GENEREX CSHXXXXF Current Sensor
Product Usage Instructions
General Safety Precautions:
Cleaning and Decontamination Instructions:
- Power Off and Unplug: Before cleaning or decontaminating, always power off the device and unplug it from any electrical outlets or disconnect it from its power source to avoid the risk of electric shock or damage.
- Use Approved Cleaning Agents: Use cleaning agents that are safe for electronics. Ensure that the solution is applied to the cloth rather than directly onto the device.
Warning and Safety Indication:
- Installation: Installation should be done by qualified personnel only. Service should also be carried out by GENEREX personnel to ensure proper handling.
- Protection Statement: Any usage of the unit not specified by the manufacturer may impair the protection provided by the equipment.
- Environmental Conditions: The equipment is designed for indoor use and should not be directly exposed to outdoor weather conditions such as rain, snow, or extreme temperatures.
- Sensor Connection Information:
The product can be connected to Sensor Manager or other compatible modules using the provided connection diagram. - Contact Information:
If you have any questions or need further assistance, you can contact GENEREX GmbH via phone at +49(40)22692910, email at info@generex.de, or visit their website at www.generex.de. - Sensor Manager / Site Manager:
Analog wiring is required for proper functionality.
General Safety
Precautions
Improper use of the products described in this manual may lead to personal injury and/or property damage. GENEREX is not liable for injuries or damages that result from improper handling of these products. Risks associated with improper use include explosion, fire, and short circuits.
Attention! Battery terminals are always live, so never place metal objects or tools on top of the batteries. Battery electrolyte solutions are highly corrosive. Should you observe leaks of electrolytes from a battery, be aware that these fluids are harmful to both eyes and skin.
Installation, maintenance, and repair of batteries and battery equipment should be performed only by trained specialists (or personnel authorized by battery manufacturers to perform such services). Persons who have not been trained in battery safety or the proper handling of batteries (or who have not been authorized to work on them) must not handle batteries.
Observe the following regulations (IEEE standards USA only):
- ZVEI publication “Instructions for the Safe Handling of Electrolyte for Lead-acid Accumulators.”
- ZVEI publication “Safety Data Sheet on Accumulator Acid (Diluted Sulfuric Acid).”
- VDE 0510 Part 2: 2001-12, in accordance with EN 50272-2:2001: “Safety Requirements for Secondary Batteries and Battery Installations – Part 2: Stationary Batteries”.
- IEEE Standard 450-2002: “Recommended Practice for Maintenance, Testing and
- Replacement of Vented Lead Acid Batteries for Stationary Application.”
- IEEE Standard 1375-1998: “Guide for Protection of Stationary Battery Systems
Observe also the following safety rules:
- Ensure that all electrical loads and power supplies/charging devices (including separators, fuses, and switches) are switched off. This must be carried out by qualified personnel.
- Remove all wristwatches, rings, chains, jewelry, and other metal objects before working with batteries.
- Use insulated tools only.
- Wear insulating rubber gloves and rubber shoes.
- Never place tools or metal components on top of the batteries.
- Make sure that the battery or batteries are not mistakenly grounded. (The consequences of an accidental or incorrect connection can be mitigated and reduced by terminating the ground connection.) If the system is grounded, terminate the connection. Touching a grounded battery by mistake can result in severe electric shock.
- Before establishing connections, make sure to verify polarity. (Better one too many times than one too few.)
- Filled lead-acid batteries contain highly explosive gas (hydrogen/air mixture). Never smoke, handle open flames or create sparks near the batteries. Always avoid electrostatic discharge: wear cotton clothing and ground yourself if necessary.
- Wear the appropriate safety clothing and equipment.
Cleaning and Decontamination Instructions
To ensure the longevity and proper functioning of your device, please follow these cleaning and decontamination guidelines:
- Power Off and Unplug: Before cleaning or decontaminating, always power off the device and unplug it from any electrical outlets or disconnect it from its power source to avoid the risk ofelectric shock or damage.
- Use Approved Cleaning Agents:
- Only use soft, lint-free cloths or microfiber cloths to clean the surface of the device.
- For general cleaning use a dry cloth. Avoid using alcohol, ammonia, or solvents that can damage the surface.
