Gamewell ZNS Microprocessor Based Conventional Fire Alarm Control Panel Installation Guide

ZNS Microprocessor Based Conventional Fire Alarm Control Panel

Specifications:

  • Product Name: Gamewell ZNS Microprocessor Based Conventional
    Fire Alarm Control Panel
  • Manufacturer: The Gamewell Company
  • Model Number: ZNS
  • Designed for: Monitoring 2 to 32 conventional initiation zones,
    2 circuits of addressable detection or control devices

Product Usage Instructions:

Installation and Wiring:

Follow the mechanical wiring instructions provided in the manual
for proper installation of the ZNS panel.

Default Operation:

Ensure that the ZNS panel is powered off before making any
connections. Use Gamewell Components for best compatibility and
performance.

Programming:

Refer to the programming section in the manual to set up and
configure the ZNS panel according to your requirements.

Maintenance and Testing:

Regularly test and maintain your ZNS panel as per the guidelines
set by the National Fire Protection Association to ensure optimal
performance and reliability.

Storage of Manual:

Keep the manual stored with the ZNS panel for future reference.
Do not remove it as it provides essential information for operation
and programming.

FAQ:

Q: Can I use non-Gamewell components with the ZNS panel?

A: It is recommended to use Gamewell Components for
compatibility and optimal system performance.

Q: How often should I perform maintenance on the ZNS
panel?

A: Maintenance and testing should be done on a regular basis,
following the guidelines of the National Fire Protection
Association, as a minimum.

“`

ZNS
MICROPROCESSOR BASED CONVENTIONAL FIRE ALARM CONTROL
PANEL
Installation & Operation Manual

The Gamewell Company 60 Pleasant Street Ashland, MA 01721

PROPRIETARY MATERIAL

Part No. 71774 Issue 4 12/4/98

ZNS Installation and Operation Manual

Issue 4 12/4/98

The information contained in this manual is proprietary to The Gamewell Company. Such information and technical drawings may not be copied or reproduced in any manner, or disclosed to organizations that might be competitive to Gamewell, without the express prior written consent of The Gamewell Company.

ZNS Installation and Operation Manual

Issue 4 12/4/98

GENERAL INFORMATION
The Gamewell Company thanks you for choosing the ZNS Microprocessor based fire alarm control panel. As with all our products we have taken great care to insure that we have provided a quality product. To receive maximum benefit and many years of reliable service we would like to make the following recommendations:
1. Read this manual carefully and in it’s entirety before proceeding with the installation of the ZNS panel.
2. Never make any connections with the power connected.
3. Gamewell spends many hours testing devices that are supplied by Gamewell to be used with it’s control panels to verify compatibility. To maximize system performance, and minimize risk of damage to the equipment, we suggest using all Gamewell Components.
4. There is no substitute for proper maintenance and testing of this or any life safety product. Gamewell recommends testing and maintenance of your ZNS in accordance with the guidelines set forth by the National Fire Protection Association, to be done on a regular basis, as a minimum.
5. This manual should be stored with the ZNS panel for future reference, and should not be removed, providing reference to the operation and programming of the installed ZNS
Thank you again for choosing Gamewell. If you have any comments regarding your ZNS panel or other Gamewell products, please feel free to contact us at:
The Gamewell Company Product Marketing Department
60 Pleasant Street Ashland, MA 01721

ZNS Installation and Operation Manual
TABLE OF CONTENTS
Overview Description
INSTALLATION AND WIRING Mechanical Wiring
Common Card Indicators Default Operation Auxiliary Power Programming
Zone Card Indicators Alarm Disconnect Low /High Current Operation Addressing Zone Programming Programming Power Requirements
Appendix A ZNS High Current Compatibility Identifier – 31016 Compatible Notification Devices
Appendix B Drawings

Issue 4 12/4/98
1 1
1 1 1
2 2 2 2 2
2 2 2 2 2 2 3 3
4 4 5
6 6

ZNS Installation and Operation Manual

Issue 4 12/4/98

GAMEWELL ZNS

This manual covers the installation, programming and service of the ZNS and its related modules. It is a supplement to the INS-2 Installation and Programming manuals (P/N’s 70708-05 and 70709-04).

OVERVIEW
Description

The ZNS is a microprocessor based conventional Fire Alarm Control Panel. It is designed to monitor 2 to 32 conventional initiation zones and also allows 2 circuits of addressable detection or control devices. The main control panel consists of an addressable INS-2 system. Addition of an ZNS Common Module provides connection to the conventional zone modules.

