GEYA ELECTRICAL GPS8-03 3 Phase Voltage Current Protector
Specifications
- Model: GPS8-03
- Function: Overvoltage, undervoltage, and overcurrent protection for household equipment
- Supply Voltage: AC220V (L1, L2, L3-N)
- Supply Frequency: 45-65Hz
- Operation Voltage Range: 80V-400V (L1, L2, L3-N)
- Rated Operational Current: 63A, 80AAC1
- Burden: AC max. 3VA
- Mounting: DIN rail
- Protection Degree: IP40 for front panel/IP20 terminals
Product Usage Instructions
Installation
- Locate a suitable spot on the DIN rail for mounting the protector.
- Ensure proper wiring connections following the provided wiring diagram.
- Check that the supply voltage and frequency fall within the specified ranges.
Setting Parameters
- Press and hold the setting key for 3 seconds to enter setting mode.
- Use the buttons to increase or decrease parameter values as needed.
- After modifying the settings, press and hold for 3 seconds to save the changes.
Manual Reset
If the automatic fault reset function is disabled, press the reset button manually to clear faults.
Operation
- The protector will monitor voltage and current levels continuously.
- If any parameter exceeds the set limits, the protector will trigger protection mechanisms.
General
- Applications
- Overvoltage,undervoltage and overcurrent protection for household equipment.
- Function Features
- Voltage/current (True RMS)monitoring and protection.
- Use true RMS measurement.
- Double bus wiring design stronger ability.
- Over/under voltage value and overcurrent values can be set.
- Self resets after a fault.
- Digital display voltage, current value, and fault status can be displayed by an LED.
- DIN rail mounting.
- Model and connotation
Technical parameters
Panel Diagram
Wiring Diagram
Parameter setting
Parameter | Range | Step value | Factory settings |
Overvoltage value | OFF,230V~300V | 1V | 275V |
Over-voltage recovery value | 225V~295V | 1V | 265V |
Under-voltage value | 145V~210V,OFF | 1V | 175V |
Under-voltage recovery value | 145V~215V | 1V | 180V |
Voltage fault action time | 0.1s~10s | 0.1s | 0.5s |
Over current value | OFF,1A~63A,80A | 0.1A | 60A/80A |
Over the current action delay | 2s~600s | 1s | 5s |
Voltage unbalance value | OFF,20V~99V | 1V | 40V |
Power on delay time | 2s~600s | 1s | 5s |
Reset time | 2s~900s | 1s | 30s |
Phase sequence | ON-OFF | OFF | |
Fault reset | ON-OFF | ON |
- NOTE: Short press
can add and drop parameters, long press can be quickly set. If the 60s do not operate the key, it will exit automatically.
- You can press and hold
for 3 seconds to exit the setup mode and enter the running mode.
Open and close manually
- Under normal operation, the load can be switched on or off manually by pressing the power key for 0.5 seconds.
Phase sequence fault
- When the phase sequence protection function is turned on, the error of phase sequence access will be prompted as shown in the following figure.
Power-on and reset delay
- During the power-on and fault reset of the product, the product will count down and display according to the set delay time, and will enter the running state when the countdown ends.
Functions Diagram
- Overvol tage or undervoltage fault
- Overcurrent fault
- Voltage unba lance fault
- Tp: Power-up delay(2~600s)
- Tr: Reset delay time(2~900s)
- Tu: Over/under voltage fault action time(0.1~10s)
- Tc: Overcurrent fault action time(2~600s)
Example
- NOTE: This product does not have an isolation function.
- Please disconnect the superior MCB during maintenance!!!
Dimensions
(mm)
Disposal of Electrical Waste
All electrical waste should be disposed of in compliance with current WEEE regulations.
Caution
- The products must be installed by qualified electricians.
- All and any electrical connections of the time relay shall comply with the appropriate safety standards.
CUSTOMER SERVICE
- GEYA ELECTRICAL CO., LTD
- Add: Wenzhou Bridge Industrial Zone, Beibaixiang Town, Yueqing, Zhejiang, China 325603
- Mobile: 008613567770207
- E-mail: sale@cngeya.com
- Web: www.geya.net
FAQ
How can I reset the protector manually?
Press the reset button on the device to manually reset it when a fault occurs.
What is the power-up delay time for the protector?
The power-up delay time can be set within the range of 2 to 900 seconds.