not exceed 30m. The crossSection should not, however be less than 0.5 mm².

Figure B-1: Wireless receiver wall fixings
Terminals D +, D-, GND, 12VDC of the Wireless receiver should be connected to the G1 socket of the wiring centre.

B.3 WIRELESS THERMOSTAT
The wireless thermostat is intended for installation only in a dry habitable location and should placed on a flat surface (as a freestanding device) in a room representati

Documents / Resources

GRANT Aerona 3 R32 Smart Controller Kit [pdf] Installation Guide
Aerona 3 R32 Smart Controller Kit, Aerona 3 R32, Smart Controller Kit, Controller Kit

References

Leave a comment

Your email address will not be published. Required fields are marked *