- For decontamination, if required, use a solution recommended by the manufacturer that is safe for electronics. Ensure that the solution is applied to the cloth rather than directly onto the device.
Warning and Safety Indication
Attention | ||
INSTALLATION BY QUALIFIED PERSONNEL ONLY! |
The BACS® installation should only be installed by qualified personnel. BACS® is installed on batteries where high voltages could cause injuries or even death if not handled properly! The BACS® connection cables (temperature cable, bus cable, measuring cable) could be live! To avoid short circuits, do not touch, replace, or cut BACS® cables before disconnecting the charger from the batteries! |
|
Service BY GENEREX PERSONNEL ONLY! |
The BACS® Current sensor can only be serviced by the manufacturer. Do not open the BACS® Current Sensor. Do not attach any kind of objects to the battery or the BACS® Current Sensor apart from the connecting cables! |
|
PROTECTION STATEMENT! |
If the unit is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. |
|
ENVIRONMENTAL CONDITIONS! |
Indoor Use: The equipment is intended for indoor environments, where it will not be directly exposed to outdoor weather conditions such as rain, snow, or extreme temperatures. |
Manufacturer Contact Information
- Germany: GENEREX SYSTEMS GmbH Brunnenkoppel 3 22041 Hamburg
- United States of America: GENEREX SYSTEMS Inc. 18610 Starcreek Dr, Suite D Cornelius, North Carolina 28037
Connection Diagram
Part Number Example
Description & Functions
- The BACS_CSHxxxxF Current Sensor is a measuring unit for the integration into the BACS bus system.
- This unit measures the string current in the negative or rather positive range of a battery circuit and displays the data in Amps.
- The active measuring value will be displayed via the web interface, and the BACS Web manager will show the “BACS Status “of the string. The measuring values will be stored sequentially in the history files, and this data can then be used later for system analysis and performance interpretation by using the BACS Viewer software.
Assembling
The BACS Current Sensor is designed for DIN Rail mounting.
- BACS – Wiring: General Bus Connection (CSHxxx F)
To connect a single BACS current sensor, use a single BACS Bus port. Do not mix up BACS Bus modules with the current sensor. Since the sensor is powered by the BACS Bus, no additional power source is required. - BACS – Daisychain for up to 16 sensors (CSHxxxxF)
- Use a daisy chain to connect other current sensors. The BACS Webmanager, according to the number of configured battery strings:
- Each BACS Webmanager can therefore hold up to 16 current sensors. For structured wiring, the current sensors can also be used with a BACS Bus Splitter in combination with a daisy chain.
- BACS – Circuit wiring and current direction (CSHxxx F)
- Open the hall sensor and place the power cable in the sensor ring. The current sensor is polarity sensitive, so be aware of the sensor’s measuring direction to avoid wrong measurements. A small arrow on the top of the hall sensor shows the correct current flow. We recommend using the + cable only.
SENIOR MANAGER / SITE MANAGER
- Analog wiring
Use the RJ12 – cable to connect the sensor with a Sensor manager or the analog ports of a SITEMANAGER 6 - Analog Daisy Chain (2 devices per port)
Connect the second sensor to the first sensor to use a daisy chain. Please note that only two devices can be connected.
Addressing
The BACS_CSHxxxxF Current Sensor can be addressed via the DIP-Switch:
Address table for the string numbers:
BACS_CSHxxxxF | ||||||
String No.: |
SW 1 |
SW 2 |
SW 3 |
SW 4 |
SW 5 |
Analog AC / DC |
1 | off | off | off | off | – | |
2 | on | off | off | off | – | |
3 | off | on | off | off | – | |
4 | on | on | off | off | – | |
5 | off | off | on | off | – | |
6 | on | off | on | off | – | |
7 | off | on | on | off | – | |
8 | on | on | on | off | – | |
9 | off | off | off | on | – | |
10 | on | off | off | on | – | |
11 | off | on | off | on | – | |
12 | on | on | off | on | – | |
13 | off | off | on | on | – | |
14 | on | off | on | on | – | |
15 | off | on | on | on | – | |
16 | on | on | on | on | – | |
– | – | – | – | – | off | DC |
– | – | – | – | – | on | AC |
The physical address of the sensor is hard-coded and can be changed by setting up the dip switches. To activate the new settings, remove the BACS Bus cable and connect the sensor again. After restart, the new address is assigned and ready to use. To avoid wrong measuring, please check your BACS string setup after changing the sensor address.