INSTALLATION AND WIRING

Mechanical Wiring

Two cabinet sizes are available for the ZNS the smaller is used to house a 2 to 16 zone system and the larger is used on 2 to 32 zone systems. 21″W x 25.5″H x 4″D (1 to 16 zones) 21″W x 31.5″H x 4″D (2 to 32 zones)
The ZNS Common Module (p/n 31014) mounts in place of the INS-2 expander module and plugs into the J5 connector. It is connected to the p/n 31015 Zone Mother Board modules. Each mother board accepts two p/n 31016 two zone Conventional Input Module. Refer to drawings A-M1104, D-M780 and D-M781 for mechanical layout.
Both high or low current zone should be wired in accordance with NFPA 70, article 760. Maximum loop resistance should not excede 25 ohms. Refer to wiring diagram A-W544 for terminations.

1

ZNS Installation and Operation Manual

Issue 4 12/4/98

COMMON CARD

Indicators

The ZNS common card module has one LED. When first powered it flashes the version number of the firmware on the ZNS module. Thereafter it will flash whenever it is responding with zone information to an INS-2 poll.

Default Operation

Default operation is a mode that allows alarms to be sensed and automatically routed to the Signaling Circuits, if for some reason the ZNS controller fails.

Auxiliary Power

Auxiliary power is available on the Common Card from terminals A+, A-. Resetable smoke detector power is available from terminals S+, S-. This power is removed for four seconds when the system is reset. Combined total current available from both A+,A- and S+,S- is 0.5 amps.

Programming

The ZNS Common Card is enabled by accessing level 4 programming area of the INS-2 main board. Press the F1 key until the LED above the F1 key is illuminated.

Output controller location C220 must also be enabled and cannot be used by any other devices. This output controller location allows the ZNS common card to reset the S+, S- output.

ZONE CARD
Indicators Alarm Disconnect Low /High Current Operation
Addressing Zone Programming

Each 2 zone module has two LED’s per zone, one to indicate alarm and the other to indicate trouble. The standard zone module has a red and yellow, the supervisory zone has two yellow LED’s.

Each zone of the 31016 2 zone card has a disconnect switch located next to the LEDs. When this switch is activated, the zone will not report an Alarm, but it will show that it is in Trouble Each zone of the 31016 2 zone card can be programmed for two modes of operation, low current and high current. The module is factory set as a high current zone. Low current mode is selected by removing the following resistors.

Resistors to remove for low current operation.

Odd Zone R1,R2,R3

Even Zone R21,R22,R23

The EOL resistor high current value is 4.7K ohms and the low current value is 15K ohms.

NOTE: Low Current zones will not function with 2-wire Smoke Detectors, and should be used with contact closure devices only.

The 31016 zone modules must be mounted from left to right. If a slot is empty the system will not detect modules beyond the first open slot.

Each 31016 2 zone card has jumpers to distinguish between Class A or Class B initiating circuits. There are also jumpers to program latching and non-latching zones. All 31016 modules are factory set for Class B latching alarm operation. See the chart below for programming options. Refer to drawing A-M1105 For resistor locations.

2

ZNS Installation and Operation Manual

Issue 4 12/4/98

Programming

Programming of the 31016 modules is accomplished with the INS-2 laptop software. Each zone card installed requires 2 addresses regardless of wether both zones are being used or not. The 31016 requires no programming of its address. It is addressed automatically, via the ZNS, by its physical location to the addresses of 1 through 32. Additional addressable modules may be added to the addressable circuits 1 and 2 starting with address 33.

JUMPER PROGRAMMING

Odd Zone

Even Zone

Alarms Latched Alarms Not Latched (Supervisory Alarms Only)

W1L Installed W1L Removed

W2L Installed W2L Removed

Class B Class A

W1A Installed W1A Removed

W2A Installed W2A Removed

Zone cards are shipped with all jumpers installed (Class B, Alarms Latched).

Power Requirements

The ZNS common card draws 2 mA from the +24V supply and 5 mA from the +5V supply.

The 31015 mother boards do not draw any power from the system.

Each 31016 zone card draws 0.5 mA from the +5V supply plus 6.5 mA for each trouble or alarm LED on. Note that for one zone, the trouble and alarm LEDs will never be on at the same time.

The current draw from the +24V supply for each zone on a 31016 zone card depends upon whether it is configured for hi-current or low current operation.

lo-current — without detect lo-current — in alarm

2.5 mA max 6 mA max

hi-current — without detectors hi-current — with detectors hi-current — in alarm

6.5 mA max 9.1 mA max 60 mA max

3

ZNS Installation and Operation Manual

Issue 4 12/4/98

APPENDIX A

ZNS High Current Compatibility Identifier – 31016

Gamewell Model No. 71033 71034 71035
71035-160 71035-210

Detectors Apollo Part No. 55000-350 55000-250 55000-150 55000-151 55000-152

71443

55000-380

Bases

Qty. Gamewell Model No.

