GEYA ELECTRICAL GPS8-03 3 Phase Voltage Current Protector

GEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-PRODUCT

Specifications

  • Model: GPS8-03
  • Function: Overvoltage, undervoltage, and overcurrent protection for household equipment
  • Supply Voltage: AC220V (L1, L2, L3-N)
  • Supply Frequency: 45-65Hz
  • Operation Voltage Range: 80V-400V (L1, L2, L3-N)
  • Rated Operational Current: 63A, 80AAC1
  • Burden: AC max. 3VA
  • Mounting: DIN rail
  • Protection Degree: IP40 for front panel/IP20 terminals

Product Usage Instructions

Installation

  1. Locate a suitable spot on the DIN rail for mounting the protector.
  2. Ensure proper wiring connections following the provided wiring diagram.
  3. Check that the supply voltage and frequency fall within the specified ranges.

Setting Parameters

  1. Press and hold the setting key for 3 seconds to enter setting mode.
  2. Use the buttons to increase or decrease parameter values as needed.
  3. After modifying the settings, press and hold for 3 seconds to save the changes.

Manual Reset

If the automatic fault reset function is disabled, press the reset button manually to clear faults.

Operation

  • The protector will monitor voltage and current levels continuously.
  • If any parameter exceeds the set limits, the protector will trigger protection mechanisms.

General

  • Applications
    • Overvoltage,undervoltage and overcurrent protection for household equipment.
  • Function Features
    • Voltage/current (True RMS)monitoring and protection.
    • Use true RMS measurement.
    • Double bus wiring design stronger ability.
    • Over/under voltage value and overcurrent values can be set.
    • Self resets after a fault.
    • Digital display voltage, current value, and fault status can be displayed by an LED.
    • DIN rail mounting.
  • Model and connotationGEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-2

Technical parameters

GEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-1

Panel Diagram

GEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-3

Wiring Diagram

GEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-4

Parameter setting

Parameter Range Step value Factory settings
Overvoltage value OFF,230V~300V 1V 275V
Over-voltage recovery value 225V~295V 1V 265V
Under-voltage value 145V~210V,OFF 1V 175V
Under-voltage recovery value 145V~215V 1V 180V
Voltage fault action time 0.1s~10s 0.1s 0.5s
Over current value OFF,1A~63A,80A 0.1A 60A/80A
Over the current action delay 2s~600s 1s 5s
Voltage unbalance value OFF,20V~99V 1V 40V
Power on delay time 2s~600s 1s 5s
Reset time 2s~900s 1s 30s
Phase sequence ON-OFF   OFF
Fault reset ON-OFF   ON

GEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-5

  • NOTE: Short pressGEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-16 can add and drop parameters, long press can be quickly set. If the 60s do not operate the key, it will exit automatically.
  • You can press and holdGEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-17 for 3 seconds to exit the setup mode and enter the running mode.

Open and close manually

  • Under normal operation, the load can be switched on or off manually by pressing the power key for 0.5 seconds.GEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-6

Phase sequence fault

  • When the phase sequence protection function is turned on, the error of phase sequence access will be prompted as shown in the following figure.GEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-7

Power-on and reset delay

  • During the power-on and fault reset of the product, the product will count down and display according to the set delay time, and will enter the running state when the countdown ends.GEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-8

Functions Diagram

  • Overvol tage or undervoltage faultGEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-9
  • Overcurrent faultGEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-10
  • Voltage unba lance faultGEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-11
  • Tp: Power-up delay(2~600s)
  • Tr: Reset delay time(2~900s)
  • Tu: Over/under voltage fault action time(0.1~10s)
  • Tc: Overcurrent fault action time(2~600s)

Example

GEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-12

  • NOTE: This product does not have an isolation function.
  • Please disconnect the superior MCB during maintenance!!!

Dimensions

(mm)GEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-13

Disposal of Electrical Waste

  • GEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-14All electrical waste should be disposed of in compliance with current WEEE regulations.

GEYA-ELECTRICAL-GPS8-03-3-Phase-Voltage-Current-Protector-FIG-15Caution

  • The products must be installed by qualified electricians.
  • All and any electrical connections of the time relay shall comply with the appropriate safety standards.

CUSTOMER SERVICE

  • GEYA ELECTRICAL CO., LTD
  • Add: Wenzhou Bridge Industrial Zone, Beibaixiang Town, Yueqing, Zhejiang, China 325603
  • Mobile: 008613567770207
  • E-mail: sale@cngeya.com
  • Web: www.geya.net

FAQ

How can I reset the protector manually?

Press the reset button on the device to manually reset it when a fault occurs.

What is the power-up delay time for the protector?

The power-up delay time can be set within the range of 2 to 900 seconds.