Status LED :
When the green LED on the BACS_CSHxxxx Current Sensor flashes, it indicates that power is available. The green LED is constantly on if the device is detected by the BACS manager and measuring values are transferred (normal operation). If the communication with the BACS manager is interrupted, the LED will start flashing after 180 seconds to indicate that there is a communication problem.
Setting up SENIOR MANAGER / SITE MANAGER
- AC / DC measuring selector
Switch SW5 provides the option to select the type of current measurement (AC or DC). - Sensor configuration
The current sensor supplies an analog voltage of 0 – 10V as a measurement result, which must be defined accordingly in the sensor settings.:- At “Name”, assign a unique name of the sensor. This name is then displayed in the sensor monitoring screen.
Offset Settings
- Use the Offset Settings to define the sensor output at 0 amps under the condition that the sensor does not measure any current flow.
- If the sensor shows a deviation at the 0 position, define an offset from the measured value X – 1. The sensor should then display 0 in the sensor monitoring screen.
BACS Configuration
Check the box at “BACS CS Current Sensor Connected “to enable the sensor.
Defining the number of installed sensors
In case of one current sensor only, enable “Only One Current Sensor For All Strings “. If not selected, BACS will assume that the number of strings is the finally the number of current sensors.
Thresholds
Define current must be detected before the sensor reports a charge/discharge cycle in progress.
Defining the threshold levels:
- To enable the threshold function, select the check box accordingly. Jobs for these thresholds can be added to the BACS event handling menu.
- Please ensure that the warning level values are always lower than the alarm level values.
Technical Data and Specifications
BACS CSHxxxxF Current Sensor
Module-Version | Current Sensor | Revision 5.x | |
Power supply | Volt | 12 VDC | |
Power supply | Cable | via bus wiring | |
Current Range | ADC | BACS_CSH50: | +/- 50 ADC |
BACS_CSH200: | +/- 200 ADC | ||
BACS_CSH500: | +/- 500 ADC | ||
BACS_CSH1000: | +/- 1000 ADC | ||
BACS_CSH2000: | +/- 2000 ADC | ||
Measuring accuracy | Resolution | 16 Bit, ±1A, ±2% | |
Current consumption | mA | 90mA | |
Control element | DIP SW | DIP-Switch for the addressing | |
Indicator | Optical | LED for status display | |
Interface | Serial | Optical, isolated 4-pole connection | |
Bus protocol | BACS | Proprietary GENEREX bus protocol, 9600 baud | |
Analog Output range | SM | 0V – 10V → 5V = 0A | |
Temperature | Operation | -10 … +60°C | |
Temperature | Storing | -25 … +85°C | |
Humidity | Rel. % | 0 – 95% not condensated | |
Max. Cable diameter (incl. cable sheath) of the current circuit you want to measure |
mm |
BACS_CSH50: BACS_CSH200 – BACS_CSH2000: | 20mm
40mm |
Dimensions CSHxxxxF | W x H x D | CSH 50F
CSH 200 – 2000F |
85 x 73 x 70 mm
100 x 106 x 70 mm |
Weight | gr | 360g | |
Environmental Conditions | Indoor Use and altitudes <2000m | ||
Pollution Degree | Pollution Degree 2 | ||
Protection class | IP | IP 20 | |
Housing | Material | ABS UL94-V0 | |
Certifications | Norm | DIN EN 50178, RoHS, UL 61010 |
Copyright of the European Union is effective (Copyright EU) (c) 2024 GENEREX GmbH, Hamburg, Germany, All rights reserved
- TEL +49(40)22692910
- EMAIL info@generex.de
- WEB www.generex.de
(This and all other product datasheets are available for download.)
FAQ
Q: Can the device be used outdoors?
A: No, the device is intended for indoor use only and should not be exposed to outdoor weather conditions.
Documents / Resources
![]() |
GENEREX CSHXXXXF Current Sensor [pdf] Installation Guide CSHXXXXF Current Sensor, CSHXXXXF, Current Sensor, Sensor |