Apollo Part No.

71036

45681-200

71086

45681-220

20

71086-LOW

45681-232

71086-GREEN

45681-231

71086-RED

45681-230

71393

45681-227

10

4

ZNS Installation and Operation Manual

Issue 4 12/4/98

Appendix A (Cont)

Compatible Notification Devices

Part # 70871 70873 71138 71140 71287 71288 71289 71290 71292 71293 71294 71295 71426 71427 71543 71544 71545 71546 71547 71548 71549 71550 71551 71552 71553 71554 71555 71556 71557 71558 71559 71560 71561

Catalog # MIZ-24-R MIZ-24-W MT-12/24-R MT-24-WM-VFR MIZ-24-LS-VFR MIZ-24-LSM-VFR MIZ-24-MS-VFR MIZ-24-IS-VFR MT-24 -LS-VFR MT-24-LSM-VFR MT-24-MS-VFR MT-24-IS-VFR MT-24 -SL-VFR MT-24-SLM-VFR AS-2415-VFR AS-241575-VFR AS-2430-VFR AS-2475-VFR AS-24110-HFR SM-12/24-R DSM-12/24-R RS-2415-VFR SR-2415-VFR SRP-2415-VFR RS-241575-VFR SRP-241575-VFR SR-241575-VFR RS-2430-VFR RSP-2430-VFR RSP-2475-VFR RS-2475-VFR RS-24110-HFR SRP-24110-HFR

Part # 71562 71569 71573 71574 71575 71576 71614 71616 71679 71680 71681 71682 71683 71684 71685 71686 71687 71688 71689 71690 71691 71692 71693 71694 71695 71696 71697 71698 71699 71711 71712 71713 71714

Catalog # SR-24110-HFR RSP-241575-VFR AMT-12/24-R AMT-24-LS-VFR AMT-24-IS-VFR AMT-24-LSM-VFR MT4-12/24-R SR-2475-VFR AS-2415W-FR AS-241575W-FR AS-2430W-FR AS-2475W-FR AS-24110W-FR AS-24100C-FW NH-12/24-R NS-2415W-FR NS-241575W-FR NS-2430W-FR NS-2475W-FR NS-24110W-FR RSS-2415W-FR RSS-241575W-FR RSSP-241575W-FR RSSP-2430W-FR RSS-2430W-FR RSSP-2475W-FR RSS-2475W-FR RSS-24110W-FR RSS-24100C-FW AH-24WP-R RS-2415W-FR RS-241575W-FR W3MT-24-VFR

Part # 71717 71727 71728 71729 71730 71731 71732 71733 71736 71737 71738 71739 71740 71741 71742 71743 71744 71745 71746 71747 71748 71749 71750 71751 71752 71758 71759 71760 71761 71762 71763 71764

Catalog # RSSP-24110W-FR AS-2415C-FW AS-2430C-FW AS-2475C-FW RSS-2415C-FW RSS-2430C-FW RSS-2475C-FW RSSP-2415W-FR ET70-2415W-FR ET70-241575W-FR ET70-2430W-FR ET70-2475W-FR ET90-2415C-FW ET90-2430C-FW ET90-2475C-FW ET90-24100C-FW E70-2415W-FR E70-241575W-FR E70-2430W-FR E70-2475W-FR E70-24110W-FR E90-2415C-FW E90-2430C-FW E90-2475C-FW E90-24100C-FW CH90-24-W CH70-24-R CH70-2415W-FR CH70-241575W-FR CH70-2430W-FR CH70-2475W-FR CH70-24110W-FR

5

ZNS Installation and Operation Manual

D-M781 D-M780 A-M1104 A-M1105 D-W1171 A-W544

APPENDIX B
Drawings
Ass’y of ZNS 16 Zones Ass’y of ZNS 32 Zones Mounting Instruction: Card Guide Configuring of 2 – Zone Card Wiring ZNS System Wiring ZNS 2 Zone Card

Issue 4 12/4/98

6

Documents / Resources

Gamewell ZNS Microprocessor Based Conventional Fire Alarm Control Panel [pdf] Installation Guide
71774, ZNS Microprocessor Based Conventional Fire Alarm Control Panel, Microprocessor Based Conventional Fire Alarm Control Panel, Microprocessor Based Conventional Fire Alarm Control Panel, Based Conventional Fire Alarm Control Panel, Conventional Fire Alarm Control Panel, Alarm Control Panel, Control Panel

References

Leave a comment

Your email address will not be published. Required fields are marked *